Electrical connection
Input side [L, N, protective earth conductor]
Connect the input terminals L, N and the protective earth conductor. The protective
conductor must permanently be connected (protection class I).
Do not plug or unplug the connectors when the unit is energized. The installation
must be in compliance with EN 60950, the supply lines must be equipped with
appropriate disconnecting devices (e.g. line safety switches).
For detailed information on stripping length, cable cross-section, torque and input
side protection, please refer to
.
Output side [L+, L+, L-, L-]
Rate the lines for the maximum output current or provide separate fuse protection.
For details on the output side fuse protection, please refer to
of the power supply units. To minimize voltage drops, a maximum cable cross-
section should be selected.
Do not plug or unplug the connectors when the unit is energized. The power supply
units are overload proof, short-circuit proof and no-load proof. The secondary
power supply unit side is galvanically isolated from the input and not internally
earthed (SELV). It can be earthed by the user (either L+ or L-), if required (PELV).
Summary of Contents for AC 900F
Page 2: ......
Page 3: ...Freelance 2016 Mounting and Installation Instructions AC 900F Controller ...
Page 58: ...CP C MM messaging module Section 3 Modules 58 M I AC 900F Controller ...
Page 70: ...TB 870F terminal block Section 4 Accessories 70 M I AC 900F Controller ...
Page 122: ...Update Restore Section 8 Service 122 M I AC 900F Controller ...
Page 152: ...CP A CM Section 9 Technical Data 152 M I AC 900F Controller ...
Page 154: ...Index 154 M I AC 900F Controller ...
Page 155: ......