Thin Cable
Section 2 Transmission Media and Components
32
9ARD000015-600
lists the topology details of Thin cable.
Bend Radius
20 x diameter (installation) / 7 x diameter
(fixed)
Operating ambient temperature
-20° C .. +70° C @ 1.5 amps; de-rate electric
current linearly to zero @ 80° C
Storage temperature
-40° C .. +85° C
Pull tension
65 lbs maximum
Connector Compatibility
Mini, Micro, Open
Topology Compatibility
Trunk, Drop
Table 22. Thin Cable Topology
Data Rate
Max
Cable
Distance
Trunk
Exchange
(Thick Cable)
Cumulative
Drop
Maximum Drop
125 kb
100 m (328 ft)
5.0
156 m (512 ft)
6 m (20 ft)
250 kb
100 m (328 ft)
2.5
78 m (256 ft)
6 m (20 ft)
500 kb
100 m (328 ft)
1.0
39 m (128 ft)
6 m (20 ft)
Table 21. Environmental Characteristics of General Specification for Thin Cables (Continued)
Applicable Environmental
Characteristics
Specification