background image

the installation drawing (Figure 10). If the indoor installation
area is subject to freezing temperatures, the water piping
must be protected by insulation. Water supply pressure
should not exceed 550 kPa (80psi). If this occurs a pressure
reducing valve and/or an expansion tank may be required.
The pressure reducing valve should be placed on the sup-
ply to the entire house in order to maintain equal hot and
cold water pressures.

Important:

Heat must not be applied to the water fittings on

the heater as they may contain nonmetallic parts. If solder
connections are used, solder the pipe to the adapter before
attaching the adapter to the hot and cold water fittings.

Install the water piping and fittings as shown in Figure 10.
Connect the cold water supply to the fitting (3/4” NPT)
marked “COLD” (or “C”). Connect the hot water supply to
the fitting (3/4” NPT) marked “HOT” (or “H”).

Important:

Always use a good grade of joint compound,

approved for use with potable water systems, and be certain
that all fittings are drawn up tight.

Important:

Some models may contain energy saving heat

traps to prevent the circulation of hot water within the pipes.
Do not remove, modify or tamper with the heat traps or any
inserts within the heat traps.

Union Connections

If a union connection is required we recommend raising the
union above the draft-hood as illustrated in Figure 10. If gal-
vanized piping is used, we recommend a galvanized nipple
extension or a galvanized coupler with a pipe nipple to raise
the union above the draft-hood. Same procedure applies if
using copper.

Please note the following:

DO NOT

install this water heater with iron piping. The sys-

tem should be installed only with new piping that is suitable
for potable (drinkable) water such as copper, CPVC or poly-
butylene. DO NOT use PVC water piping.

DO NOT

use any pumps, valves or fittings that are not com-

patible with potable water.

DO NOT

use valves that may cause excessive restriction to

water flow. Use full flow ball or gate valves only.

DO NOT

use any lead based solder in potable water lines.

Use appropriate tin-antimony or other equivalent material.

DO NOT

use with piping that has been treated with chro-

mates, boiler seal or other chemicals.

DO NOT

add any chemicals to the system piping that will

contaminate the potable water supply.

Mixing Valves

Hot water can scald:

Water heaters are intended to pro-

duce hot water. Water heated to a temperature that will sat-
isfy space heating, clothes washing, dish washing, and
other sanitizing needs can scald and permanently injure you
upon contact. Some people are more likely to be perma-
nently injured by hot water than others. These include the
elderly, children, the infirm, and physically/mentally handi-
capped.
If any one using the hot water fits into one of these groups
or if there is a provincial, state or local code requiring a cer-
tain temperature water at the hot water faucet, then you
must take special precautions. In addition to using the low-
est possible temperature setting that will satisfy your hot-
water needs, a means such as a mixing valve, should be
used at the hot-water faucets or at the water heater. Mixing
valves are available at plumbing supply or hardware stores.
Follow manufacturer’s instructions for installation of these
valves. Before changing the factory settings on the thermo-
stat, read the “Temperature Regulation” section in this man-
ual.

Closed System/Thermal Expansion

Periodic discharge from the temperature and pressure relief
valve may be due to thermal expansion in a closed water
supply system. The water utility supply meter may contain a

Figure 11

Typical Tempering Valve Installation

TEMPERING VALVE

(SET TO 49°C (120°F))

FOLLOW THE TEMPERING

VALVE MANUFACTURER'S

INSTRUCTIONS

COLD WATER INLET

PIPE

INSULATION

HOT WATER

OUTLET

TEMPERED

WATER TO

FIXTURE

WARNING

Never allow small children to use a hot-water
faucet, or to draw their own bath water.
Never leave a child or impaired person unat-
tended in a bathtub or shower. Scald burns
can result.

– 11 –

Summary of Contents for ATMOSPHERIC VENTED WATER HEATER

Page 1: ...TY Do not store or use gasoline or other flammable vapours and liquids in the vicinity of this or any other appliance Installation and service must be per formed by a qualified installer service agenc...

Page 2: ...lation 13 Electrical Supply 14 24 Volt Control precautions Installations Check 15 IV OPERATING INSTRUCTIONS 15 Water Temperature Regulation 15 Temperature Adjustment Lighting Instructions White Rodger...

Page 3: ...e outside In addition to the installation instructions found in this man ual the heater shall be installed according to all local and provincial or state codes and with the latest edition of the follo...

Page 4: ...Shut Off Devices for Hot Water Supply Systems ANSI Z21 22 is applicable If this water heater has been exposed to flooding freezing fire or any unusual condition do not put it into operation until it h...

Page 5: ...firm clearances Heaters with a volume of 19 gallons through 50 gallons and 60 gallon standard input must have the following minimum clearances to combustibles Front 102mm 4 in Sides and Rear 25mm 1 in...

Page 6: ...ng tank or piping connections Refer to Figure 1 Under no circumstances is the manufacturer to be held responsi ble for any water damage in connection with this water heater Gas Supply Install the gas...

Page 7: ...occur To avoid risk of fire or explosion ensure the area is well ventilated and all sources of ignition are de activated Contact your local gas authority for local requirements Gas Leak Testing Impor...

Page 8: ...Refer to Figure 5 a or b and Table 2 for proper sizing and location of combustion air ducts and openings CHECK LOCAL CODES a Two permanent openings shall be provided connecting the confined space e g...

Page 9: ...quipment located in confined spaces all air from outdoors When supplying air directly from the outdoors using hor izontal ducting each opening shall have a free mini mum area of one square inch per 2...

Page 10: ...Figure 8 CSA U L recognized fuel gas and carbon monoxide CO detectors are recommended in all applications and should be installed using the manufacturer s instructions and local codes rules or regula...

Page 11: ...lves that may cause excessive restriction to water flow Use full flow ball or gate valves only DO NOT use any lead based solder in potable water lines Use appropriate tin antimony or other equivalent...

Page 12: ...eater Do not use an old or existing valve as it may be damaged or not adequate for the working pressure of the new water heater Do not place any valve between the relief valve and the tank The Tempera...

Page 13: ...h ing connection point see Figure 14 Hold this connec tion in place against the heater Slide it up enough to pinch the lower connection post into the matching con nection point in place with your fing...

Page 14: ...er is installed in accordance with prevailing provisions of local codes and the latest edition of Canadian Electrical Code CAN CSA C22 1 Part I Canada or National Electrical Code NFPA 70 U S A Before...

Page 15: ...nd combustible construction as per specifica tions 7 Is the water piping correctly connected Are you certain that there are no leaks 8 Is the water heater filled with water 9 Is the cold water supply...

Page 16: ...the appliance and call for service Valves for reducing the point of use temperature by mixing cold and hot water are available see Figure 11 Also avail able are inexpensive devices that attach to fau...

Page 17: ...through the view port Do not release the gas control knob Repeat immediately if pilot does not light on the first try If the pilot does not light by the fourth attempt with the igniter repeat steps 5...

Page 18: ...un appareil en marche N actionnez aucun interrupteur lectrique n utilisez aucun t l phone de votre b timent Appelez imm diatement votre fournisseur de gaz depuis un voisin et suivez les instructions d...

Page 19: ...ons Condensation Moisture from the products of combustion condenses on the tank surface and forms drops of water which may fall onto the burner or other hot surfaces This will produce a siz zling or f...

Page 20: ...24 Volt Damper Models The 24 Volt control valve is in constant communications with the different components that are connected to it ensuring all components are in the proper positions and in working...

Page 21: ...This lockout is required to allow the control to reset itself If the gas control valve is submerged under water for any length of time the gas control valve assembly should be replaced LED FLASH SEQU...

Page 22: ...ing to be shut down for an extended period the drain valve should be left open Important Condensation may occur when refilling tank and should not be confused with a tank leak The following maintenanc...

Page 23: ...or 6 Restart the water heater following the Operating Instructions 7 If the pilot burner does not stay lit after several attempts it is possible that the TCO embedded in the safety switch opened due t...

Page 24: ...ngage the pins on the valve module 4 Re assemble in the reverse order Note Care is required to align the pins on the valve module to their proper location in the control module during re assembly Valv...

Page 25: ...ressure with the hand on the valve pins Note Care is required to align the pins on the valve module to their proper location in the control module during re assembly When re installing the gas control...

Page 26: ...those used for boiler treatment into the potable water used for space heating 3 Do not use this heater as a replacement for an existing boiler installation 4 If the space heating water system requires...

Page 27: ...OO SMALL 1 Pilot line or orifice clogged 2 Low gas pressure 3 Defective pilot 1 Clean locate source and correct 2 Check with gas utility company 3 Replace pilot INSUFFICIENT HOT WATER 1 Thermostat set...

Page 28: ...tat 2 Low gas pressure 3 Orifice not properly installed 1 Replace gas control thermostat 2 Check with gas utility company 3 Reinstall the orifice 1 Air in gas line 2 Defective pilot electrode 3 Cold d...

Page 29: ...Y QUICK CONNECT LEADS Figure 33 Repair Parts Heaters without 24V vent damper 12 11 13 15 14 10 9 16 4 8 5 3 6 7 2 1 IX REPAIR PARTS ILLUSTRATION 1 NIPPLE HOT OUTLET 2 NIPPLE COLD INLET 3 DRAFTHOOD 4 T...

Page 30: ...D TUBE 17 PILOT THERMOCOUPLE ASSEMBLY 18 VIEWPORT 19 TWO PIECE GROMMET WITH CLIP 20 MANIFOLD DOOR 21 GAS MANIFOLD 22 PILOT TUBE 23 GAS ORIFICE 24 MANIFOLD DOOR GASKET 25 BURNER Figure 36 Manifold Door...

Page 31: ...31 This page intentionally left blank May be used for notes or to record other installation information...

Page 32: ...599 Hill Street West Fergus ON Canada N1M 2X1 PHONE 1 888 479 8324 www hotwatercanada ca email techsupport hotwater com...

Reviews: