Optigo OP10 user manual
Chapter 3
Technical data
9
Outputs
AO.................................................................... 0…10 V DC; 8 bit D/A short-circuit protected
DO1 and DO2 (OP10)........... Triac controlled, 24 V AC, 0.5 A continuous (connected to G0)
DO1 and DO2 (OP10-230).. Triac controlled, 24 V AC, 0.16 A continuous with internal trafo
............................................... (connected to G0)
DO3............................................................... Change-over (SPDT) relay 230 V AC, 1000 VA
G
DO
....................................................................Reference for DO1 and DO2. 24 V AC output
Other data
Display ............................................................... Numeric / graphic. Background illumination
Setpoints
Range Factory
setting
Temperature
supply air
room
tap hot water
10...80°C
10...50°C
10…80°C
21°C
21°C
55°C
P-band 0…99°C
15°C
I-time
0…990 s
60 s
D-factor 0…99
0
Cascade factor
0…99
2
Minimum at cascade
0…99°C
15
Maximum at cascade
0…99°C
25
Damper minimum limit
0…99
10
Start of outdoor compensation
-30…50°C
10°C
Outdoor compensation at -20°C outdoor temp
-10…10°C
5°C
Supply temperature (water-heated radiator heating)
at -20°C outdoor temperature
at 20°C outdoor temperature
0…99°C
0…99°C
60°C
20°C
Frost protection
7°C (fixed)
Shutdown mode
25°C (fixed)
Accessories
Temperature sensors...............PT1000 sensors, for example:TG-R5/PT1000, TG-KH/PT1000
Casing..............................................................................................................................EK216
The accessories are available from Regin. For more detailed information, see product sheets
and instructions which are available at