Overload in off grid mode. •
Please check if the eps load power exceeds the limit. • Or
seek for help from us.
Bat Power
Low
Iso Fault
The battery power is low. •
Wait the battery to be recharged. • Or
seek for help from us.
HW Bus Vol
Res Cur Fault
Bus voltage out of range detected by hardware. •
Disconnect PV, grid and battery, then reconnect. • Or
seek help from us, if not go back to normal state.
Fault
PV Volt Fault
PV input current high detected by hardware. •
Disconnect PV, grid and battery, then reconnect. • Or
seek help from us, if not go back to normal state.
The isolation has failed.
• Please check if the insulation of electrical wires is damaged. • Wait
for a while to check if back to normal. • Or seek
for help from us.
HW Pv Cur
SW PV Cur
Over Load
The residual current is high. •
Please check if the insulation of electrical wires is damaged. • Wait
for a while to check if back to normal. • Or seek
for help from us.
Fault
Fault
Fault
PV voltage out of range. •
Please check the output voltage of PV panels. • Or
seek for help from us.
Temp fault
EPS Over
PV input current high detected by software. •
Disconnect PV, grid and battery, then reconnect. • Or
seek help from us, if not go back to normal state.
Ground Fault
Load
Over load in on grid mode. •
Please check if the load power exceeds the limit. • Or
seek for help from us.
The inverter temperature is high. •
Please check if the environment temperature. • Wait
for a while to check if back to normal. • Or seek
for help from us.
The ground connection failed. •
Check the voltage of neutral and PE. •
Check AC wiring. •
Disconnect PV, grid and battery, then reconnect. • Or
seek help from us, if not go back to normal state.