Optigo OP10 user manual
Chapter 10
Configuration
32
0°C temperature boost
In control mode 4 an extra temperature boost can be added at 0°C outdoor temperature. The
boost recedes from the set value to 0 over ±3 degrees.
Supply temp
Outdoor temp
SP
H
SP
L
-20
0
+20
D-factor
Control mode 5, Domestic hot water temperature control is often a very difficult application
which calls for responsive control. Optigo therefore utilises PID-control for this control
mode. In this menu you set the D-factor.
Menus X.7
Universal input UI1 (Control modes 1, 2, 3)
Pump exercise (Control mode 4)
Periodic overheating (Control mode 5)
Input UI1
For control modes 1, 2 and 3 you can choose to configure the universal input UI1 as either an
analogue input for a frost protection sensor on either output (snowflake-symbol) in a water-
heated system or as a digital input for a high temperature limiting switch (sun-symbol) in an
electric heater. It can also be set to --, not active.
If set to frost protection sensor Optigo will activate the frost protection function and also
shutdown mode, see chapter 5.
If set to high temperature limit switch, the fan will run for an extra 3 minutes after the
heating output has been turned off at shutdown.
Frost protection on AO1
Frost protection on AO2