DIGITAL TANK THERMOSTAT INSTALLATION

1.  Mount the thermostat on the storage tank jacket when or at 

a suitable location close to the storage tank, see Figure 10. 

2.  Install  three  conductor  low  voltage  wiring  between  the 

thermostat’s  terminal  strip  and  the  HPWH  unit’s  terminal 

strip as shown in the Digital Tank Thermostat Wiring on page 

37

. Use standard 18 AWG thermostat wire or equivalent.

TEMPERATURE SENSOR INSTALLATION

The HPWH unit is shipped from the factory with a Digital Tank 

Thermostat that includes a Temperature Sensor and a Sensor 

Well. To install the Sensor Well:
1.  Coat the Temperature Sensor and the inside of the Sensor 

Well with heat transfer compound (paste) such as Honeywell 

P/N 107408 or equivalent.

2.  Secure the Temperature Sensor inside the Sensor Well with 

the supplied clip or with an appropriate stop.

3.  Check the condition of the anode rod(s) on existing storage 

tanks and replace if depleted. 

4.  Install  the  sensor  well  in  the  storage  tank’s  designated 

temperature  control  opening.  Typically  a  3/4”  female  NPT 

fitting in the lower portion of the storage tank. 

5. 

DO NOT

  install  Sensor  Well  or  temperature  sensor  in  the 

upper half of the storage tank.

6.  Do  not  install  Sensor  Well  near  the  cold  water  supply 

connection to the storage tank to prevent short cycling.

7.  Install  two  conductor  low  voltage  wiring  between  the 

Temperature  Sensor  and  Digital  Tank  Thermostat  terminal 

strip as shown in the Digital Tank Thermostat Wiring on page 

37

.  Wiring  can  be  installed  up  to  650  feet  using  24 AWG 

thermostat wire or equivalent.

REMOTE TEMPERATURE

SENSOR AND SENSOR WELL

HPWH

BACKUP

WATER

HEATER

DIGITAL TANK

THERMOSTAT

STORAGE

TANK

Figure 10

AIR FLOW AND DUCTING

GENERAL GUIDELINES

Review  Locating  The  Water  Heater  on  page  10,    and  this 

section prior to connecting ductwork to the HPWH. See Features 

And Components on page 8 to locate components.

 

Do not duct air from a garage or other

space where potentially harmful fumes

from solvents, chemicals or exhaust

from automobiles are present into any

other space in the building structure.
Gas and carbon monoxide detectors

are available.

Breathing carbon monoxide can cause brain damage or

death. Always read and understand instruction manual.

Breathing Hazard - Carbon Monoxide Gas

The supply (outlet) air from a HPWH installed in a garage or a 

unit drawing return (inlet) air from a garage or any area where 

solvents or other chemicals that emit potentially harmful fumes 

are stored or automobiles are located must never be ducted to 

any other space inside the building structure. This would include 

all occupied and unoccupied spaces such as attics or basements. 

Potentially harmful fumes and vapors could be introduced into 

occupied spaces. See Unit Placement on page 16. 

DUCT SIZING

Supply and return air ducting must be sized properly to insure 

adequate  airflow.  Table  6,  Table  7  and  Table  8  on  page  21 

provide requirements for the total equivalent supply and return 

duct  lengths  allowed.  These  tables  are  based  on  the  most 

common duct material options available today. Exceeding those 

maximum lengths will adversely affect the operation of the heat 

pump.

DUCT INSULATION

The cooled air from the HPWH may be below room dew point.  

Insulate  the  supply  duct  to  prevent  dripping  from  moisture 

condensing on the duct. 
It is not necessary to insulate return ducts unless the air in the 

return duct is lower than the room air. Also consider insulating all 

ductwork to reduce blower noise from the unit.

MAKE DUCT CONNECTIONS

Install  all  ductwork  to  and  from  unit  in  accordance  with  all 

applicable codes. Duct construction must allow unit to operate 

within  the  limits  of  the  unit  external  static  pressure  as  in  the 

HPWH unit’s performance and specification sheets. See Table 

1 on page 9 also.
Use  flexible  connections  to  minimize  duct-to-duct  alignment 

problems and noise transmission.
Install ductwork, accessory grilles, and plenums so that they do 

not restrict access to filter and so they prevent dirt, dust, and 

debris from settling in unit.

BUILDING AIR PRESSURE

When  installing  ducting  to  or  from  an  alternate  location  (other 

than  the  installed  space)  both  the  supply  (outlet)  and  return 

(inlet) air may need to be ducted to prevent positive or negative 

building air pressure conditions within the installed space.

Summary of Contents for AWH-35

Page 1: ...70 SERIES 100 INSTALLATION OPERATION SERVICE MAINTENANCE LIMITED WARRANTY 820 SW 41st Street Renton WA 98057 Read and understand this instruction manual and the safety messages herein before installin...

Page 2: ......

Page 3: ...ank Thermostat Wiring 37 Standard Tank Thermostat Wiring 38 High Ambient Air Kit Wiring 39 Building Recirculation Pump Wiring Diagram 40 PIPING DIAGRAMS 41 LIMITED WARRANTY 47 TABLE OF CONTENTS 3 SAFE...

Page 4: ...possible injury or death WARNING indicates a potentially hazardous situation which if not avoided could result in injury or death CAUTION indicates a potentially hazardous situation which if not avoi...

Page 5: ...er procedures or the use of non approved refrigerants refrigerant substitutes or refrigerant additives could result in death or serious injury or equipment damage Explosion Hazard Do not use oxygen to...

Page 6: ...G APPLIANCE INTRODUCTION 6 Detailed installation diagrams are in this manual These diagrams will serve to provide the installer with a reference for the materials and suggested methods of piping IT IS...

Page 7: ...flowing through the tubes and air flowing across the fins The Blower moves ambient air from the installed space or air ducted to the HPWH from another location across the fins of evaporator coil The r...

Page 8: ...IQUID COMPONENT WATER CIRCUIT A WATER INLET B WATER PUMP C HEAT EXCHANGER CONDENSER D WATER OUTLET WARM RETURN AIR IN COOL SUPPLY AIR OUT ACCUMULATOR COMPRESSOR CONDENSER HEAT EXCHANGER REFRIGERANT TO...

Page 9: ...8 660 AWH 115 33 1 113 000 89 000 7 4 4 2 3200 23 1 5 63 38 42 5 8 665 AWH 140 41 6 142 000 110 000 9 2 3 9 3800 28 2 0 63 38 42 5 8 725 AWH 170 50 1 171 000 133 000 11 1 3 9 4900 34 2 0 75 46 42 5 8...

Page 10: ...ating range the HPWH unit s Ambient Air Limit Thermostat will discontinue heating operation until the entering air temperature returns to this operating range See Figure 15 on page 37 High Ambient Air...

Page 11: ...ssary to access an adequate or greater source of heat for optimal efficiency See Building Air Pressure Air Flow and Ducting on page 19 CLEARANCES To ensure optimal performance a minimum of 30 inches c...

Page 12: ...this could result in death serious bodily injury or property damage The load current rating and the overcurrent protection for these conductors shall not exceed 15 amperes for 14 AWG 20 amperes for 1...

Page 13: ...demand of the application a Mixing Valve should be installed upstream from the building fixtures or at the hot water taps to further reduce system water temperature Mixing valves are available at plum...

Page 14: ...ause brain damage or death Always read and understand instruction manual Breathing Hazard Carbon Monoxide Gas The supply outlet air from a HPWH installed in a garage or a unit drawing return inlet air...

Page 15: ...unless spreader bars are furnished and used as depicted in Figure 4 and Figure 5 The side panels and roof of the unit are not constructed to handle significant force from the sides or above The HPWH...

Page 16: ...H in new construction the following critical points must be observed The HPWH unit 1 Must be installed indoors 2 Should be installed near a floor drain for condensate removal 3 The HPWH storage tank a...

Page 17: ...S 1 This HPWH unit is not designed to supply hot water directly to hot water fixtures The HPWH unit must be installed with a separate storage tank as shown in the water piping diagrams in this instruc...

Page 18: ...NK PRE HEAT CONFIGURATION When water temperatures above 140 F 60 C are required the HPWH and storage tank are piped in series upstream with a backup water heater See Water Temperature on page 10 The b...

Page 19: ...he building structure Gas and carbon monoxide detectors are available Breathing carbon monoxide can cause brain damage or death Always read and understand instruction manual Breathing Hazard Carbon Mo...

Page 20: ...r entering the HPWH unit the supply air may not be suitable for supplemental space cooling purposes The air temperature drops approximately 12 F to 20 F 7 C to 11 C as it flows through the HPWH unit I...

Page 21: ...12 14 16 18 20 22 24 MODEL CFM EXT in WG MAXIMUM EQUIVALENT LENGTH FEET AWH 35 1040 0 35 6 18 45 93 185 AWH 55 1650 0 35 3 8 18 40 77 137 AWH 75 2150 0 35 5 11 23 47 83 139 AWH 100 3200 0 35 3 6 14 26...

Page 22: ...t Water Temperature on page 10 See Figure 7 and Figure 8 on page 18 14 On two tank preheat piping configurations ensure the cold INSTALLATION CHECKLIST 22 water supply is not connected to the back up...

Page 23: ...mentioned above call the toll free technical support phone number on the back cover of this manual for further assistance 6 When all of the above procedures are complete adjust the tank temperature c...

Page 24: ...buttons to adjust to the desired differential set point 3 When complete press the SET button to save the change 4 The operating mode of the thermostat will be shown on the LED display next as CoL for...

Page 25: ...performing any maintenance on the blower assembly disconnect all power to the unit and follow the prescribed lock out tag out procedure Inspect and tighten all bearing collar and wheel set screws afte...

