Optigo OP10 user manual
Chapter 4
Installation and wiring
10
Chapter 4 Installation and wiring
Installation
Optigo is intended to be installed and handled by professional personnel.
The installation should conform to the requirements of installation category 3 and pollution
degree 2.
There are a number of mounting alternatives:
-
DIN-standard casing (minimum 7 modules)
-
Cabinet, either on a DIN-rail or, using the two screw-pockets provided, by being
screwed to any suitable flat surface in the cabinet
-
The controller can also be mounted in a cabinet door or other control panel, using a
suitable front-mounting kit
For installations which are connected to 230 V AC:
-
Observe that there is a risk of electric shock on contact with terminals 1-3 and 10-12.
-
Mount Optigo in a DIN-casing or similar where it can be used without risk of electric
shock. The casing should provide at least 6 mm insulation from connected cables and
terminals 1-3 and 10-12.
-
Optigo should be protected against overload by a fuse in the installation. Since the
maximum load is 1000 VA, a fuse of 6 A is suitable.
-
Circuit breaker and fuse: The controller should be connected to a circuit breaker so the
power supply to the controller can be cut. Place this breaker close to the controller where
it is easy for the operator to reach. It should be clearly marked as a circuit breaker for the
controller.