74
3.
Connect the shortened belt ends by
inserting the protruding tongue through
the hole of the other half of the belt.
4.
Grab the second tongue and similarly
insert it through the second hole – this
time use the pliers to drag the segment
tongue easier and twist it back to the
starting position.
5.
Your belt is now shortened and the
tension of the belt is increased.
Polymer Energy Recovery Wheel
This section is provided to assure the polymer
energy recovery feature will be properly
setup to perform in accordance with the job
specifications for your particular application.
Figure 35 - Polymer Energy Recovery Wheel
1.
Removable Segment
2.
Permanent Tension Belt
3.
Pulley
4.
Embedded Segment Stiffeners
5.
Segment Retaining Latches
6.
Bearing Beam and Bearing Access
Cover Plate (Diameter Seals are behind
Bearing Beam on both sides)
7.
Adjustable Purge
8.
Motor
The Energy Recovery Cassette consists of a
frame wheel, wheel drive system, and energy
transfer segments. Segments are removable
for cleaning or replacement. The segments
rotate through counter flowing exhaust and
outdoor air supply streams where they
transfer heat and/or water vapor from the
warm, moist air stream to the cooler and/or
drier air stream.
The initial setup and servicing of the energy
recovery wheel is very important to maintain
proper operation efficiency and building
occupant comfort.
Normal
maintenance
requires
periodic
inspection of filters, the cassette wheel, drive
belts, air seals, wheel drive motor, and its
electrical connections.
Wiring diagrams are provided with each
motor. When wired according to wiring
diagram, motor rotates clockwise when
viewed from the shaft/pulley side.
By carefully reviewing the information
within this section and following
the
instructions, the risk of improper operation
and/or
component
damage
will
be
minimized.
It is important that periodic maintenance be
performed to help assure trouble free
operation.