Page 26: ...plication and usage instructions 5 Allow the unit to dry thoroughly 6 If necessary apply an anti microbial agent on the insulation per the instructions provided on the product label 7 Discard collecte...

Page 27: ...t pump reduce piping or add booster pump clean heat exchanger with a mild acid wash open all shut off valves Heat pump is not running low pressure fault 1 Room temperature below 50 F 2 Blower not oper...

Page 28: ...in the inlet and outlet water piping connected between the HPWH unit and the storage tank On new installations ensure the maximum equivalent feet of inlet and outlet piping was not exceeded This is th...

Page 29: ...ent The cause of the pressure switch contacts opening must be corrected and the control system must be reset before the HPWH will resume compressor operation See Table 11 for pressure switch activatio...

Page 30: ...e containing a relay or triac transformer and several electronic components Leads from the internal motor sensors are connected to the module As the motor temperature rises or falls the resistance als...

Page 31: ...nits TABLE 13 ABBREVIATION DESCRIPTION WIRING NOTES PM Phase Monitor Factory If installed PC Pump Contactor Factory Load pump if installed BC Blower Contactor Factory CC Compressor Contactor Factory H...

Page 32: ...UNIT WIRING DIAGRAMS FUSE SIZES 208 230 VAC SINGLE PHASE 60 HZ 32...

Page 33: ...UNIT WIRING DIAGRAMS FUSE SIZES 208 230 VAC THREE PHASE 60 HZ AWH 35 AWH 55 and AWH 75 only 33...

Page 34: ...UNIT WIRING DIAGRAMS FUSE SIZES 208 230 VAC THREE PHASE 60 HZ only 34...

Page 35: ...UNIT WIRING DIAGRAMS FUSE SIZES 460 VAC THREE PHASE 60 HZ 35...

Page 36: ...UNIT WIRING DIAGRAMS FUSE SIZES 460 VAC THREE PHASE 60 HZ only 36...

Page 37: ...AIR TEMPERATURE SENSOR RANCO DIGITAL THERMOSTAT PART ETC 212000 000 24V COM NC NO C NC C NO DIGITAL TANK THERMOSTAT FULL GAUGE MODEL MT511Ri NOTE TANK TEMPERATURE SETTING MUST NOT EXCEED 140 F 60 C C...

Page 38: ...ATION NOTES 1 Configure stage 1 for cooling 2 Configure stage 2 for heating 3 Set cooling set point at 50 F 4 Set heating set point 95 F 5 Set cooling differential to 10 F 6 Set heating differential t...

Page 39: ...e on fall WHITE Close RED Close BLACK Close C NO NC 1 2 3 4 5 6 7 8 9 0 1 1 1 2 1 OUTPUT THERMOSTAT TERMINAL STRIP HPWH TERMINAL STRIP AMBIENT AIR LIMIT THERMOSTAT CONFIGURATION NOTES 1 Configure stag...

Page 40: ...NK FIELD SUPPLIED LINE TEMPERATURE CONTROL INSTALLED IN THE CIRCULATING LOOP RETURN LINE CIRC PUMP MOTOR L1 HOT L2 NEUTRAL 120 VAC POWER NOTE USE SEPARATE 120 VAC POWER SUPPLY FOR PUMP CIRCUIT Figure...

Page 41: ...URE RELIEF VALVE PRESSURE RELIEF VALVE CIRCULATING PUMP DRAIN WYE STRAINER FULL PORT BALL VALVE TEMPERATURE GAGE CHECK VALVE TANK OR LINE TEMPERATURE CONTROL WARNING THIS DRAWING SHOWS SUGGESTED PIPIN...

Page 42: ...E TEMPERATURE GAGE CHECK VALVE WARNING THIS DRAWING SHOWS SUGGESTED PIPING CONFIGURATION AND OTHER DEVICES CHECK WITH LOCAL CODES AND ORDINANCES FOR ADDITIONAL REQUIREMENTS TANK OR LINE TEMPERATURE CO...

Page 43: ...N COLD WATER SUPPLY LINE THERMOSTAT NOTE CONNECT BUILDING RECIRC RETURN TO INLET OF BACKUP WATER HEATER WHEN PRESENT TANK THERMOSTAT PIPE T P TO OPEN DRAIN RETURN WATER INLET PURGE VALVE SUPPLY WATER...

Page 44: ...ULL PORT BALL VALVE TEMPERATURE GAGE CHECK VALVE TANK OR LINE TEMPERATURE CONTROL WARNING THIS DRAWING SHOWS SUGGESTED PIPING CONFIGURATION AND OTHER DEVICES CHECK WITH LOCAL CODES AND ORDINANCES FOR...

Page 45: ...AND ORDINANCES FOR ADDITIONAL REQUIREMENTS LEGEND TEMPERATURE PRESSURE RELIEF VALVE PRESSURE RELIEF VALVE CIRCULATING PUMP DRAIN WYE STRAINER FULL PORT BALL VALVE TEMPERATURE GAGE CHECK VALVE TANK OR...