Configuration
Configuring The Controller
WattMaster Controls
AZ2-GPC-XP-Config-1A.doc
Page 1 of 2
Prepared By:
___________________________________________________
Date:
_______________________
Project Name:
_______________________________________________________________________________
Project Location:
____________________________________________________________________________
____________________________________________________________________________
____________________________________________________________________________
____________________________________________________________________________
Contact: ________________________________ GPC-XP #
_______
of _
_______
GPC-XP Address
________
Input/Output Configuration
Binary Input Binary Input Description
Type (24 V Contact)
BIN1
BIN2
BIN3
BIN4
BIN5
BIN6
BIN7
BIN8
Analog Input Analog Input Description
Type (User Config.)
AI1
AI2
AI3
AI4
AI5
AI6
AI7
AI8
1.) The Binary Inputs require 24 VAC power to the input when used. They are user configurable via computer with Prism software
installed for N.O. or N.C. operation, a global binary signal from another controller, a push-button override or to follow another relay
on the controller.
2.) The Analog Input signals are user selectable by moving a jumper on the controller. Available signals are 0-5 VDC, 0-10 VDC, 4-
20 mA, or Thermistor Type III. They are user configurable via computer with Prism software installed to read in Farhenheit or
Celsius, configured to read a wall mounted sensor with slide offset, a communicating (E-BUS) temperature sensor, a
communicating (E-BUS) CO2 sensor, a communicating (E-BUS) humidity sensor or a global analog signal broadcast from another
controller.
www.az2controls.com
GPC-XP Controller - Configuration Worksheet
Click The Box On The Right To Download The Latest Version Of Adobe Acrobat.
WattMaster Controls Inc.
Phone: 816-505-1100
8500 NW River Park Drive
Fax: 816-505-1101
Parkville, Mo 64152
Toll Free: 866-918-1100
Request To Run (Request For Water Loop System To Run)
System POF (System Proof Of Water Flow)
N.C. Operation
N.O. Operation
Boiler POF (Boiler Water Loop Proof Of Flow)
Emergency Shutdown (Emergency WSHP Loop Shutdown)
N.O. Operation
Spray Pump POF (Tower Spray Pump Proof Of Water Flow)
N.O. Operation
Boiler Alarm (Boiler Generated Alarm)
N.O. Operation
Not Used
Not Used
N.C. Operation
OSA Temp (Outside Air Temperature)
Therm. Type III - F
TW Supply Water (Tower Supply Water Temperature)
Therm. Type III - F
TW Return Water (Tower Return Water Temperature)
Therm. Type III - F
Loop Pressure (System Loop Water Pressure)
0-5 VDC
Boiler Loop Temp (Boiler Loop Water Temperature)
Therm. Type III - F
OSA Humidity (Outside Air Humidity)
0-5 VDC
Sump Temp (Tower Sump Water Temperature)
Therm. Type III - F
Not Used
Figure 41: GPC-XP Configuration Worksheet Page 1 Of 2 For WSHP Loop Controller
38
WSHP Loop Controller
GPC-XP Guide