background image

6

CLOSED WATER SYSTEM

A closed system will exist if a back-flow preventer (check valve),
pressure reducing valve, or other similar device is installed in the cold
water line between the water heater and the street main (or well).
Excessive pressure may develop due to the thermal expansion of heated
water causing premature tank failure or intermittent relief valve operation.
This type of failure is  not covered by the limited warranty.  An expansion
tank may be necessary in the cold water supply to alleviate this situation.
Contact the local plumbing authority.

If the temperature and pressure relief valve on the appliance discharges
periodically, this may be due to thermal expansion in a closed water
supply system.  Contact the water supplier or local plumbing inspector
on how to correct situation.  DO NOT PLUG THE TEMPERATURE AND
PRESSURE RELIEF VALVE.

RELIEF VALVE

A NEW TEMPERATURE AND PRESSURE RELIEF VALVE COMPLYING WITH
THE STANDARD FOR RELIEF VALVES AND AUTOMATIC GAS SHUT OFF
DEVICES FOR HOT WATER SUPPLY SYSTEMS, ANSI Z21.22 (LATEST
EDITION) MUST BE INSTALLED IN THE HEATER IN THE MARKED OPENING
PROVIDED.  THE VALVE MUST BE OF A SIZE (INPUT RATING) THAT
WILL BE ADEQUATE FOR YOUR SIZE HEATER.

Check the metal tag on the relief valve and compare it to the heater’s
rating plate.  The pressure rating of relief valve must not exceed the
working pressure shown on the rating plate of the heater.  In addition
the hourly Btu rated temperature steam discharge capacity of the relief
valve shall not be less than the input rating of the heater.  

NO VALVE IS

TO BE PLACED BETWEEN THE RELIEF VALVE AND TANK.  DO NOT PLUG
THE RELIEF VALVE.

The drain line connected to this valve must not contain a reducing coupling
or other restriction and must terminate near a suitable drain to prevent
water damage during valve operation.  The discharge line shall be installed
in a manner to allow complete drainage of both the valve and line. 

DO

NOT THREAD, PLUG OR CAP THE END OF THE DRAIN LINE.

VENTING

 

 WARNING

THE INSTRUCTIONS IN THIS SECTION ON VENTING MUST BE FOLLOWED
TO AVOID CHOKED COMBUSTION OR RECIRCULATION OF FLUE GASES.
SUCH CONDITIONS CAUSE SOOTING OR RISKS OF FIRE AND
ASPHYXIATION. NEVER OPERATE THE HEATER UNLESS IT IS VENTED
TO THE OUTDOORS AND HAS ADEQUATE AIR SUPPLY TO AVOID RISKS
OF IMPROPER OPERATION, FIRE, EXPLOSION OR ASPHYXIATION.

VENT PIPE TERMINATION

The first step is to determine where the vent pipe will terminate.  The
vent may terminate through the roof (see Figure 9) or through a sidewall
(see Figure 8).

IMPORTANT

The vent system must terminate so that proper clearances are maintained
as cited in local codes or the latest edition of the National Fuel Gas Code,
ANSI Z223.1, 7.3.4e and 7.8a, b.

For your convenience instructions on proper installation through a
sidewall are provide in Figure 3 and the numbered points below:

1. The exit terminals of a mechanical vent system shall be not less than

7 feet above grade when located adjacent to public walkways.

2. A venting system shall terminate at least 3 feet above any forced air

inlet located within 10 feet.

3. The venting system shall terminate at least 4 feet below, 4 feet

horizontally from or, 1 foot above any door, window or gravity air
inlet  into any building.

4. The manufacturer also recommends that the vent system termination

not be installed closer than 3 feet from an inside corner of an L shaped
structure and not be less than 1 foot above grade.  The vent shall
terminate a minimum of 12'' above expected snowfall level to prevent
blockage of vent termination.

CAUTION: IF BUILDING COLD WATER SUPPLY HAS A BACK-FLOW
PREVENTER, CHECK VALVE OR WATER METER WITH CHECK VALVE,
PROVISIONS FOR THERMAL EXPANSION OF WATER IN THE HOT WATER
SYSTEM MUST BE PROVIDED.

FIGURE 2

CIRCULATING RETURN LINE CONNECTIONS
TEMPERED WATER LOOP, IF USED, CONNECT TO POINT "A".  STORED
TEMPERATURE WATER LOOP, IF USED, CONNECT TO COLD WATER INLET

 WARNING

TEMPERATURE SETTING SHOULD NOT EXCEED SAFE USE
TEMPERATURE AT FIXTURES.  SEE TEMPERATURE REGULATION
ON PAGE 9.   IF HIGHER PREHEAT TEMPERATURES ARE
NECESSARY TO OBTAIN ADEQUATE BOOSTER OUTPUT, ADD AN
ANTI-SCALD VALVE FOR HOT WATER SUPPLIED TO FIXTURES.

SINGLE TEMPERATURE

MIXING VALVE APPLICATION FOR TWO TEMPERATURE WATER

Summary of Contents for BTF-75

Page 1: ...Y BEFORE INSTALLING AND USING THIS APPLIANCE A DIVISION OF A O SMITH CORPORATION McBee South Carolina U S A Stratford Ontario Canada www hotwater com KEEP THIS MANUAL IN THE POCKET ON THE HEATER FOR F...

Page 2: ...tions and the local code authority having jurisdiction In the absence of local codes the installation must comply with the latest editions of the National Fuel Gas Code ANSI Z223 1 NFPA 54 The NFPA Th...

Page 3: ...ral gas models A natural gas heater will not function safely on LP gas and no attempt should be made to convert a heater from natural gas to LP gas LP gas must be used with great caution It is highly...

Page 4: ...in before operating Please refer to manufacturer s instructions DISHWASHING MACHINE REQUIREMENT These appliances meet the National Sanitation Foundation Standard for sanitary installations when used w...

Page 5: ...60 75 percent for metal grills or louvers UNCONFINED SPACE In buildings of conventional frame brick or stone construction unconfined spaces may provide adequate air for combustion ventilation and dil...

Page 6: ...TINGMUSTBEFOLLOWED TOAVOIDCHOKEDCOMBUSTIONORRECIRCULATIONOFFLUEGASES SUCH CONDITIONS CAUSE SOOTING OR RISKS OF FIRE AND ASPHYXIATION NEVEROPERATETHEHEATERUNLESSITISVENTED TOTHEOUTDOORSANDHASADEQUATEAI...

Page 7: ...ceed the thirty 30 equivalent feet of 3 inch pipe or eighty five 85 equivalent feet of 4 inch pipe 3 The blower discharge adapter is made to accept only straight sections of 3 pipe To start a minimum...

Page 8: ...ow be positioned on the outside wall using the drilled hole as a centering point for the template 3 A MASONRYSIDEWALLS Chisel an opening approximately one half inch larger than the marked circle B WOO...

Page 9: ...tions are not reversed when making these connections See Figure 7 G Replace side panel and secure with two screws 5 The blower discharge adapter is made to accept only straight sections of 3 pipe To s...

Page 10: ...run All piping and fittings must be joined by the proper procedures as described under VENTPIPEPREPARATION IMPORTANT The vent system must terminate so that proper clearances are maintained as cited i...

Page 11: ...f the joint Tapered fitting sockets are designed so that an interference fit should occur when the pipe is inserted about 1 3 to 2 3 of the way into the socket Occasionally when pipe fitting dimension...

Page 12: ...e sparingly and only to the male threads of pipe joints Do not apply compound to the first two threads Use compounds resistant to the action of liquefied petroleum gases Do not use teflon tape on ther...

Page 13: ...ly counterclockwise until it stops 4 This appliance is equipped with a device which automatically lights the burner DONOTTRYTOLIGHTTHEBURNERBYHAND 5 Wait five 5 minutes to clear out any gas If you the...

Page 14: ...atures produced at various thermostat dial settings Short repeated heating cycles caused by small hot water uses can cause temperatures at the point of use to exceed the thermostat setting by up to 20...

Page 15: ...n etc For safety and satisfactory operation it is recommended that the heater be checked once a year by a competent service person T P VALVE At least once a year the temperature and pressure relief va...

Page 16: ...e service you received First please contact your dealer or the A O Smith authorized service agent in your area and explain to them why you are not satisfied This will usually correct the problem If af...

Page 17: ...ch Replace control harness Replace blower and motor Replace switch Check for low voltage less than 102 vac have service checked and repaired If voltage is above 102 vac make sure there is not more tha...

Page 18: ...connectors 3 System wiring harness in good condition and securely connected at both ends Not Applicable 1 Replace control 1 Airflow proving switch stuck closed 2 Airflow proving switch mis wired or ju...

Page 19: ...E AT HSI ELEMENT OUTPUT SEE INSET B 120V NOMINAL CHECK DAMAGED OR BROKEN HSI ELEMENT WARNING Line Voltage Hazard Can cause property damage severe injury or death Only a trained experienced service tec...

Page 20: ...all other costs Such costs may include but are not limited to a Labor charges for service removal repair or reinstallation of the water heater or any component part b Shipping delivery handling and a...

Reviews: