A.O. Smith AWH-35 Instruction Manual Download Page 20

20

Negative Pressure

Ducting  supply  air  only  to  an  alternate  location,  such  as  the 

outdoors, may cause excessive negative air pressure inside the 

building envelope. 
Excessive  negative  pressure  inside  the  building  structure  may 

result  in  cold  or  hot  air  from  outdoors  being  drawn  inside  the 

building and place additional load on space heating and cooling 

equipment.  Negative  air  pressure  in  buildings  can  also  cause 

reverse flow in chimneys and gas vents.

Positive Pressure

Ducting return air only from an alternate location, such as the 

outdoors, may cause excessive positive air pressure inside the 

building envelope.
Excessive  positive  pressure  inside  the  building  structure  may 

place additional load on space heating and cooling equipment by 

interfering with the delivery of conditioned air.

WHEN TO INSTALL DUCTING

HPWH  units  are  often  installed  in  unoccupied  spaces  or 

equipment  rooms  where  there  is  an  ample  source  of  ambient 

heat and no need to redirect the supply air to another location. 

Ductwork  is  not  necessary  in  these  circumstances.  See  Heat 

Source and Conditioned Space on page 10 and Unconditioned 

Space on page 11.
Typical applications when ducting is installed. 

•  Duct supply (outlet) air to alternate location for spot cooling 

or discard supply air not wanted in the installed space.

•  Duct return (inlet) air from an alternate location (outdoors, 

warm equipment room) to optimize efficiency.

SUPPLY AIR DUCTING

Observe  and  follow  these  guidelines  and  instructions  when 

installing supply (outlet) air duct:

Sharp Spinning Blades! 

The blower operates at a high RPM that can cause injury. To 

prevent  inadvertent  access to the blower opening, supply 

ducting or other  suitable means  to  prevent  access  must 

be  provided.

DANGER

1.  When  duct  work  is  not  field  connected  to  the  supply  air 

outlet  on  the  HPWH  unit  a  field  supplied  safety  guard 

must be installed over the supply air connection. Failure 

to comply could result in severe injury.

2.  All ductwork and plenums shall be field supplied or fabricated.
3.  The total equivalent length of all supply and return air ducting 

must not exceed the maximum equivalent lengths shown in 

Table 6 or Table 7 on page 21.

4.  Cooling output (supply air) from the HPWH is supplemental 

only  and  must  not  be  factored  into  sizing  calculations  for 

space cooling equipment. Cooling output  is only produced 

when  the  HPWH  is  operating  to  satisfy  a  water  heating 

demand.  Once  the  storage  tank  temperature  is  satisfied, 

the HPWH will stop until the next water heating demand is 

initiated regardless of space cooling needs. 

5.  Depending on the temperature of the air entering the HPWH 

unit  the  supply  air  may  not  be  suitable  for  supplemental 

space cooling purposes.
The air temperature drops approximately 12°F to 20°F (7°C 

to 11°C) as it flows through the HPWH unit. If the return air 

to  the  HPWH  unit  is  derived  from  a  location  that  is  above 

80°F (27°C) the supply air from the HPWH unit will not be 

suitable  for  offsetting  the  building  cooling  load.  This  will 

often be the case when the return air is ducted from a warm 

equipment room or from the outdoor atmosphere. In these 

circumstances do not duct supply air to another location for 

spot cooling.

6.  Ducting supply air only to an alternate location, such as the 

outdoors, may cause excessive negative air pressure inside 

the building envelope.
Provision must be made to prevent a negative pressure in 

the installed space or building envelope. Return air must be 

supplied  to  the  HPWH  from  the  alternate  location  through 

ducting  or  louvers  that  communicate  with  the  alternate 

location where the supply ducting terminates. See the Return 

Air Ducting section that follows.

RETURN AIR DUCTING

Observe  and  follow  these  guidelines  and  instructions  when 

installing return (inlet) air duct:
1.  All ductwork and plenums shall be field supplied or fabricated.
2.  The total equivalent length of all supply and return air ducting 

must not exceed the maximum equivalent lengths shown in 

Table 6 or Table 7 on page 21.

3.  When  installing  return  air  duct  to  the  HPWH  unit  a  field 

supplied/fabricated filter access door must be installed.

4.  Ducting return air only from an alternate location, such as the 

outdoors, may cause excessive positive air pressure inside 

the building envelope.
Provision  must  be  made  to  prevent  a  positive  pressure  in 

the installed space or building envelope. Supply air must be 

supplied  to  the  HPWH  from  the  alternate  location  through 

ducting that communicates with the alternate location from 

where the return air is derived. See the preceding Supply Air 

Ducting section.

5.  If  the  alternate  location  where  return  air  is  derived  from 

has temperatures above 95°F (35°C) for extended periods 

the  accessory  High Ambient Air  Kit  should  be  installed  for 

optimum efficiency. See 

page 39

BLOWER ASSEMBLY ADJUSTMENTS

Sharp Spinning Blades! 

The blower operates at a high RPM that can cause injury. To 

prevent  inadvertent  access to the blower opening, supply 

ducting or other  suitable means  to  prevent  access  must 

be  provided.

DANGER

The  HPWH  blower  is  a  belt  driven  assembly.  The  blower  belt 

and sheaves are factory pre-set and should not require any field 

adjustment. The blower assembly should be checked to ensure 

the blower wheel moves freely and that sufficient tension is on 

the blower belt. If belt looseness is suspected, check the blower 

maintenance section of the manual for re-set recommendations.

Summary of Contents for AWH-35

Page 1: ...70 SERIES 100 INSTALLATION OPERATION SERVICE MAINTENANCE LIMITED WARRANTY 820 SW 41st Street Renton WA 98057 Read and understand this instruction manual and the safety messages herein before installin...

Page 2: ......

Page 3: ...ank Thermostat Wiring 37 Standard Tank Thermostat Wiring 38 High Ambient Air Kit Wiring 39 Building Recirculation Pump Wiring Diagram 40 PIPING DIAGRAMS 41 LIMITED WARRANTY 47 TABLE OF CONTENTS 3 SAFE...

Page 4: ...possible injury or death WARNING indicates a potentially hazardous situation which if not avoided could result in injury or death CAUTION indicates a potentially hazardous situation which if not avoi...

Page 5: ...er procedures or the use of non approved refrigerants refrigerant substitutes or refrigerant additives could result in death or serious injury or equipment damage Explosion Hazard Do not use oxygen to...

Page 6: ...G APPLIANCE INTRODUCTION 6 Detailed installation diagrams are in this manual These diagrams will serve to provide the installer with a reference for the materials and suggested methods of piping IT IS...

Page 7: ...flowing through the tubes and air flowing across the fins The Blower moves ambient air from the installed space or air ducted to the HPWH from another location across the fins of evaporator coil The r...

Page 8: ...IQUID COMPONENT WATER CIRCUIT A WATER INLET B WATER PUMP C HEAT EXCHANGER CONDENSER D WATER OUTLET WARM RETURN AIR IN COOL SUPPLY AIR OUT ACCUMULATOR COMPRESSOR CONDENSER HEAT EXCHANGER REFRIGERANT TO...

Page 9: ...8 660 AWH 115 33 1 113 000 89 000 7 4 4 2 3200 23 1 5 63 38 42 5 8 665 AWH 140 41 6 142 000 110 000 9 2 3 9 3800 28 2 0 63 38 42 5 8 725 AWH 170 50 1 171 000 133 000 11 1 3 9 4900 34 2 0 75 46 42 5 8...

Page 10: ...ating range the HPWH unit s Ambient Air Limit Thermostat will discontinue heating operation until the entering air temperature returns to this operating range See Figure 15 on page 37 High Ambient Air...

Page 11: ...ssary to access an adequate or greater source of heat for optimal efficiency See Building Air Pressure Air Flow and Ducting on page 19 CLEARANCES To ensure optimal performance a minimum of 30 inches c...

Page 12: ...this could result in death serious bodily injury or property damage The load current rating and the overcurrent protection for these conductors shall not exceed 15 amperes for 14 AWG 20 amperes for 1...

Page 13: ...demand of the application a Mixing Valve should be installed upstream from the building fixtures or at the hot water taps to further reduce system water temperature Mixing valves are available at plum...

Page 14: ...ause brain damage or death Always read and understand instruction manual Breathing Hazard Carbon Monoxide Gas The supply outlet air from a HPWH installed in a garage or a unit drawing return inlet air...

Page 15: ...unless spreader bars are furnished and used as depicted in Figure 4 and Figure 5 The side panels and roof of the unit are not constructed to handle significant force from the sides or above The HPWH...

Page 16: ...H in new construction the following critical points must be observed The HPWH unit 1 Must be installed indoors 2 Should be installed near a floor drain for condensate removal 3 The HPWH storage tank a...

Page 17: ...S 1 This HPWH unit is not designed to supply hot water directly to hot water fixtures The HPWH unit must be installed with a separate storage tank as shown in the water piping diagrams in this instruc...

Page 18: ...NK PRE HEAT CONFIGURATION When water temperatures above 140 F 60 C are required the HPWH and storage tank are piped in series upstream with a backup water heater See Water Temperature on page 10 The b...

Page 19: ...he building structure Gas and carbon monoxide detectors are available Breathing carbon monoxide can cause brain damage or death Always read and understand instruction manual Breathing Hazard Carbon Mo...

Page 20: ...r entering the HPWH unit the supply air may not be suitable for supplemental space cooling purposes The air temperature drops approximately 12 F to 20 F 7 C to 11 C as it flows through the HPWH unit I...

Page 21: ...12 14 16 18 20 22 24 MODEL CFM EXT in WG MAXIMUM EQUIVALENT LENGTH FEET AWH 35 1040 0 35 6 18 45 93 185 AWH 55 1650 0 35 3 8 18 40 77 137 AWH 75 2150 0 35 5 11 23 47 83 139 AWH 100 3200 0 35 3 6 14 26...

Page 22: ...t Water Temperature on page 10 See Figure 7 and Figure 8 on page 18 14 On two tank preheat piping configurations ensure the cold INSTALLATION CHECKLIST 22 water supply is not connected to the back up...

Page 23: ...mentioned above call the toll free technical support phone number on the back cover of this manual for further assistance 6 When all of the above procedures are complete adjust the tank temperature c...

Page 24: ...buttons to adjust to the desired differential set point 3 When complete press the SET button to save the change 4 The operating mode of the thermostat will be shown on the LED display next as CoL for...

Page 25: ...performing any maintenance on the blower assembly disconnect all power to the unit and follow the prescribed lock out tag out procedure Inspect and tighten all bearing collar and wheel set screws afte...

Page 26: ...plication and usage instructions 5 Allow the unit to dry thoroughly 6 If necessary apply an anti microbial agent on the insulation per the instructions provided on the product label 7 Discard collecte...

Page 27: ...t pump reduce piping or add booster pump clean heat exchanger with a mild acid wash open all shut off valves Heat pump is not running low pressure fault 1 Room temperature below 50 F 2 Blower not oper...

Page 28: ...in the inlet and outlet water piping connected between the HPWH unit and the storage tank On new installations ensure the maximum equivalent feet of inlet and outlet piping was not exceeded This is th...

Page 29: ...ent The cause of the pressure switch contacts opening must be corrected and the control system must be reset before the HPWH will resume compressor operation See Table 11 for pressure switch activatio...

Page 30: ...e containing a relay or triac transformer and several electronic components Leads from the internal motor sensors are connected to the module As the motor temperature rises or falls the resistance als...

Page 31: ...nits TABLE 13 ABBREVIATION DESCRIPTION WIRING NOTES PM Phase Monitor Factory If installed PC Pump Contactor Factory Load pump if installed BC Blower Contactor Factory CC Compressor Contactor Factory H...

Page 32: ...UNIT WIRING DIAGRAMS FUSE SIZES 208 230 VAC SINGLE PHASE 60 HZ 32...

Page 33: ...UNIT WIRING DIAGRAMS FUSE SIZES 208 230 VAC THREE PHASE 60 HZ AWH 35 AWH 55 and AWH 75 only 33...

Page 34: ...UNIT WIRING DIAGRAMS FUSE SIZES 208 230 VAC THREE PHASE 60 HZ only 34...

Page 35: ...UNIT WIRING DIAGRAMS FUSE SIZES 460 VAC THREE PHASE 60 HZ 35...

Page 36: ...UNIT WIRING DIAGRAMS FUSE SIZES 460 VAC THREE PHASE 60 HZ only 36...

Page 37: ...AIR TEMPERATURE SENSOR RANCO DIGITAL THERMOSTAT PART ETC 212000 000 24V COM NC NO C NC C NO DIGITAL TANK THERMOSTAT FULL GAUGE MODEL MT511Ri NOTE TANK TEMPERATURE SETTING MUST NOT EXCEED 140 F 60 C C...

Page 38: ...ATION NOTES 1 Configure stage 1 for cooling 2 Configure stage 2 for heating 3 Set cooling set point at 50 F 4 Set heating set point 95 F 5 Set cooling differential to 10 F 6 Set heating differential t...

Page 39: ...e on fall WHITE Close RED Close BLACK Close C NO NC 1 2 3 4 5 6 7 8 9 0 1 1 1 2 1 OUTPUT THERMOSTAT TERMINAL STRIP HPWH TERMINAL STRIP AMBIENT AIR LIMIT THERMOSTAT CONFIGURATION NOTES 1 Configure stag...

Page 40: ...NK FIELD SUPPLIED LINE TEMPERATURE CONTROL INSTALLED IN THE CIRCULATING LOOP RETURN LINE CIRC PUMP MOTOR L1 HOT L2 NEUTRAL 120 VAC POWER NOTE USE SEPARATE 120 VAC POWER SUPPLY FOR PUMP CIRCUIT Figure...

Page 41: ...URE RELIEF VALVE PRESSURE RELIEF VALVE CIRCULATING PUMP DRAIN WYE STRAINER FULL PORT BALL VALVE TEMPERATURE GAGE CHECK VALVE TANK OR LINE TEMPERATURE CONTROL WARNING THIS DRAWING SHOWS SUGGESTED PIPIN...

Page 42: ...E TEMPERATURE GAGE CHECK VALVE WARNING THIS DRAWING SHOWS SUGGESTED PIPING CONFIGURATION AND OTHER DEVICES CHECK WITH LOCAL CODES AND ORDINANCES FOR ADDITIONAL REQUIREMENTS TANK OR LINE TEMPERATURE CO...

Page 43: ...N COLD WATER SUPPLY LINE THERMOSTAT NOTE CONNECT BUILDING RECIRC RETURN TO INLET OF BACKUP WATER HEATER WHEN PRESENT TANK THERMOSTAT PIPE T P TO OPEN DRAIN RETURN WATER INLET PURGE VALVE SUPPLY WATER...

Page 44: ...ULL PORT BALL VALVE TEMPERATURE GAGE CHECK VALVE TANK OR LINE TEMPERATURE CONTROL WARNING THIS DRAWING SHOWS SUGGESTED PIPING CONFIGURATION AND OTHER DEVICES CHECK WITH LOCAL CODES AND ORDINANCES FOR...

Page 45: ...AND ORDINANCES FOR ADDITIONAL REQUIREMENTS LEGEND TEMPERATURE PRESSURE RELIEF VALVE PRESSURE RELIEF VALVE CIRCULATING PUMP DRAIN WYE STRAINER FULL PORT BALL VALVE TEMPERATURE GAGE CHECK VALVE TANK OR...

Page 46: ...ion of it in a modified form will void this warranty 4 SERVICE REPAIR AND EXPENSE Under this limited warranty the warrantor will provide only a replacement heat pump water heater or part thereof The o...

Page 47: ...talled Dealer s Name Dealer s Address Phone No City and State Zip Fill in the following for your own reference Keep it Registration is not a condition of warranty The model and serial number are found...

Page 48: ...500 Tennessee Waltz Parkway Ashland City TN 37015 Technical Support 800 527 1953 Parts 800 433 2545 Fax 800 644 9306 www hotwater com...

Reviews: