Section 9 Technical Data
CP-C RU
M&I – AC 900F Controller
145
CP-C RU
Application
Input (+) and (-)
L+ and L
-
outputs
Mechanical data
Electrical connection
CP-A RU
Redundancy unit
Rated voltage
24 V DC
Voltage range
10 - 40 V AC
Rated current per channel
1 - 20 A
Peak current per channel
30 A for 300 s
Protection against transient overvoltage Yes
Rated voltage
24 V DC
Rated current at Ta < 60 °C
1 - 40 A
Current derating at 60 °C < Ta
≤
70 °C
- 2.5% per K temperature increase
Peak current
60 A for 300 s
Energy recovery resistance
< 40 V
Voltage drop
typ. 0.6 W
Dimensions W x H x D
60 x 130 x 137 mm
Weight
0.89 kg
Installation
DIN rail
Mounting position
Horizontal
Minimum distance between devices
> 10 mm horizontal, > 50 mm vertical
Type of protection
IP 20
Wire size
Finely stranded with wire end
errule
2.5 - 10 mm
2
Finely stranded without wire
end ferrule
0.5 - 10 mm
2