background image

14

connected to the storage tank. If more than one water heating 

appliance is connected to the storage tank the aggregate total 

of all heating input ratings of all connected appliances must be 

factored when choosing a T&P valve for the storage tank.
The  pressure  rating  of  the  T&P  valve  should  always  be  rated 

equal to or below the working pressure rating of the storage tank 

or water heater, whichever rating is lower.
Contact the manufacturer of the storage tank for assistance in 

sizing  of  a  temperature  and  pressure  relief  valve.  Follow  the 

storage  tank  manufacturer’s  instructions  regarding  the  proper 

installation of these products.

TANK SELECTION

The HPWH unit is not an instantaneous water heater and must 

be connected to a storage tank. Storage tank configurations must 

meet these criteria:
1.  The HPWH must not be connected directly to a standard gas 

or electric water heater.

2.  If the HPWH is connected to a used storage tank, the tank 

should be thoroughly cleaned of scale and sediment before 

the HPWH is installed.

3.  Connection ports used on the storage tank must permit the 

recommended  flow  rate  through  HPWH.  The  connection 

ports used on the storage tank must not be smaller than the 

inlet outlet connection sizes on the HPWH unit. See Table 4 

on page 13.

4.  Water heated by the HPWH should be returned to the tank at 

a location that is above the level of the tank’s cold water inlet 

and/or the heat pump’s inlet source. 

5.  The  HPWH  unit’s  inlet  and  outlet  lines  to  the  storage  tank 

should  be  dedicated.  Example:  no  other  line  (such  as  a 

building re-circulating loop or cold water supply) should be 

connected to the HPWH unit’s inlet or outlet water lines.

SOLAR TANKS

Solar tanks should be used with caution. Some solar tanks with 

top connections have dip tubes which may significantly reduce 

the efficiency performance of the HPWH unit.
Before  using  any  solar  tank  in  this  application,  contact  your 

representative or call the toll free technical support number on 

the back cover of this manual for further assistance.

CONTAMINATED AIR

Do not duct air from a garage or other

space where potentially harmful fumes

from solvents, chemicals or exhaust

from automobiles are present into any

other space in the building structure.
Gas and carbon monoxide detectors

are available.

Breathing carbon monoxide can cause brain damage or

death. Always read and understand instruction manual.

Breathing Hazard - Carbon Monoxide Gas

The supply (outlet) air from a HPWH installed in a garage or a 

unit drawing return (inlet) air from a garage or any area where 

solvents or other chemicals that emit potentially harmful fumes 

are stored or automobiles are located must never be ducted to 

any other space inside the building structure. This would include 

all occupied and unoccupied spaces such as attics or basements. 

TABLE 5

Water Temperature

Time to Produce 2nd & 3rd

Degree Burns on Adult Skin

180°F (82°C)

Nearly instantaneous

170°F (77°C)

Nearly instantaneous

160°F (71°C)

About 1/2 second

150°F (66°C)

About 1-1/2 seconds

140°F (60°C)

Less than 5 seconds

130°F (54°C)

About 30 seconds

120°F (49°C)

More than 5 minutes

CONDENSATE REMOVAL

The HPWH unit produces condensate which must be discharged. 

If there is no drain easily accessible, a condensate lift pump must 

be installed to discharge the condensate to a remote location. See 

Condensate Drain Line on page 18 for installation instructions.

CONTAMINATED WATER

Connecting the heat pump to any system other than a water

system may lead to premature corrosion of the unit's heat

exchanger and void the unit warranty.

Corrosive Chemical Hazard

This HPWH unit must not be used to heat any fluid other than 

water.  Corrosive  chemicals  must  not  be  introduced  into  the 

waterways in this HPWH unit.

TEMPERATURE - PRESSURE RELIEF VALVE

Explosion Hazard

Temperature-Pressure Relief Valve

must comply with ANSI Z21.22-

CSA 4.4 and ASME code.

