Input/Output Configuration
Relay Output
Relay Output Description
Type (User Config.)
Rated 1 A @ 24 VAC)
RLY1
RLY2
RLY3
RLY4
RLY5
RLY6
RLY7
RLY8
Analog Output Analog Output Description
Type (User Config.)
AOI
AO2
AO3
AO4
1.) The Relay Outputs are user configurable via computer with Prism software installed for on above/off below, on above/on below,
off above/on below, off above/off below, follow an active binary input on the controller, follow an inactive binary input on the
controller, follow a relay output on the controller, follow a schedule, ventilation control, as a lead relay for lead/lag control and as a
lag relay for lead/lag control.
2.) The Analog Outputs are user configurable via computer with Prism software installed. The output is adjustable between 0 VDC
to 10 VDC range for direct acting floating point control, reverse acting floating point control, direct acting P.I.D. control and reverse
acting P.I.D. control.
Notes
:
www.az2controls.com
GPC-XP Controller - Configuration Worksheet
Project Name:
_________________________________________________________________________________
WattMaster Controls Inc.
Phone: 816-505-1100
8500 NW River Park Drive
Fax: 816-505-1101
Parkville, Mo 64152
Toll Free: 866-918-1100
System Pump 1 (Lead System Pump For Lead/Lag)
Lead Rly - Lead/Lag
System Pump 2 (Lag System Pump For Lead/Lag)
Lag Rly - Lead/Lag
TW Spray Pump (Cooling Tower Spray Pump)
On Above/Off Below
Tower Fan (Cooling Tower Fan)
On Above/Off Below
Cool Bypass Valve (Cooling Tower Bypass Valve)
On Above/Off Below
Boiler Enable (Boiler Loop Enable)
Off Above/On Below
Request To Run (Request For System To Run)
Follow Active BI
System Active (WSHP Loop Is Active)
Follow Inactive BI
Tower Fan VFD (Tower Fan Variable Frequency Drive)
DA Floating Point
System Pump VFD (System Pump Variable Frequency Drive)
RA Floating Point
Mod Cooling (Modulating Cooling
DA Floating Point
Mod Heating
RA Floating Point
Figure 42: GPC-XP Configuration Worksheet Page 2 Of 2 For WSHP Loop Controller