INSTALLATION REQUIREMENTS

Read all installation requirements in this manual before installation 

begins. The installation must conform to these instructions and 

all local and national code authority having jurisdiction.
Costs to diagnose, perform service and repair damage caused 

by installation errors are not covered under the limited warranty. 
Costs  to  correct  installation  errors  are  not  covered  under  the 

limited warranty.

WATER TEMPERATURE

MAXIMUM SYSTEM TEMPERATURE

The  HPWH  units  covered  in  this  manual  are  capable  of 

maintaining  a  maximum  system/storage  tank  temperature  of 

140°F  (60°C).  Some  commercial  water  heating  applications 

may require higher temperatures. Install a booster water heater 

downstream  from  the  storage  tank  for    temperatures  above 

140°F (60°C). See Figure 8 on page 18.

INLET & OUTLET WATER TEMPERATURE

The  inlet  (entering)  water  temperature  operating  range  for  the 

HPWH is 50°F to 140°F (10°C to 60°C). The water temperature 

rise (Delta T - ∆T) through the condenser (heat exchanger) will 

be approximately 8°F to 12°F (4°C to 7°C). 
Outlet  water  temperatures  up  to  152°F  (67°C)  are  possible 

during normal operation. Exposure to water  temperatures this 

high can cause serious bodily injury or death.  See Mixing Valves 

and Table 5 on page 14. 

Service & Installation Notes: 

If the inlet (entering) water temperature is outside the operating 

temperature range for extended periods the control system may 

lock out on high or low refrigerant pressure switch events/trips. 
When  the  control  system  locks  out  on  a  refrigerant  pressure 

switch event the compressor will stop running, the blower and 

circulation  pump  (on  models  equipped  with  factory  installed 

pump) will continue to operate. This is a hard lock out condition. 

The  control  system  is  manually  reset  by  cycling  power  to  the 

HPWH off and then on again.

The tank thermostat must not be set any higher than 140°F 

(60°C) to prevent control system lock outs.

Ground  water  temperatures  can  fall  below  50°F  (10°C)  for 

extended periods during winter months in many regions. For this 

reason the cold water supply lines  and should not be connected 

directly to the HPWH inlet or T fitted into the inlet (return) water 

piping. The cold water supply lines should be connected directly 

to the storage tank only. See the Piping Diagrams on page 4

1

 

in this manual for more information.

AIR TEMPERATURE

ENTERING AIR TEMPERATURE

The  return  (entering)  air  temperature  range  of  operation  for 

the unit is 50° - 95°F (10°C to 35°C). The air temperature drop 

(Delta T - ∆T) through the evaporator (heat exchanger) will be 

approximately 12°F to 20°F (7°C to 11°C).
If  the  entering  air  temperature  is  outside  this  operating  range 

the HPWH unit’s Ambient Air Limit Thermostat will discontinue 

heating operation until the entering air temperature returns to this 

operating range. See Figure 1

5

 on page 

37

.

High Ambient Air Kits

 are available that will allow the unit to 

operate with entering air temperatures up to 120°F (49°C). These 

accessory  kits  must  be  installed  if  entering  air  temperatures 

exceed 95°F (35°C) for extended periods.

Contact  your  local  distributor  or  call  the  technical  support 

phone number listed on the back cover of this manual for more 

information on ordering one of these accessory kits.

Service & Installation Notes:

When the High Ambient Air kit is installed the heating stage set 

point on the Ambient Air Limit thermostat must be raised to 120°F 

(49°C) to allow heating operation up to this temperature.

LOCATING THE WATER HEATER

PROPERTY DAMAGE!

All water heaters eventually leak.

Do not install without adequate drainage.

CAUTION

INDOOR INSTALLATION ONLY

The HPWH unit is designed for indoor installation only.
Carefully choose a location for the HPWH unit. Placement is a 

very important consideration for optimal performance and safety. 
Locate the HPWH near a floor drain. The unit should be located 

in an area where leakage from the HPWH unit or the storage tank 

it is connected to will not result in damage to the area adjacent 

to the water heater or to lower floors of the structure. See Unit 

Placement on page 16.

