![AAON RQ NextGen Series Installation Operation & Maintenance Download Page 99](http://html2.mh-extra.com/html/aaon/rq-nextgen-series/rq-nextgen-series_installation-operation-and-maintenance_5032934099.webp)
99
Appendix B - Thermistor Temperature vs. Resistance Values
Deg C Deg F Resistance (kOhms)
-40
-40
2889.6
-35
-31
2087.22
-30
-22
1522.20
-25
-13
1121.44
-20
-4
834.72
-15
5
627.28
-10
14
475.74
-5
23
363.99
0
32
280.82
5
41
218.41
10
50
171.17
15
59
135.14
20
68
107.44
25
77
86.00
30
86
69.28
35
95
56.16
40
104
45.81
45
113
37.58
50
122
30.99
55
131
25.68
60
140
21.40
65
149
17.91
Deg C Deg F Resistance (kOhms)
70
158
15.07
75
167
12.73
80
176
10.79
85
185
9.20
90
194
7.87
95
203
6.77
100
212
5.85
105
221
5.09
110
230
4.45
115
239
3.87
120
248
3.35
125
257
2.92
130
266
2.58
135
275
2.28
140
284
2.02
145
293
1.80
150
302
1.59
155
311
1.39
160
320
1.25
165
329
1.12
170
338
1.01
175
347
0.92
180
356
0.83
Summary of Contents for RQ NextGen Series
Page 2: ......
Page 26: ...26 Figure 3 RQ Cabinet Standard and Power Exhaust Gasket Locations...
Page 40: ...40 Figure 23 Post Corner Hole Piping Figure 24 Post Back Hole Piping...
Page 88: ...88 Gas Heater Operating Instructions Figure 36 Gas Heater Instructions...
Page 95: ...95...
Page 96: ...96...
Page 105: ...105 Maintenance Log E Coated Coil...
Page 107: ...107...