Indication
Cause
Remark
Collector temperature too
high
Temperature S
1
is greater than
T
collector max
.
You can let the message disappear
automatically by allowing the heating
fluid to cool down.
You can also manually eliminate the
message by pressing the RESET and
ENTER buttons simultaneously.
Non-drainback systems:
The solar systems pump runs at full power
for 10 minutes, pumping the fluid in the
solar system round. If T
col
> T
collector max
after this has elapsed, the pump will stop
running for 30 minutes. After 30 minutes,
the pump will start running again and the
controller of the solar heating system checks
whether T
col
is less than T
collector max
.
Drain-back systems:
The solar system's pump stops running
immediately (for 30 minutes). After
30 minutes, the pump will start running
again and the controller of the solar heating
system checks whether T
col
is less than
T
collector max
.
1.
2.
0311753_SGS_28-120_II_UKUK_V2.0 , 2017-05-03
103
Summary of Contents for BFC-120
Page 6: ...6...
Page 13: ...User part 0311753_SGS_28 120_II_UKUK_V2 0 2017 05 03 13...
Page 14: ...14...
Page 16: ...16 User part...
Page 18: ...18 User part...
Page 24: ...24 User part...
Page 40: ...40 User part...
Page 41: ...Installation Maintenance and Service part 0311753_SGS_28 120_II_UKUK_V2 0 2017 05 03 41...
Page 42: ...42 User part...
Page 82: ...82 Installation Maintenance and Service part...
Page 90: ...90 Installation Maintenance and Service part...
Page 104: ...104 Installation Maintenance and Service part...
Page 110: ...Fig Dimensions SGS 28 30 50 60 110 Installation Maintenance and Service part...
Page 112: ...Fig Dimensions SGS 80 100 120 112 Installation Maintenance and Service part...
Page 121: ...12 8 Declaration of conformity 0311753_SGS_28 120_II_UKUK_V2 0 2017 05 03 121...
Page 124: ...124 Installation Maintenance and Service part...
Page 126: ...126 Installation Maintenance and Service part...