FREEZING TEMPERATURES

The HPWH unit must not be installed in space where freezing 

temperatures  will  occur.  Exposure  to  freezing  ambient 

temperatures below 32°F (0°C) may result in severe damage to 

internal components. Damage caused by exposure to freezing 

temperatures is not covered under the limited warranty.

COASTAL REGIONS

When the HPWH will be installed within 5 miles of a seacoast the 

optional Corrosive Duty Package is required. The corrosive duty 

package

 

includes

 

 a 

 

316 

 

stainless 

 

steel cabinet 

 

and 

 

 

phe

nolic

 

coating applied to the evaporator and blower. Damage caused to 

units  not  equipped  with  the  corrosive  duty  package  in  coastal 

regions is not covered under the limited warranty.

HEAT SOURCE

The HPWH unit should be located where there is an adequate 

source  of  ambient  heat  and  where  the  cooling  benefit  can  be 

utilized when possible.
If  installation  in  a  space  with  an  adequate  heat  source  is  not 

possible  the  HPWH  unit  can  be  ducted  to/from  another  space 

such as a boiler room or to the outdoors where sufficient heat is 

available. See Air Flow and Ducting on page 19.

CONDITIONED SPACE

When installed in a conditioned space ducting supply (outlet) air 

to an alternate location may be necessary to avoid over-cooling 

of the space where the HPWH is installed or provide spot cooling 

in areas for comfort and/or to offset cooling load. See Building Air 

Pressure

,

 Air Flow and Ducting on page 19.

Summary of Contents for AWH-35

Page 1: ...70 SERIES 100 INSTALLATION OPERATION SERVICE MAINTENANCE LIMITED WARRANTY 820 SW 41st Street Renton WA 98057 Read and understand this instruction manual and the safety messages herein before installin...

Page 2: ......

Page 3: ...ank Thermostat Wiring 37 Standard Tank Thermostat Wiring 38 High Ambient Air Kit Wiring 39 Building Recirculation Pump Wiring Diagram 40 PIPING DIAGRAMS 41 LIMITED WARRANTY 47 TABLE OF CONTENTS 3 SAFE...

Page 4: ...possible injury or death WARNING indicates a potentially hazardous situation which if not avoided could result in injury or death CAUTION indicates a potentially hazardous situation which if not avoi...

Page 5: ...er procedures or the use of non approved refrigerants refrigerant substitutes or refrigerant additives could result in death or serious injury or equipment damage Explosion Hazard Do not use oxygen to...

Page 6: ...G APPLIANCE INTRODUCTION 6 Detailed installation diagrams are in this manual These diagrams will serve to provide the installer with a reference for the materials and suggested methods of piping IT IS...

Page 7: ...flowing through the tubes and air flowing across the fins The Blower moves ambient air from the installed space or air ducted to the HPWH from another location across the fins of evaporator coil The r...

Page 8: ...IQUID COMPONENT WATER CIRCUIT A WATER INLET B WATER PUMP C HEAT EXCHANGER CONDENSER D WATER OUTLET WARM RETURN AIR IN COOL SUPPLY AIR OUT ACCUMULATOR COMPRESSOR CONDENSER HEAT EXCHANGER REFRIGERANT TO...

Page 9: ...8 660 AWH 115 33 1 113 000 89 000 7 4 4 2 3200 23 1 5 63 38 42 5 8 665 AWH 140 41 6 142 000 110 000 9 2 3 9 3800 28 2 0 63 38 42 5 8 725 AWH 170 50 1 171 000 133 000 11 1 3 9 4900 34 2 0 75 46 42 5 8...

Page 10: ...ating range the HPWH unit s Ambient Air Limit Thermostat will discontinue heating operation until the entering air temperature returns to this operating range See Figure 15 on page 37 High Ambient Air...

Page 11: ...ssary to access an adequate or greater source of heat for optimal efficiency See Building Air Pressure Air Flow and Ducting on page 19 CLEARANCES To ensure optimal performance a minimum of 30 inches c...

Page 12: ...this could result in death serious bodily injury or property damage The load current rating and the overcurrent protection for these conductors shall not exceed 15 amperes for 14 AWG 20 amperes for 1...

Page 13: ...demand of the application a Mixing Valve should be installed upstream from the building fixtures or at the hot water taps to further reduce system water temperature Mixing valves are available at plum...

Page 14: ...ause brain damage or death Always read and understand instruction manual Breathing Hazard Carbon Monoxide Gas The supply outlet air from a HPWH installed in a garage or a unit drawing return inlet air...

Page 15: ...unless spreader bars are furnished and used as depicted in Figure 4 and Figure 5 The side panels and roof of the unit are not constructed to handle significant force from the sides or above The HPWH...

Page 16: ...H in new construction the following critical points must be observed The HPWH unit 1 Must be installed indoors 2 Should be installed near a floor drain for condensate removal 3 The HPWH storage tank a...

Page 17: ...S 1 This HPWH unit is not designed to supply hot water directly to hot water fixtures The HPWH unit must be installed with a separate storage tank as shown in the water piping diagrams in this instruc...

Page 18: ...NK PRE HEAT CONFIGURATION When water temperatures above 140 F 60 C are required the HPWH and storage tank are piped in series upstream with a backup water heater See Water Temperature on page 10 The b...

Page 19: ...he building structure Gas and carbon monoxide detectors are available Breathing carbon monoxide can cause brain damage or death Always read and understand instruction manual Breathing Hazard Carbon Mo...

Page 20: ...r entering the HPWH unit the supply air may not be suitable for supplemental space cooling purposes The air temperature drops approximately 12 F to 20 F 7 C to 11 C as it flows through the HPWH unit I...

Page 21: ...12 14 16 18 20 22 24 MODEL CFM EXT in WG MAXIMUM EQUIVALENT LENGTH FEET AWH 35 1040 0 35 6 18 45 93 185 AWH 55 1650 0 35 3 8 18 40 77 137 AWH 75 2150 0 35 5 11 23 47 83 139 AWH 100 3200 0 35 3 6 14 26...

Page 22: ...t Water Temperature on page 10 See Figure 7 and Figure 8 on page 18 14 On two tank preheat piping configurations ensure the cold INSTALLATION CHECKLIST 22 water supply is not connected to the back up...

Page 23: ...mentioned above call the toll free technical support phone number on the back cover of this manual for further assistance 6 When all of the above procedures are complete adjust the tank temperature c...

Page 24: ...buttons to adjust to the desired differential set point 3 When complete press the SET button to save the change 4 The operating mode of the thermostat will be shown on the LED display next as CoL for...

Page 25: ...performing any maintenance on the blower assembly disconnect all power to the unit and follow the prescribed lock out tag out procedure Inspect and tighten all bearing collar and wheel set screws afte...

Page 26: ...plication and usage instructions 5 Allow the unit to dry thoroughly 6 If necessary apply an anti microbial agent on the insulation per the instructions provided on the product label 7 Discard collecte...

Page 27: ...t pump reduce piping or add booster pump clean heat exchanger with a mild acid wash open all shut off valves Heat pump is not running low pressure fault 1 Room temperature below 50 F 2 Blower not oper...

Page 28: ...in the inlet and outlet water piping connected between the HPWH unit and the storage tank On new installations ensure the maximum equivalent feet of inlet and outlet piping was not exceeded This is th...

Page 29: ...ent The cause of the pressure switch contacts opening must be corrected and the control system must be reset before the HPWH will resume compressor operation See Table 11 for pressure switch activatio...

Page 30: ...e containing a relay or triac transformer and several electronic components Leads from the internal motor sensors are connected to the module As the motor temperature rises or falls the resistance als...

Page 31: ...nits TABLE 13 ABBREVIATION DESCRIPTION WIRING NOTES PM Phase Monitor Factory If installed PC Pump Contactor Factory Load pump if installed BC Blower Contactor Factory CC Compressor Contactor Factory H...

Page 32: ...UNIT WIRING DIAGRAMS FUSE SIZES 208 230 VAC SINGLE PHASE 60 HZ 32...

Page 33: ...UNIT WIRING DIAGRAMS FUSE SIZES 208 230 VAC THREE PHASE 60 HZ AWH 35 AWH 55 and AWH 75 only 33...

Page 34: ...UNIT WIRING DIAGRAMS FUSE SIZES 208 230 VAC THREE PHASE 60 HZ only 34...

Page 35: ...UNIT WIRING DIAGRAMS FUSE SIZES 460 VAC THREE PHASE 60 HZ 35...

Page 36: ...UNIT WIRING DIAGRAMS FUSE SIZES 460 VAC THREE PHASE 60 HZ only 36...

Page 37: ...AIR TEMPERATURE SENSOR RANCO DIGITAL THERMOSTAT PART ETC 212000 000 24V COM NC NO C NC C NO DIGITAL TANK THERMOSTAT FULL GAUGE MODEL MT511Ri NOTE TANK TEMPERATURE SETTING MUST NOT EXCEED 140 F 60 C C...

Page 38: ...ATION NOTES 1 Configure stage 1 for cooling 2 Configure stage 2 for heating 3 Set cooling set point at 50 F 4 Set heating set point 95 F 5 Set cooling differential to 10 F 6 Set heating differential t...

Page 39: ...e on fall WHITE Close RED Close BLACK Close C NO NC 1 2 3 4 5 6 7 8 9 0 1 1 1 2 1 OUTPUT THERMOSTAT TERMINAL STRIP HPWH TERMINAL STRIP AMBIENT AIR LIMIT THERMOSTAT CONFIGURATION NOTES 1 Configure stag...

Page 40: ...NK FIELD SUPPLIED LINE TEMPERATURE CONTROL INSTALLED IN THE CIRCULATING LOOP RETURN LINE CIRC PUMP MOTOR L1 HOT L2 NEUTRAL 120 VAC POWER NOTE USE SEPARATE 120 VAC POWER SUPPLY FOR PUMP CIRCUIT Figure...

Page 41: ...URE RELIEF VALVE PRESSURE RELIEF VALVE CIRCULATING PUMP DRAIN WYE STRAINER FULL PORT BALL VALVE TEMPERATURE GAGE CHECK VALVE TANK OR LINE TEMPERATURE CONTROL WARNING THIS DRAWING SHOWS SUGGESTED PIPIN...

Page 42: ...E TEMPERATURE GAGE CHECK VALVE WARNING THIS DRAWING SHOWS SUGGESTED PIPING CONFIGURATION AND OTHER DEVICES CHECK WITH LOCAL CODES AND ORDINANCES FOR ADDITIONAL REQUIREMENTS TANK OR LINE TEMPERATURE CO...

Page 43: ...N COLD WATER SUPPLY LINE THERMOSTAT NOTE CONNECT BUILDING RECIRC RETURN TO INLET OF BACKUP WATER HEATER WHEN PRESENT TANK THERMOSTAT PIPE T P TO OPEN DRAIN RETURN WATER INLET PURGE VALVE SUPPLY WATER...

Page 44: ...ULL PORT BALL VALVE TEMPERATURE GAGE CHECK VALVE TANK OR LINE TEMPERATURE CONTROL WARNING THIS DRAWING SHOWS SUGGESTED PIPING CONFIGURATION AND OTHER DEVICES CHECK WITH LOCAL CODES AND ORDINANCES FOR...

Page 45: ...AND ORDINANCES FOR ADDITIONAL REQUIREMENTS LEGEND TEMPERATURE PRESSURE RELIEF VALVE PRESSURE RELIEF VALVE CIRCULATING PUMP DRAIN WYE STRAINER FULL PORT BALL VALVE TEMPERATURE GAGE CHECK VALVE TANK OR...

Page 46: ...ion of it in a modified form will void this warranty 4 SERVICE REPAIR AND EXPENSE Under this limited warranty the warrantor will provide only a replacement heat pump water heater or part thereof The o...

Page 47: ...talled Dealer s Name Dealer s Address Phone No City and State Zip Fill in the following for your own reference Keep it Registration is not a condition of warranty The model and serial number are found...

Page 48: ...500 Tennessee Waltz Parkway Ashland City TN 37015 Technical Support 800 527 1953 Parts 800 433 2545 Fax 800 644 9306 www hotwater com...

Reviews: