40
Variable Speed Compressors
Variable speed compressors with VFD speed
control are standard on RZ Series units .
Variable speed compressors must not be
operated outside the factory determined
turndown ratio or frequency range. The
factory determined compressor VFD ranges
are given in the following table.
Table 5 - RZ Variable Speed Compressor
VFD Frequency Range
Model (RZA-)
Air Cooled / Evap Cond
Compressor
VFD Range
(Hz)
45 / 51
25-73 Hz
55 / 66
25-74 Hz
65 / 73
25-92 Hz
75 / 79
25-94 Hz
90 / 101
25-85 Hz
105 / 109
25-100 Hz
120 / 124
25-100 Hz
130 / 136
25-88 Hz
140 / 148
25-100 Hz
145 / 161
25-95 Hz
160 / 172
25-80 Hz
180 / 197
25-98 Hz
200 / 221
25-76 Hz
220 / 241
25-88 Hz
240 / 261
25-92 Hz
Scroll compressors are directional
and will be damaged by operation in
the wrong direction. Low pressure
switches on compressors have been
disconnected after factory testing.
Rotation must be checked by a
qualified service technician at startup
using suction and discharge pressure
gauges and any wiring alteration must
only be made at the unit power
connection.
No variable speed compressor shall
operate below 25 Hz. Operating
variable speed compressors outside
the frequency range specified in this
manual voids all warranties and may
result in compressor failure.
CAUTION
CAUTION