Indication
Cause
Measure
Insufficient or no hot
water
The water heater is off.
Turn on the water heater (see section 4.1).
There is no supply voltage.
Make sure that:
the control switch is set to I.
the isolator is in ON position.
there is power on the isolator.
there is power to the electrical connector
block.
The measured voltage must be
230 V
AC
(-15%, +10%).
•
•
•
•
The hot water supply is used up.
Reduce the hot water consumption. Wait
until the water heater heats up.
The controller is in the OFF mode.
Set the controller in the ON mode.
The temperature (T
set
) is set too low.
Set the temperature (T
set
) to a higher value.
Glycol leakage
Leakage from a fluid connection
(threaded)
Tighten the threaded connection.
Leakage from a component
Tighten component joints
Any defective components must be
replaced
1.
2.
Leakage from solar heating system
Consult the supplier and/or manufacturer
11.1.2
Displayed errors
Note
For the coding of the connections, refer to the Electrical wiring diagram.
Note
Contact your service and maintenance engineer if the error persists.
Code and description
Cause
Measure
S01 (blocking error)
Open circuit from
temperature sensor T
2
at
the bottom of the tank.
Sensor is not (correctly) connected
Connect the sensor lead to JP3
Damaged cable and/or defective sensor
Replace the cable and/or sensor
S02 (blocking error)
Open circuit from sensor 1
of temperature sensor T
1
at the top of tank
(1).
Sensor is not (correctly) connected
Connect the sensor lead to JP5
Damaged cable and/or defective sensor
Replace the cable and/or sensor
S03 (blocking error)
Open circuit in sensor 2 of
temperature sensor T
1
at
the top of the tank
(1)
.
Sensor is not (correctly) connected
Connect the sensor lead to JP5
Damaged cable and/or defective sensor
Replace the cable and/or sensor
S04 (blocking error)
Open circuit from
dummy 1.
Dummy is not (correctly) connected
Connect the dummy sensor (dummy sensor
1 and 2) leads to JP4.
Defective dummy
Replace the dummy sensor
S05 (blocking error)
Open circuit from
dummy 2
Dummy is not (correctly) connected
Connect the dummy sensor (dummy sensor
1 and 2) leads to JP4.
Defective dummy
Replace the dummy sensor
n
0311753_SGS_28-120_II_UKUK_V2.0 , 2017-05-03
97
Summary of Contents for SGS-28
Page 6: ...6 ...
Page 13: ...User part 0311753_SGS_28 120_II_UKUK_V2 0 2017 05 03 13 ...
Page 14: ...14 ...
Page 16: ...16 User part ...
Page 18: ...18 User part ...
Page 24: ...24 User part ...
Page 40: ...40 User part ...
Page 41: ...Installation Maintenance and Service part 0311753_SGS_28 120_II_UKUK_V2 0 2017 05 03 41 ...
Page 42: ...42 User part ...
Page 82: ...82 Installation Maintenance and Service part ...
Page 90: ...90 Installation Maintenance and Service part ...
Page 104: ...104 Installation Maintenance and Service part ...
Page 110: ...Fig Dimensions SGS 28 30 50 60 110 Installation Maintenance and Service part ...
Page 112: ...Fig Dimensions SGS 80 100 120 112 Installation Maintenance and Service part ...
Page 121: ...12 8 Declaration of conformity 0311753_SGS_28 120_II_UKUK_V2 0 2017 05 03 121 ...
Page 124: ...124 Installation Maintenance and Service part ...
Page 126: ...126 Installation Maintenance and Service part ...