Shield (see Figure 2). This Shield reflects heat from the
High-input heaters to prevent damage to combustible floors.
The Shield is held in place by three (3) tabs that rest on the
inside of the legs of the water heater. Ensure the Shield is
positioned horizontally (parallel to the bottom of the heater)
and in the designated position of 38mm (1.5 in.) below the
flame-arrestor.
The water heater shall be located in an area not subject to

freezing temperatures. Water heaters located in uncondi-
tioned spaces (e.g., attics, basements, etc.) may require
insulation of the water and drain piping to protect against
freezing. Proper ventilation needs to be provided for water
heaters installed in unconditioned spaces (e.g., attics, base-
ments, etc.) in order to avoid an event where air tempera-
ture exceeds 42°C (108°F). The drain and controls must be
easily accessible for operation and service. Maintain proper
clearances as specified on the data plate.
Ensure that the water heater is level. This heater may be
installed in a closet or alcove and is certified for operation
on a combustible floor.
Do not locate the water heater near an air-moving device.
The operation of air-moving devices such as exhaust fans,
ventilation systems, clothes dryers, fireplaces, etc., can

affect the proper operation of the water heater. Special
attention must be given to conditions these devices may
create. Flow reversal of flue gases may cause an increase
of carbon monoxide inside of the dwelling, as shown in
Figure 7.
If the water heater is located in an area that is subject to an
excessive amount of lint, dirt or oil, it may be necessary to
clean the flame arrestor periodically (see “Maintenance”
section).

Important:

It is always recommended that a suitable drain

pan be installed under the water heater to protect the area
from water damage resulting from normal condensation, a
leaking tank or piping connections. Refer to Figure 1. Under
no circumstances is the manufacturer to be held responsi-
ble for any water damage in connection with this water
heater.

Gas Supply

Install the gas piping as shown in Figure 4. Use only new
pipe and fittings with clean-cut threads. Sealing compounds
used on the pipe threads shall be approved for use with nat-
ural and propane gas.
Use gas piping of adequate sizing to ensure gas input. Gas
piping material must be approved for use with natural gas
and propane fuels. All piping must comply with all local
codes and with the latest edition of 

“Natural Gas and

Propane Installation Code” CAN/CSA-B149.1

in Canada,

“National Fuel Gas Code” ANSI Z223.1 (NFPA 54)

in the

U.S.A. The final connection to the water heater is made
using 1/2” NPT.
Before connecting to the gas service, check that a properly
sized gas meter and regulator are available to service the
water heater. If other appliances are using the same meter
and regulator, ensure that the capacity of the meter and reg-
ulator matches that of the combined input of all appliances
connected to it.

DO NOT

tamper with the gas control/thermostat, igniter,

thermocouple, or temperature and pressure relief valve.
Tampering voids all warranties. Only a qualified service
technician should service these components.

WARNING

Do not install directly on carpet. Instead, place the
water heater on a metal or wood panel extending a
minimum of 75mm (3 in.) from all sides. In alcoves or
closets, cover the carpet completely. Ensure this
panel is capable of supporting the weight of this
heater when filled with water.
FAILURE TO PROPERLY INSTALL THIS HEATER MAY
RESULT IN A FIRE HAZARD.

Figure 3

Minimum Clearance Locations

AIR INTAKE

VENT

FRONT 600mm
(24 in.) MIN.
FOR SERVICE

BACK 25mm (1 in.)

SIDES
25mm
(1 in.)

SIDES AND
BACK 25mm
(1 in.)

TOP TO CEILING
200mm (8 in.)

Figure 2

Heat Shield Installation (60 gallon only)

HEAT SHIELD

FLAME

ARRESTOR

DRAIN
VALVE

LEG

BOTTOM

PAN

Figure 4

Recommended Gas Piping

GROUND-

JOINT UNION

MANUAL

GAS

SHUT-OFF

GAS CONTROL/THERMOSTAT

75mm (3 in.)

– 6 –

Summary of Contents for ATMOSPHERIC VENTED WATER HEATER

Page 1: ...TY Do not store or use gasoline or other flammable vapours and liquids in the vicinity of this or any other appliance Installation and service must be per formed by a qualified installer service agenc...

Page 2: ...lation 13 Electrical Supply 14 24 Volt Control precautions Installations Check 15 IV OPERATING INSTRUCTIONS 15 Water Temperature Regulation 15 Temperature Adjustment Lighting Instructions White Rodger...

Page 3: ...e outside In addition to the installation instructions found in this man ual the heater shall be installed according to all local and provincial or state codes and with the latest edition of the follo...

Page 4: ...Shut Off Devices for Hot Water Supply Systems ANSI Z21 22 is applicable If this water heater has been exposed to flooding freezing fire or any unusual condition do not put it into operation until it h...

Page 5: ...firm clearances Heaters with a volume of 19 gallons through 50 gallons and 60 gallon standard input must have the following minimum clearances to combustibles Front 102mm 4 in Sides and Rear 25mm 1 in...

Page 6: ...ng tank or piping connections Refer to Figure 1 Under no circumstances is the manufacturer to be held responsi ble for any water damage in connection with this water heater Gas Supply Install the gas...

Page 7: ...occur To avoid risk of fire or explosion ensure the area is well ventilated and all sources of ignition are de activated Contact your local gas authority for local requirements Gas Leak Testing Impor...

Page 8: ...Refer to Figure 5 a or b and Table 2 for proper sizing and location of combustion air ducts and openings CHECK LOCAL CODES a Two permanent openings shall be provided connecting the confined space e g...

Page 9: ...quipment located in confined spaces all air from outdoors When supplying air directly from the outdoors using hor izontal ducting each opening shall have a free mini mum area of one square inch per 2...

Page 10: ...Figure 8 CSA U L recognized fuel gas and carbon monoxide CO detectors are recommended in all applications and should be installed using the manufacturer s instructions and local codes rules or regula...

Page 11: ...lves that may cause excessive restriction to water flow Use full flow ball or gate valves only DO NOT use any lead based solder in potable water lines Use appropriate tin antimony or other equivalent...

Page 12: ...eater Do not use an old or existing valve as it may be damaged or not adequate for the working pressure of the new water heater Do not place any valve between the relief valve and the tank The Tempera...

Page 13: ...h ing connection point see Figure 14 Hold this connec tion in place against the heater Slide it up enough to pinch the lower connection post into the matching con nection point in place with your fing...

Page 14: ...er is installed in accordance with prevailing provisions of local codes and the latest edition of Canadian Electrical Code CAN CSA C22 1 Part I Canada or National Electrical Code NFPA 70 U S A Before...

Page 15: ...nd combustible construction as per specifica tions 7 Is the water piping correctly connected Are you certain that there are no leaks 8 Is the water heater filled with water 9 Is the cold water supply...

Page 16: ...the appliance and call for service Valves for reducing the point of use temperature by mixing cold and hot water are available see Figure 11 Also avail able are inexpensive devices that attach to fau...

Page 17: ...through the view port Do not release the gas control knob Repeat immediately if pilot does not light on the first try If the pilot does not light by the fourth attempt with the igniter repeat steps 5...

Page 18: ...un appareil en marche N actionnez aucun interrupteur lectrique n utilisez aucun t l phone de votre b timent Appelez imm diatement votre fournisseur de gaz depuis un voisin et suivez les instructions d...

Page 19: ...ons Condensation Moisture from the products of combustion condenses on the tank surface and forms drops of water which may fall onto the burner or other hot surfaces This will produce a siz zling or f...

Page 20: ...24 Volt Damper Models The 24 Volt control valve is in constant communications with the different components that are connected to it ensuring all components are in the proper positions and in working...

Page 21: ...This lockout is required to allow the control to reset itself If the gas control valve is submerged under water for any length of time the gas control valve assembly should be replaced LED FLASH SEQU...

Page 22: ...ing to be shut down for an extended period the drain valve should be left open Important Condensation may occur when refilling tank and should not be confused with a tank leak The following maintenanc...

Page 23: ...or 6 Restart the water heater following the Operating Instructions 7 If the pilot burner does not stay lit after several attempts it is possible that the TCO embedded in the safety switch opened due t...

Page 24: ...ngage the pins on the valve module 4 Re assemble in the reverse order Note Care is required to align the pins on the valve module to their proper location in the control module during re assembly Valv...

Page 25: ...ressure with the hand on the valve pins Note Care is required to align the pins on the valve module to their proper location in the control module during re assembly When re installing the gas control...

Page 26: ...those used for boiler treatment into the potable water used for space heating 3 Do not use this heater as a replacement for an existing boiler installation 4 If the space heating water system requires...

Page 27: ...OO SMALL 1 Pilot line or orifice clogged 2 Low gas pressure 3 Defective pilot 1 Clean locate source and correct 2 Check with gas utility company 3 Replace pilot INSUFFICIENT HOT WATER 1 Thermostat set...

Page 28: ...tat 2 Low gas pressure 3 Orifice not properly installed 1 Replace gas control thermostat 2 Check with gas utility company 3 Reinstall the orifice 1 Air in gas line 2 Defective pilot electrode 3 Cold d...

Page 29: ...Y QUICK CONNECT LEADS Figure 33 Repair Parts Heaters without 24V vent damper 12 11 13 15 14 10 9 16 4 8 5 3 6 7 2 1 IX REPAIR PARTS ILLUSTRATION 1 NIPPLE HOT OUTLET 2 NIPPLE COLD INLET 3 DRAFTHOOD 4 T...

Page 30: ...D TUBE 17 PILOT THERMOCOUPLE ASSEMBLY 18 VIEWPORT 19 TWO PIECE GROMMET WITH CLIP 20 MANIFOLD DOOR 21 GAS MANIFOLD 22 PILOT TUBE 23 GAS ORIFICE 24 MANIFOLD DOOR GASKET 25 BURNER Figure 36 Manifold Door...

Page 31: ...31 This page intentionally left blank May be used for notes or to record other installation information...

Page 32: ...599 Hill Street West Fergus ON Canada N1M 2X1 PHONE 1 888 479 8324 www hotwatercanada ca email techsupport hotwater com...

Reviews: