www.a-ts.cn A-TS Technology
FT50
53
Start
P0214.F=3
P0201.F=?
P0206.F=50
P0204.F=50
P0205.F=-50
P1602.F=20
P1603.F=20
P0401.M=?
P0402.M=?
P0403.M=?
P0404.M=?
P0405.M=?
P0406.M=?
P0412.M=?
Start quick commissioning
Access level
0: User level 1: Standard level
2: Advanced level 3: Expert level
Frequency converter model
Before leaving the factory, the model parameter of the frequency converter has been
set to the default value according to the complete machine, and the user does not
need to modify it. Set value range
:
6(2.2kw) - 29(355kw)
Reference frequency (Hz)
Set the benchmark for both internal calculation and percentage of the
given frequency, generally set it to 50Hz.
Upper frequency limit(
Hz)
Set the upper output frequency limit of the frequency converter.
Set value range: P0205.F-P0206.F*2
Lower frequency limit (Hz)
Set the lower output frequency limit of the frequency converter.
Set value range: -(P0206.F)*2-P0204.F*2
Acceleration time (s)
It defines the time required for the ramp function to accelerate from 0Hz to
the
frequency converter reference frequency (P0206.F).
Setting value range: 0.0-1200.0s
Deceleration time (s)
It defines the time required for the ramp function to decelerate from the
frequency converter reference frequency (P0206.F) to 0Hz.
Setting value range: 0.0-1200.0s
Motor rated power (kW)
Set as per the motor rated power on the nameplate
Motor rated voltage (V)
Set as per the motor rated voltage on the nameplate
Motor rated current (A)
Set as per the motor rated current on the nameplate
Motor rated frequency(
Hz)
Set as per the motor rated frequency on the nameplate
Motor rated speed (r
pm)
Set as per the motor rated speed on the nameplate
Number of motor pole pairs
Set the number of motor pole pairs.
For example, the number of pole pairs of a 4-pole motor is 2.
Motor power factor
Set as per the motor power factor on the nameplate
P0224.F=?
Load type selection
0: High overload
1: Low overload