Code and description
Cause
Measure
S06 (blocking error)
Open circuit from
temperature sensor S
3
at
the top of the storage
tank.
Sensor is not (correctly) connected
Connect the sensor lead to J14 (ports 1 and
3) of the solar controller
Damaged cable and/or defective sensor
Replace the cable and/or sensor
S07 (blocking error)
Open circuit from
temperature sensor S
2
at
the bottom of the tank.
Sensor is not (correctly) connected
Connect the sensor lead to J14 (ports 2 and
4) of the solar controller
Damaged cable and/or defective sensor
Replace the cable and/or sensor
S08 (blocking error)
Open circuit from
temperature sensor S
1
in
the collector.
Sensor is not (correctly) connected
Connect the sensor lead to J13 (ports 2 and
4) of the solar controller
Damaged cable and/or defective sensor
Replace the cable and/or sensor
S11 (blocking error)
Short circuit in
temperature sensor T
2
at
the bottom of the tank.
Short circuit in sensor circuit
Replace the cable and/or sensor.
S12 (blocking error)
Short circuit in sensor 1 of
temperature sensor T
1
at
top of tank
(1)
Short circuit in sensor circuit
Replace the cable and/or sensor.
S13 (blocking error)
Short circuit in sensor 2 of
temperature sensor T
1
at
the top of the tank
(1)
.
Short circuit in sensor circuit
Replace the cable and/or sensor.
S14 (blocking error)
Short circuit from
dummy 1
Short circuit in sensor circuit
Replace the cable dummy sensor
(2)
.
S15 (blocking error)
Short circuit from
dummy 2
Short circuit in sensor circuit
Replace the cable dummy sensor
(2)
.
S17 (blocking error)
Short circuit from
temperature sensor S
2
at
the bottom of the tank.
Short circuit in sensor circuit
Replace the cable and/or sensor
S18 (blocking error)
Short circuit from
temperature sensor S
1
in
the collector.
Short circuit in sensor circuit
Replace the cable and/or sensor
F01 (blocking error)
Defect in power supply
circuit
Live and neutral connected wrong way
around.
Be sure to connect the live and neutral
correctly (see section 7.8); the water heater
is phase-sensitive
Condensation on the flame probe
Disconnect the lead at the flame probe
Ignite the water heater three times, with
an interrupted ionisation circuit
Reconnect the ionisation lead to the
flame probe
Ignite the water heater again
The repeated ignition attempts will have
caused the condensation to evaporate
•
•
•
•
•
Floating neutral
Install an isolating transformer (see section
7.8.3.1)
98
Installation, Maintenance and Service part
Summary of Contents for BFC-120
Page 6: ...6...
Page 13: ...User part 0311753_SGS_28 120_II_UKUK_V2 0 2017 05 03 13...
Page 14: ...14...
Page 16: ...16 User part...
Page 18: ...18 User part...
Page 24: ...24 User part...
Page 40: ...40 User part...
Page 41: ...Installation Maintenance and Service part 0311753_SGS_28 120_II_UKUK_V2 0 2017 05 03 41...
Page 42: ...42 User part...
Page 82: ...82 Installation Maintenance and Service part...
Page 90: ...90 Installation Maintenance and Service part...
Page 104: ...104 Installation Maintenance and Service part...
Page 110: ...Fig Dimensions SGS 28 30 50 60 110 Installation Maintenance and Service part...
Page 112: ...Fig Dimensions SGS 80 100 120 112 Installation Maintenance and Service part...
Page 121: ...12 8 Declaration of conformity 0311753_SGS_28 120_II_UKUK_V2 0 2017 05 03 121...
Page 124: ...124 Installation Maintenance and Service part...
Page 126: ...126 Installation Maintenance and Service part...