A.O. Smith AWH-35 Instruction Manual Download Page 17

ELECTRICAL CONNECTIONS

CORRECT POWER SUPPLY!

Ensure the power supply at the job site matches the

voltage and phase listed on the HPWH rating label

before connecting power to the HPWH unit.

Damage caused to the HPWH as the result of applying

the wrong voltage or phase is not covered under the

limited warranty.

Energizing the HPWH with the wrong voltage or phase 

will cause permanent damage to the HPWH unit.

CAUTION

CORRECT VOLTAGE AND PHASE

The  HPWH  units  covered  by  this  instruction  manual  can 

be  ordered  with  multiple  power  supply  voltage  and  phase 

configurations.  Ensure  the  power  supply  voltage  and  phase 

at  the  job  site  matches  the  power  supply  ratings  listed  on  the 

HPWH rating label BEFORE INSTALLATION BEGINS.
Voltage applied to the HPWH should not vary more than +5% to 

-10% of the voltage requirement listed on the HPWH rating label 

for satisfactory operation.
Energizing the HPWH with the wrong voltage and/or phase may  

cause  permanent  damage  to  HPWH  components.  Damage 

resulting from applying the wrong power supply voltage or phase 

to the HPWH is not covered under the limited warranty.

Before removing any access panels or

servicing the water heater, make sure

the electrical supply to the water heater

is turned “OFF.”

Electrical Shock Hazard

Failure to do this could result in death,

serious bodily injury, or property

damage.

BRANCH CIRCUIT DISCONNECT SWITCH

The  power  supply  wiring  and  equipment  grounding  must  be 

installed  in  accordance  with  local  codes  or,  in  the  absence  of 

local codes,  the National Electrical Code, ANSI/NFPA 70 or the 

Canadian Electrical Code, CSA C22.1. 
Install an adequately fused disconnect switch as close to the unit 

as possible. See unit rating label for maximum fuse size (MFS). 
Run the power supply lines from the disconnect to the control box 

at the side panel of the unit. Connect the lines to the terminals on 

input side of power distribution block L1 

&

 L2 

for single phase

 and

L1

, L2

 & 

L3 f

or

 

three phase

s

Connect ground wire to ground lug.

See Minimum Circuit Ampacity & Maximum Fuse Size on page 

12 for wire, fuse and breaker sizing information.

TRANSFORMER CONFIGURATION 208 VAC MODELS

The transformer leads must be changed on units connected to 

a 208 VAC power supply as described below. See Unit Wiring 

Diagrams-Fuse Sizes

 on

 page

s 32-36

 for 

component locations

BEFORE CONNECTING THE THERMOSTAT, turn on power to 

the HPWH momentarily and measure the voltage to the primary 

winding of the transformer at the F3 fuse block. If the measured 

WATER CONNECTIONS

Water piping must be installed in accordance with the instructions 

in this manual and all local plumbing codes having jurisdiction. 

See Figure 7 and Figure 8 on page 18 and the Piping Diagrams 

on page 4

1

 as a reference for these instructions. 

INSTALLATION INSTRUCTIONS 

1.  This HPWH unit is not designed to supply hot water directly 

to hot water fixtures. The HPWH unit must be installed with a 

separate storage tank as shown in the water piping diagrams 

in this instruction manual.

2.  Water lines installed between the storage tank and the HPWH 

unit 

MUST NOT be less than the water pipe connection sizes 

on the unit. See Table 4 on page 13.

3. 

T

he HPWH should be plumbed directly to the storage tank. 

4.  The  cold  water  supply  must  be  connected  directly  to  the 

storage  tank  at  a  low  connection  port  on  the  storage  tank 

on single tank and two tank preheat piping configurations

 for 

optimal efficiency. See Figure 7 and Figure 8 on page 

18

5.  The  cold  water  supply  MUST  NOT  be  connected  the  inlet 

(entering/return) water line to the HPWH unit.

6.  The outlet (supply) water from the HPWH unit should connect 

to a middle or lower port on the storage tank.

7.  The inlet (return) water from the HPWH unit should connect 

to a port on the storage tank lower than the outlet.

8.  A heat trap should be installed between the storage tank and 

the backup water heater on two tank preheat systems. See 

Piping Diagram

 on page 41

.

9.  A T&P valve must be installed in the designated opening on 

the storage tank per the tank manufacturer’s requirements. 

See Temperature - Pressure Relief Valve on page 14.

10. Factory installed water pumps can provide the unit specified 

water  flow  for  up  to  a  total  of  50  equivalent  feet  of  piping 

between  the  HPWH  unit  and  the  storage  tank.  IE:  25 

equivalent feet of inlet piping and 25 equivalent feet of outlet 

piping.  Do  not  exceed  this  maximum  equivalent  feet  on 

models equipped with factory-installed pumps.

11. For optimal  performance minimize  the equivalent  length of  

water piping between the HPWH and storage tank.

12. Building hot water recirculation loop should be connected to 

the  inlet  of  the  backup  water    heater  on  two  tank  preheat 

configurations  or  to  the  storage  tank  on  single  tank 

configurations. The recirculating pump MUST BE controlled 

by  a  field  supplied  thermostat  installed  in  the  building 

recirculation  return  line  near  the  storage  tank  or  back  up 

heater.  The  thermostat  should  stop  pump  operation  the 

moment the recirculation line is hot.

13. Use  swing-type  check  valves  (not  spring-loaded  types)  on 

the water outlet lines of all HPWH units plumbed in parallel to 

prevent hot water short-circuiting. 

14. Water  lines  shared  by  parallel  HPWH  units  must  be  large 

enough to handle combined water flows. Flow rates through 

the heat pumps and tank(s) must be balanced. See Table 1 

on page 9 fo

r HPWH unit flow rates.

voltage is above 215 VAC no changes are necessary. 
If  the  measured  voltage  is  215  VAC  or  less,  then  the  primary 

leads of the transformer must be changed from the 230 VAC tap 

to the 208 VAC tap. Do this by disconnecting the orange wire 

from  the  transformer  primary  terminal  and  replacing  with  the 

red wire. Before reapplying power, ensure orange lead is safely 

isolated with a wire nut and electrical tape.

17

Summary of Contents for AWH-35

Page 1: ...70 SERIES 100 INSTALLATION OPERATION SERVICE MAINTENANCE LIMITED WARRANTY 820 SW 41st Street Renton WA 98057 Read and understand this instruction manual and the safety messages herein before installin...

Page 2: ......

Page 3: ...ank Thermostat Wiring 37 Standard Tank Thermostat Wiring 38 High Ambient Air Kit Wiring 39 Building Recirculation Pump Wiring Diagram 40 PIPING DIAGRAMS 41 LIMITED WARRANTY 47 TABLE OF CONTENTS 3 SAFE...

Page 4: ...possible injury or death WARNING indicates a potentially hazardous situation which if not avoided could result in injury or death CAUTION indicates a potentially hazardous situation which if not avoi...

Page 5: ...er procedures or the use of non approved refrigerants refrigerant substitutes or refrigerant additives could result in death or serious injury or equipment damage Explosion Hazard Do not use oxygen to...

Page 6: ...G APPLIANCE INTRODUCTION 6 Detailed installation diagrams are in this manual These diagrams will serve to provide the installer with a reference for the materials and suggested methods of piping IT IS...

Page 7: ...flowing through the tubes and air flowing across the fins The Blower moves ambient air from the installed space or air ducted to the HPWH from another location across the fins of evaporator coil The r...

Page 8: ...IQUID COMPONENT WATER CIRCUIT A WATER INLET B WATER PUMP C HEAT EXCHANGER CONDENSER D WATER OUTLET WARM RETURN AIR IN COOL SUPPLY AIR OUT ACCUMULATOR COMPRESSOR CONDENSER HEAT EXCHANGER REFRIGERANT TO...

Page 9: ...8 660 AWH 115 33 1 113 000 89 000 7 4 4 2 3200 23 1 5 63 38 42 5 8 665 AWH 140 41 6 142 000 110 000 9 2 3 9 3800 28 2 0 63 38 42 5 8 725 AWH 170 50 1 171 000 133 000 11 1 3 9 4900 34 2 0 75 46 42 5 8...

Page 10: ...ating range the HPWH unit s Ambient Air Limit Thermostat will discontinue heating operation until the entering air temperature returns to this operating range See Figure 15 on page 37 High Ambient Air...

Page 11: ...ssary to access an adequate or greater source of heat for optimal efficiency See Building Air Pressure Air Flow and Ducting on page 19 CLEARANCES To ensure optimal performance a minimum of 30 inches c...

Page 12: ...this could result in death serious bodily injury or property damage The load current rating and the overcurrent protection for these conductors shall not exceed 15 amperes for 14 AWG 20 amperes for 1...

Page 13: ...demand of the application a Mixing Valve should be installed upstream from the building fixtures or at the hot water taps to further reduce system water temperature Mixing valves are available at plum...

Page 14: ...ause brain damage or death Always read and understand instruction manual Breathing Hazard Carbon Monoxide Gas The supply outlet air from a HPWH installed in a garage or a unit drawing return inlet air...

Page 15: ...unless spreader bars are furnished and used as depicted in Figure 4 and Figure 5 The side panels and roof of the unit are not constructed to handle significant force from the sides or above The HPWH...

Page 16: ...H in new construction the following critical points must be observed The HPWH unit 1 Must be installed indoors 2 Should be installed near a floor drain for condensate removal 3 The HPWH storage tank a...

Page 17: ...S 1 This HPWH unit is not designed to supply hot water directly to hot water fixtures The HPWH unit must be installed with a separate storage tank as shown in the water piping diagrams in this instruc...

Page 18: ...NK PRE HEAT CONFIGURATION When water temperatures above 140 F 60 C are required the HPWH and storage tank are piped in series upstream with a backup water heater See Water Temperature on page 10 The b...

Page 19: ...he building structure Gas and carbon monoxide detectors are available Breathing carbon monoxide can cause brain damage or death Always read and understand instruction manual Breathing Hazard Carbon Mo...

Page 20: ...r entering the HPWH unit the supply air may not be suitable for supplemental space cooling purposes The air temperature drops approximately 12 F to 20 F 7 C to 11 C as it flows through the HPWH unit I...

Page 21: ...12 14 16 18 20 22 24 MODEL CFM EXT in WG MAXIMUM EQUIVALENT LENGTH FEET AWH 35 1040 0 35 6 18 45 93 185 AWH 55 1650 0 35 3 8 18 40 77 137 AWH 75 2150 0 35 5 11 23 47 83 139 AWH 100 3200 0 35 3 6 14 26...

Page 22: ...t Water Temperature on page 10 See Figure 7 and Figure 8 on page 18 14 On two tank preheat piping configurations ensure the cold INSTALLATION CHECKLIST 22 water supply is not connected to the back up...

Page 23: ...mentioned above call the toll free technical support phone number on the back cover of this manual for further assistance 6 When all of the above procedures are complete adjust the tank temperature c...

Page 24: ...buttons to adjust to the desired differential set point 3 When complete press the SET button to save the change 4 The operating mode of the thermostat will be shown on the LED display next as CoL for...

Page 25: ...performing any maintenance on the blower assembly disconnect all power to the unit and follow the prescribed lock out tag out procedure Inspect and tighten all bearing collar and wheel set screws afte...

Page 26: ...plication and usage instructions 5 Allow the unit to dry thoroughly 6 If necessary apply an anti microbial agent on the insulation per the instructions provided on the product label 7 Discard collecte...

Page 27: ...t pump reduce piping or add booster pump clean heat exchanger with a mild acid wash open all shut off valves Heat pump is not running low pressure fault 1 Room temperature below 50 F 2 Blower not oper...

Page 28: ...in the inlet and outlet water piping connected between the HPWH unit and the storage tank On new installations ensure the maximum equivalent feet of inlet and outlet piping was not exceeded This is th...

Page 29: ...ent The cause of the pressure switch contacts opening must be corrected and the control system must be reset before the HPWH will resume compressor operation See Table 11 for pressure switch activatio...

Page 30: ...e containing a relay or triac transformer and several electronic components Leads from the internal motor sensors are connected to the module As the motor temperature rises or falls the resistance als...

Page 31: ...nits TABLE 13 ABBREVIATION DESCRIPTION WIRING NOTES PM Phase Monitor Factory If installed PC Pump Contactor Factory Load pump if installed BC Blower Contactor Factory CC Compressor Contactor Factory H...

Page 32: ...UNIT WIRING DIAGRAMS FUSE SIZES 208 230 VAC SINGLE PHASE 60 HZ 32...

Page 33: ...UNIT WIRING DIAGRAMS FUSE SIZES 208 230 VAC THREE PHASE 60 HZ AWH 35 AWH 55 and AWH 75 only 33...

Page 34: ...UNIT WIRING DIAGRAMS FUSE SIZES 208 230 VAC THREE PHASE 60 HZ only 34...

Page 35: ...UNIT WIRING DIAGRAMS FUSE SIZES 460 VAC THREE PHASE 60 HZ 35...

Page 36: ...UNIT WIRING DIAGRAMS FUSE SIZES 460 VAC THREE PHASE 60 HZ only 36...

Page 37: ...AIR TEMPERATURE SENSOR RANCO DIGITAL THERMOSTAT PART ETC 212000 000 24V COM NC NO C NC C NO DIGITAL TANK THERMOSTAT FULL GAUGE MODEL MT511Ri NOTE TANK TEMPERATURE SETTING MUST NOT EXCEED 140 F 60 C C...

Page 38: ...ATION NOTES 1 Configure stage 1 for cooling 2 Configure stage 2 for heating 3 Set cooling set point at 50 F 4 Set heating set point 95 F 5 Set cooling differential to 10 F 6 Set heating differential t...

Page 39: ...e on fall WHITE Close RED Close BLACK Close C NO NC 1 2 3 4 5 6 7 8 9 0 1 1 1 2 1 OUTPUT THERMOSTAT TERMINAL STRIP HPWH TERMINAL STRIP AMBIENT AIR LIMIT THERMOSTAT CONFIGURATION NOTES 1 Configure stag...

Page 40: ...NK FIELD SUPPLIED LINE TEMPERATURE CONTROL INSTALLED IN THE CIRCULATING LOOP RETURN LINE CIRC PUMP MOTOR L1 HOT L2 NEUTRAL 120 VAC POWER NOTE USE SEPARATE 120 VAC POWER SUPPLY FOR PUMP CIRCUIT Figure...

Page 41: ...URE RELIEF VALVE PRESSURE RELIEF VALVE CIRCULATING PUMP DRAIN WYE STRAINER FULL PORT BALL VALVE TEMPERATURE GAGE CHECK VALVE TANK OR LINE TEMPERATURE CONTROL WARNING THIS DRAWING SHOWS SUGGESTED PIPIN...

Page 42: ...E TEMPERATURE GAGE CHECK VALVE WARNING THIS DRAWING SHOWS SUGGESTED PIPING CONFIGURATION AND OTHER DEVICES CHECK WITH LOCAL CODES AND ORDINANCES FOR ADDITIONAL REQUIREMENTS TANK OR LINE TEMPERATURE CO...

Page 43: ...N COLD WATER SUPPLY LINE THERMOSTAT NOTE CONNECT BUILDING RECIRC RETURN TO INLET OF BACKUP WATER HEATER WHEN PRESENT TANK THERMOSTAT PIPE T P TO OPEN DRAIN RETURN WATER INLET PURGE VALVE SUPPLY WATER...

Page 44: ...ULL PORT BALL VALVE TEMPERATURE GAGE CHECK VALVE TANK OR LINE TEMPERATURE CONTROL WARNING THIS DRAWING SHOWS SUGGESTED PIPING CONFIGURATION AND OTHER DEVICES CHECK WITH LOCAL CODES AND ORDINANCES FOR...

Page 45: ...AND ORDINANCES FOR ADDITIONAL REQUIREMENTS LEGEND TEMPERATURE PRESSURE RELIEF VALVE PRESSURE RELIEF VALVE CIRCULATING PUMP DRAIN WYE STRAINER FULL PORT BALL VALVE TEMPERATURE GAGE CHECK VALVE TANK OR...

Page 46: ...ion of it in a modified form will void this warranty 4 SERVICE REPAIR AND EXPENSE Under this limited warranty the warrantor will provide only a replacement heat pump water heater or part thereof The o...

Page 47: ...talled Dealer s Name Dealer s Address Phone No City and State Zip Fill in the following for your own reference Keep it Registration is not a condition of warranty The model and serial number are found...

Page 48: ...500 Tennessee Waltz Parkway Ashland City TN 37015 Technical Support 800 527 1953 Parts 800 433 2545 Fax 800 644 9306 www hotwater com...

Reviews: