Bear in mind that the total weight of the installation always comprises a water heater
complete with storage tank (completely filled with water). This maximum floor load may
be between 400 and 4500 kg. This depends on the type of storage tank.
7.2.3
Water composition
The water must comply with the regulations for drinking water for human consumption.
Water composition
Hardness
(alkaline earth ions)
> 1.00 mmol/l:
German hardness > 5.6° dH
French hardness > 10.0° fH
English hardness > 7.0° eH
CaCO
3
> 100 mg/l
•
•
•
•
Conductivity
> 125 µS/cm
Acidity (pH value)
7.0 < pH value < 9.5
Note
If the water specifications differ from the specifications in the table, the tank protection
cannot be guaranteed, refer to Warranty.
7.2.4
Working clearances
For access to the water heater, it is recommended that the following clearances are
observed (see figure):
AA: around the water heater's control column and cleaning openings: 100 cm.
BB: all sides of the water heater: 50 cm.
Top of the water heater: 100 cm.
Fig. Working clearances
SGS 28 - 60
Fig. Working clearances
SGS 80 - 120
A
A
AA
B
B
B
B
A
A
AA
Note
When installing the water heater, be aware that any leakage from the tank and/or
connections can cause damage to the immediate environment or floors below the level of
the boiler room. If this is the case, the water heater should be installed above a waste
water drain or in a suitable metal leak tray.
Note
The leak tray must have an appropriate waste water drain and must be at least 5 cm
deep with a length and width at least 5 cm greater than the diameter of the water heater.
n
•
•
•
n
54
Installation, Maintenance and Service part
Summary of Contents for SGS-28
Page 6: ...6 ...
Page 13: ...User part 0311753_SGS_28 120_II_UKUK_V2 0 2017 05 03 13 ...
Page 14: ...14 ...
Page 16: ...16 User part ...
Page 18: ...18 User part ...
Page 24: ...24 User part ...
Page 40: ...40 User part ...
Page 41: ...Installation Maintenance and Service part 0311753_SGS_28 120_II_UKUK_V2 0 2017 05 03 41 ...
Page 42: ...42 User part ...
Page 82: ...82 Installation Maintenance and Service part ...
Page 90: ...90 Installation Maintenance and Service part ...
Page 104: ...104 Installation Maintenance and Service part ...
Page 110: ...Fig Dimensions SGS 28 30 50 60 110 Installation Maintenance and Service part ...
Page 112: ...Fig Dimensions SGS 80 100 120 112 Installation Maintenance and Service part ...
Page 121: ...12 8 Declaration of conformity 0311753_SGS_28 120_II_UKUK_V2 0 2017 05 03 121 ...
Page 124: ...124 Installation Maintenance and Service part ...
Page 126: ...126 Installation Maintenance and Service part ...