background image

10

INSTALLATION OF VENT SYSTEM, SIDEWALL

With the route of the venting system and selection of materials completed,
as discussed in section of this manual titled PLANNING THE VENT
SYSTEM, the through the wall vent terminal in place and the first section
of piping, up to first elbow, installed at the blower it is time to complete
the installation of the venting system for the sidewall installation.

Before completing the installation of the venting system be sure to read
the sections of this manual discussing the proper method of cutting and
cementing PVC pipe and fittings: VENT PIPE PREPARATION.

It is recommended that the completion of the venting system start at the
blower assembly and run to the coupling on the inside wall of the vent
terminal, Figure 5.

The vent system piping should be supported every 5 feet of vertical run
and every 3 feet of horizontal run.  All piping and fittings must be joined
by the proper procedures as described under: VENT PIPE PREPARATION.

     

FIGURE 8

INSTALLATION OF VERTICAL VENT SYSTEM

This unit is approved for venting through the roof with only the vent
terminal that is included with the unit, see Figure 9.  A proper flashing or
"BOOT" should be used to seal the pipe where it exits the roof.  The total
vent system should not exceed the thirty (30) equivalent feet of 3 inch
pipe or sixty (60) equivalent feet of 4 inch pipe as listed in Table 1.

NOTE: The equivalent feet of pipe listed above are exclusive of  the
"TEE" termination with installed screens.

Provide support for all pipe protruding through the roof.  All piping should
be properly secured.  The vent system piping should be supported every
5 feet of vertical run and every 3 feet of horizontal run.  All piping and
fittings must be joined by the proper procedures as described under:
VENT PIPE PREPARATION.

IMPORTANT

The vent system must terminate so that proper clearances are maintained
as cited in local codes or the latest edition of the National Fuel Gas Code,
ANSI Z223.1 and as listed below:

1. Vent Termination must extend a minimum of 12 inches above roof or

12 inches above the anticipated snow level to prevent blockage of
the vent termination.

2. The venting system shall terminate at least four (4) feet from or  one

(1) foot above any gable, dormer or other roof structure with building
interior access; i.e., vent, window, etc.

3. The venting system shall terminate three (3) feet above any forced

air inlet located within ten feet.

     

FIGURE 9

VENT PIPE PREPARATION

1. INITIAL PREPARATION

A.  Make sure the solvent cement you are planning to use is designed

for the specific application you are attempting.

B. Know the physical and chemical characteristics and limitations

of the PVC and CPVC piping materials that you are about to use.

C. Know the reputation of your manufacturer and their products.

D. Know your own qualifications or those of your contractor. The

solvent welding technique of joining PVC and CPVC pipe is a
specialized skill just as any other pipe fitting technique.

E. Closely supervise the installation and inspect the finished  job

before start-up.

F.

Contact the manufacturer, supplier, or competent consulting

agency if you have any questions about the application or
installation of PVC and CPVC pipe.

G. Take the time and effort to do a professional job. Shortcuts will

only cause you problems and delays in start-up. By far,  the
majority of failures in PVC and CPVC systems are the result of
shortcuts and/or improper joining techniques.

2. SELECTION OF MATERIALS

Cutting Device - Saw or Pipe Cutter

Deburring Tool, Knife, File, or Beveling Machine (2" and
above)

Brush - Pure Bristle

Summary of Contents for BTF-75

Page 1: ...Y BEFORE INSTALLING AND USING THIS APPLIANCE A DIVISION OF A O SMITH CORPORATION McBee South Carolina U S A Stratford Ontario Canada www hotwater com KEEP THIS MANUAL IN THE POCKET ON THE HEATER FOR F...

Page 2: ...tions and the local code authority having jurisdiction In the absence of local codes the installation must comply with the latest editions of the National Fuel Gas Code ANSI Z223 1 NFPA 54 The NFPA Th...

Page 3: ...ral gas models A natural gas heater will not function safely on LP gas and no attempt should be made to convert a heater from natural gas to LP gas LP gas must be used with great caution It is highly...

Page 4: ...in before operating Please refer to manufacturer s instructions DISHWASHING MACHINE REQUIREMENT These appliances meet the National Sanitation Foundation Standard for sanitary installations when used w...

Page 5: ...60 75 percent for metal grills or louvers UNCONFINED SPACE In buildings of conventional frame brick or stone construction unconfined spaces may provide adequate air for combustion ventilation and dil...

Page 6: ...TINGMUSTBEFOLLOWED TOAVOIDCHOKEDCOMBUSTIONORRECIRCULATIONOFFLUEGASES SUCH CONDITIONS CAUSE SOOTING OR RISKS OF FIRE AND ASPHYXIATION NEVEROPERATETHEHEATERUNLESSITISVENTED TOTHEOUTDOORSANDHASADEQUATEAI...

Page 7: ...ceed the thirty 30 equivalent feet of 3 inch pipe or eighty five 85 equivalent feet of 4 inch pipe 3 The blower discharge adapter is made to accept only straight sections of 3 pipe To start a minimum...

Page 8: ...ow be positioned on the outside wall using the drilled hole as a centering point for the template 3 A MASONRYSIDEWALLS Chisel an opening approximately one half inch larger than the marked circle B WOO...

Page 9: ...tions are not reversed when making these connections See Figure 7 G Replace side panel and secure with two screws 5 The blower discharge adapter is made to accept only straight sections of 3 pipe To s...

Page 10: ...run All piping and fittings must be joined by the proper procedures as described under VENTPIPEPREPARATION IMPORTANT The vent system must terminate so that proper clearances are maintained as cited i...

Page 11: ...f the joint Tapered fitting sockets are designed so that an interference fit should occur when the pipe is inserted about 1 3 to 2 3 of the way into the socket Occasionally when pipe fitting dimension...

Page 12: ...e sparingly and only to the male threads of pipe joints Do not apply compound to the first two threads Use compounds resistant to the action of liquefied petroleum gases Do not use teflon tape on ther...

Page 13: ...ly counterclockwise until it stops 4 This appliance is equipped with a device which automatically lights the burner DONOTTRYTOLIGHTTHEBURNERBYHAND 5 Wait five 5 minutes to clear out any gas If you the...

Page 14: ...atures produced at various thermostat dial settings Short repeated heating cycles caused by small hot water uses can cause temperatures at the point of use to exceed the thermostat setting by up to 20...

Page 15: ...n etc For safety and satisfactory operation it is recommended that the heater be checked once a year by a competent service person T P VALVE At least once a year the temperature and pressure relief va...

Page 16: ...e service you received First please contact your dealer or the A O Smith authorized service agent in your area and explain to them why you are not satisfied This will usually correct the problem If af...

Page 17: ...ch Replace control harness Replace blower and motor Replace switch Check for low voltage less than 102 vac have service checked and repaired If voltage is above 102 vac make sure there is not more tha...

Page 18: ...connectors 3 System wiring harness in good condition and securely connected at both ends Not Applicable 1 Replace control 1 Airflow proving switch stuck closed 2 Airflow proving switch mis wired or ju...

Page 19: ...E AT HSI ELEMENT OUTPUT SEE INSET B 120V NOMINAL CHECK DAMAGED OR BROKEN HSI ELEMENT WARNING Line Voltage Hazard Can cause property damage severe injury or death Only a trained experienced service tec...

Page 20: ...all other costs Such costs may include but are not limited to a Labor charges for service removal repair or reinstallation of the water heater or any component part b Shipping delivery handling and a...

Reviews: