Water composition
Hardness
(alkaline earth ions)
> 1.00 mmol/l:
- German hardness > 5.6° dH
- French hardness > 10.0° fH
- British hardness > 7.0° eH
Conductivity
> 125 muS/cm
Acidity (pH-value)
7.0 < pH-value < 9.5
3.3.1 Air humidity and ambient temperature
The installation area should be frost-free or be protected against frost. The
table gives the ambient conditions that shall be observed in order to be able to
ensure the functioning of the applied electronics.
Speci
fi
cations for air humidity and ambient temperature
3.3.2 Maximum fl oor loading
In view of the weight of the device, take the maximum
fl
oor loading into
account. See the table below.
Speci
fi
cation for weight in connection with the maximum
fl
oor loading
3.3.3 Water composition
The device is designed for heating drinking water. The drinking water shall
comply with the regulations for drinking water for human consumption. The
table gives an overview of the speci
fi
cations.
Speci
fi
cations for water
Remark
When the speci
fi
cations mentioned in the table are deviated from, the
protection of the tank can not be guaranteed
(11 “Warranty (certi
fi
cate)”)
.
3.3.4 Working area
In view of the accessibility of the device, it is recommended to apply the
following distances (see
fi
gure):
•
AA: on the front side of the device: 100 cm.
•
BB: around the device: 50 cm.
•
Top side of the device: 50 cm.
Installation
3
Air humidity and ambient temperature
Air humidity
max. 93% RH at +25°C
Ambient temperature
Functional: 0
≤
t
≤
60°C
Weight of the device fi lled with water
TWI 35-130
199 kg
TWI 45-190
271 kg
Summary of Contents for TWI 35-130
Page 2: ...www aosmithinternational com your installer...
Page 3: ...Instruction manual TWI 35 130 G TWI 45 190 G 1...
Page 4: ...2 Instruction manual TWI 35 130 G TWI 45 190 G...
Page 6: ...4 Instruction manual TWI 35 130 G TWI 45 190 G...
Page 25: ...Instruction manual TWI 35 130 G TWI 45 190 G 23 Device types IMD 0531 R0...
Page 36: ...34 Instruction manual TWI 35 130 G TWI 45 190 G 4 Conversion to another gas category...
Page 44: ...42 Instruction manual TWI 35 130 G TWI 45 190 G 8 Shut down...
Page 58: ...56 Instruction manual TWI 35 130 G TWI 45 190 G Annex 12...
Page 61: ...Instruction manual TWI 35 130 G TWI 45 190 G 59...
Page 62: ...60 Instruction manual TWI 35 130 G TWI 45 190 G 0308 489 R1 0...