Pump exercise
If the pump stands still for prolonged periods during the summer there is the risk of the pump
impeller seizing. To reduce this risk the Optigo has a pump exercise function which will start
and run the pump for 5 minutes at 15:00 each day. In this menu the exercise function can be
turned Off if not desired. Default is On.
Periodic overheating
To reduce the risk of Legionella bacteria growth a periodic overheating of the water can be
configured. The water temperature will be raised to 65°C once daily at 03:00 (3 am). The
elevated temperature is maintained for 10 minutes. In this menu the overheating function can
be turned Off if not desired. Default is On
Menus X.8
Startpoint for outdoor compensation, S.P (Control mode
2)
Supply air min limit (Control mode 3)
Low temperature setpoint (Control mode 4)
For control mode 2. S.P is the outdoor temperature at which the setpoint compensation starts.
At temperatures lower than S.P a compensation will be added to the setpoint value. The
maximum compensation is set in menu 2.9 and is achieved at -20°C
For control mode 3 the supply air temperature can be minimum and maximum limited. In
this menu you set the minimum supply air temperature.
For control mode 4 you need to establish a relationship between outdoor temperature and
supply water temperature. This is set by the two setpoints SP
L
and SP
H
where SP
L
is the
water temperature to be held at an outdoor temperature of +20°C and SP
H
is the water
temperature to be held at -20°C. Intermediate values are calculated with linear interpolation.
In this menu you set SP
L
.