Properly sized temperature-

pressure relief valve must be

installed in the designated 

opening in the storage tank.

Can result in overheating and

excessive tank pressure.

Can cause serious injury or death.

This  heat  pump  water  heater  should  only  be  connected  to  a 

storage tank with a properly rated/sized and certified combination 

temperature - pressure relief valve. The valve must be certified by 

a nationally recognized testing laboratory that maintains periodic 

inspection  of  production  of  listed  equipment  of  materials  as 

meeting the requirements for Relief Valves for Hot Water Supply 

Systems, ANSI Z21.22 • CSA 4.4, and the code requirements of 

ASME.
When the HPWH unit is connected to a storage tank a temperature 

and  pressure  relief  valve  must  be  installed  in  the  designated 

opening for the T&P valve per the storage tank manufacturer’s 

requirements. The T&P  valve’s  Btu/hr  rating  must  be  equal  to 

or greater than the total heating input rating of all water heaters  

Summary of Contents for AWH-35

Page 1: ...70 SERIES 100 INSTALLATION OPERATION SERVICE MAINTENANCE LIMITED WARRANTY 820 SW 41st Street Renton WA 98057 Read and understand this instruction manual and the safety messages herein before installin...

Page 2: ......

Page 3: ...ank Thermostat Wiring 37 Standard Tank Thermostat Wiring 38 High Ambient Air Kit Wiring 39 Building Recirculation Pump Wiring Diagram 40 PIPING DIAGRAMS 41 LIMITED WARRANTY 47 TABLE OF CONTENTS 3 SAFE...

Page 4: ...possible injury or death WARNING indicates a potentially hazardous situation which if not avoided could result in injury or death CAUTION indicates a potentially hazardous situation which if not avoi...

Page 5: ...er procedures or the use of non approved refrigerants refrigerant substitutes or refrigerant additives could result in death or serious injury or equipment damage Explosion Hazard Do not use oxygen to...

Page 6: ...G APPLIANCE INTRODUCTION 6 Detailed installation diagrams are in this manual These diagrams will serve to provide the installer with a reference for the materials and suggested methods of piping IT IS...

Page 7: ...flowing through the tubes and air flowing across the fins The Blower moves ambient air from the installed space or air ducted to the HPWH from another location across the fins of evaporator coil The r...

Page 8: ...IQUID COMPONENT WATER CIRCUIT A WATER INLET B WATER PUMP C HEAT EXCHANGER CONDENSER D WATER OUTLET WARM RETURN AIR IN COOL SUPPLY AIR OUT ACCUMULATOR COMPRESSOR CONDENSER HEAT EXCHANGER REFRIGERANT TO...

Page 9: ...8 660 AWH 115 33 1 113 000 89 000 7 4 4 2 3200 23 1 5 63 38 42 5 8 665 AWH 140 41 6 142 000 110 000 9 2 3 9 3800 28 2 0 63 38 42 5 8 725 AWH 170 50 1 171 000 133 000 11 1 3 9 4900 34 2 0 75 46 42 5 8...

Page 10: ...ating range the HPWH unit s Ambient Air Limit Thermostat will discontinue heating operation until the entering air temperature returns to this operating range See Figure 15 on page 37 High Ambient Air...

Page 11: ...ssary to access an adequate or greater source of heat for optimal efficiency See Building Air Pressure Air Flow and Ducting on page 19 CLEARANCES To ensure optimal performance a minimum of 30 inches c...

Page 12: ...this could result in death serious bodily injury or property damage The load current rating and the overcurrent protection for these conductors shall not exceed 15 amperes for 14 AWG 20 amperes for 1...

Page 13: ...demand of the application a Mixing Valve should be installed upstream from the building fixtures or at the hot water taps to further reduce system water temperature Mixing valves are available at plum...

Page 14: ...ause brain damage or death Always read and understand instruction manual Breathing Hazard Carbon Monoxide Gas The supply outlet air from a HPWH installed in a garage or a unit drawing return inlet air...

Page 15: ...unless spreader bars are furnished and used as depicted in Figure 4 and Figure 5 The side panels and roof of the unit are not constructed to handle significant force from the sides or above The HPWH...

Page 16: ...H in new construction the following critical points must be observed The HPWH unit 1 Must be installed indoors 2 Should be installed near a floor drain for condensate removal 3 The HPWH storage tank a...

Page 17: ...S 1 This HPWH unit is not designed to supply hot water directly to hot water fixtures The HPWH unit must be installed with a separate storage tank as shown in the water piping diagrams in this instruc...

Page 18: ...NK PRE HEAT CONFIGURATION When water temperatures above 140 F 60 C are required the HPWH and storage tank are piped in series upstream with a backup water heater See Water Temperature on page 10 The b...

Page 19: ...he building structure Gas and carbon monoxide detectors are available Breathing carbon monoxide can cause brain damage or death Always read and understand instruction manual Breathing Hazard Carbon Mo...

Page 20: ...r entering the HPWH unit the supply air may not be suitable for supplemental space cooling purposes The air temperature drops approximately 12 F to 20 F 7 C to 11 C as it flows through the HPWH unit I...

Page 21: ...12 14 16 18 20 22 24 MODEL CFM EXT in WG MAXIMUM EQUIVALENT LENGTH FEET AWH 35 1040 0 35 6 18 45 93 185 AWH 55 1650 0 35 3 8 18 40 77 137 AWH 75 2150 0 35 5 11 23 47 83 139 AWH 100 3200 0 35 3 6 14 26...

Page 22: ...t Water Temperature on page 10 See Figure 7 and Figure 8 on page 18 14 On two tank preheat piping configurations ensure the cold INSTALLATION CHECKLIST 22 water supply is not connected to the back up...

Page 23: ...mentioned above call the toll free technical support phone number on the back cover of this manual for further assistance 6 When all of the above procedures are complete adjust the tank temperature c...

Page 24: ...buttons to adjust to the desired differential set point 3 When complete press the SET button to save the change 4 The operating mode of the thermostat will be shown on the LED display next as CoL for...

Page 25: ...performing any maintenance on the blower assembly disconnect all power to the unit and follow the prescribed lock out tag out procedure Inspect and tighten all bearing collar and wheel set screws afte...

Page 26: ...plication and usage instructions 5 Allow the unit to dry thoroughly 6 If necessary apply an anti microbial agent on the insulation per the instructions provided on the product label 7 Discard collecte...

Page 27: ...t pump reduce piping or add booster pump clean heat exchanger with a mild acid wash open all shut off valves Heat pump is not running low pressure fault 1 Room temperature below 50 F 2 Blower not oper...

Page 28: ...in the inlet and outlet water piping connected between the HPWH unit and the storage tank On new installations ensure the maximum equivalent feet of inlet and outlet piping was not exceeded This is th...

Page 29: ...ent The cause of the pressure switch contacts opening must be corrected and the control system must be reset before the HPWH will resume compressor operation See Table 11 for pressure switch activatio...

Page 30: ...e containing a relay or triac transformer and several electronic components Leads from the internal motor sensors are connected to the module As the motor temperature rises or falls the resistance als...

Page 31: ...nits TABLE 13 ABBREVIATION DESCRIPTION WIRING NOTES PM Phase Monitor Factory If installed PC Pump Contactor Factory Load pump if installed BC Blower Contactor Factory CC Compressor Contactor Factory H...

Page 32: ...UNIT WIRING DIAGRAMS FUSE SIZES 208 230 VAC SINGLE PHASE 60 HZ 32...

Page 33: ...UNIT WIRING DIAGRAMS FUSE SIZES 208 230 VAC THREE PHASE 60 HZ AWH 35 AWH 55 and AWH 75 only 33...

Page 34: ...UNIT WIRING DIAGRAMS FUSE SIZES 208 230 VAC THREE PHASE 60 HZ only 34...

Page 35: ...UNIT WIRING DIAGRAMS FUSE SIZES 460 VAC THREE PHASE 60 HZ 35...

Page 36: ...UNIT WIRING DIAGRAMS FUSE SIZES 460 VAC THREE PHASE 60 HZ only 36...

Page 37: ...AIR TEMPERATURE SENSOR RANCO DIGITAL THERMOSTAT PART ETC 212000 000 24V COM NC NO C NC C NO DIGITAL TANK THERMOSTAT FULL GAUGE MODEL MT511Ri NOTE TANK TEMPERATURE SETTING MUST NOT EXCEED 140 F 60 C C...

Page 38: ...ATION NOTES 1 Configure stage 1 for cooling 2 Configure stage 2 for heating 3 Set cooling set point at 50 F 4 Set heating set point 95 F 5 Set cooling differential to 10 F 6 Set heating differential t...

Page 39: ...e on fall WHITE Close RED Close BLACK Close C NO NC 1 2 3 4 5 6 7 8 9 0 1 1 1 2 1 OUTPUT THERMOSTAT TERMINAL STRIP HPWH TERMINAL STRIP AMBIENT AIR LIMIT THERMOSTAT CONFIGURATION NOTES 1 Configure stag...

Page 40: ...NK FIELD SUPPLIED LINE TEMPERATURE CONTROL INSTALLED IN THE CIRCULATING LOOP RETURN LINE CIRC PUMP MOTOR L1 HOT L2 NEUTRAL 120 VAC POWER NOTE USE SEPARATE 120 VAC POWER SUPPLY FOR PUMP CIRCUIT Figure...

Page 41: ...URE RELIEF VALVE PRESSURE RELIEF VALVE CIRCULATING PUMP DRAIN WYE STRAINER FULL PORT BALL VALVE TEMPERATURE GAGE CHECK VALVE TANK OR LINE TEMPERATURE CONTROL WARNING THIS DRAWING SHOWS SUGGESTED PIPIN...

Page 42: ...E TEMPERATURE GAGE CHECK VALVE WARNING THIS DRAWING SHOWS SUGGESTED PIPING CONFIGURATION AND OTHER DEVICES CHECK WITH LOCAL CODES AND ORDINANCES FOR ADDITIONAL REQUIREMENTS TANK OR LINE TEMPERATURE CO...

Page 43: ...N COLD WATER SUPPLY LINE THERMOSTAT NOTE CONNECT BUILDING RECIRC RETURN TO INLET OF BACKUP WATER HEATER WHEN PRESENT TANK THERMOSTAT PIPE T P TO OPEN DRAIN RETURN WATER INLET PURGE VALVE SUPPLY WATER...

Page 44: ...ULL PORT BALL VALVE TEMPERATURE GAGE CHECK VALVE TANK OR LINE TEMPERATURE CONTROL WARNING THIS DRAWING SHOWS SUGGESTED PIPING CONFIGURATION AND OTHER DEVICES CHECK WITH LOCAL CODES AND ORDINANCES FOR...

Page 45: ...AND ORDINANCES FOR ADDITIONAL REQUIREMENTS LEGEND TEMPERATURE PRESSURE RELIEF VALVE PRESSURE RELIEF VALVE CIRCULATING PUMP DRAIN WYE STRAINER FULL PORT BALL VALVE TEMPERATURE GAGE CHECK VALVE TANK OR...

Page 46: ...ion of it in a modified form will void this warranty 4 SERVICE REPAIR AND EXPENSE Under this limited warranty the warrantor will provide only a replacement heat pump water heater or part thereof The o...

Page 47: ...talled Dealer s Name Dealer s Address Phone No City and State Zip Fill in the following for your own reference Keep it Registration is not a condition of warranty The model and serial number are found...

Page 48: ...500 Tennessee Waltz Parkway Ashland City TN 37015 Technical Support 800 527 1953 Parts 800 433 2545 Fax 800 644 9306 www hotwater com...

Reviews: