Thin Cable
Section 2 Transmission Media and Components
28
9ARD000015-600
The electric current is computed using the formula:
I = 4.65V / ((Cable DCR * Length of Network) +
(Contact DCR * Number of Contacts)).
Where, Cable DCR = 0.00445 ohms/ft, Contact DCR = 0.001 ohms, and Number of
Contacts = 128 (because each tap has two contacts in series). The Cable DCR is
determined using an ambient of 80
°
C, and temperature coefficient of
0.00393 per
°
C.
Thin Cable
shows the physical configuration of Thin cable.
provides the various specifications of Thin cable and their corresponding
table numbers.
Figure 8. Thin Cable Physical Configuration
Table 14. Specifications of Thin Cable and their Corresponding Table Numbers
Characteristics
Table Number
Data Pair Specification
Physical