is
Instruction manual ADMR
67
Explosive ignition
Poor flame profile
Incorrect supply
pressure and/or burner
pressure
Set the correct supply pressure and/or burner
pressure. (3.11 "Checking the supply pressure and burner
pressure")
If ignition is not improved, consult your installation engineer.
Contaminated burner
Clean the burner(s) (15.4.2 "Clean the burner(s)")
Contaminated orifice
Clean the orifice(s) (15.3.4 "Clean the orifice(s)")
Inadequate air supply
Improve the air supply by providing better ventilation in the boiler
room.
Hot water supply
insufficient or absent
Appliance is turned off
Start the appliance up (9 "Starting and running")
No supply voltage
present
1. Check if the isolator is ON.
2. Check that there is power to the isolator.
3. Check whether the ON/OFF switch of the electronic controller is
ON (position I).
4. Check whether there is power to the electrical connector block.
5. The measured voltage must be 230 VAC (-15%, +10%).
See the ADMR electrical diagram (17 "Appendices")
If the error persists, consult your installation engineer.
Hot water supply is
used up
Reduce hot water consumption and give the appliance time to heat
up.
If there continues to be insufficient hot water, or none at all, consult
your installation engineer.
The controller is in OFF
mode.
Switch the controller to the ON mode (11.2 "Switching on the "ON
mode"")
Temperature (T
set
) is
set too low.
Adjust (11.3 "Setting the water temperature") temperature (T
set
) to
a higher value.
Symptom
Cause
Solution
Remark
Summary of Contents for ADMR - 40
Page 4: ...4 Instruction manual ADMR gis ...
Page 10: ...Introduction 10 Instruction manual ADMR 1 gis ...
Page 54: ...Shutting down 54 Instruction manual ADMR 10 gis ...
Page 62: ...Main menu 62 Instruction manual ADMR 11 gis ...
Page 76: ...is Instruction manual ADMR 76 ...
Page 78: ...Maintenance frequency 78 Instruction manual ADMR 14 is ...
Page 84: ...Performing maintenance 84 Instruction manual ADMR 15 s ...
Page 92: ...Appendices 92 Instruction manual ADMR 17 is ...
Page 94: ...Instruction manual ADMR 94 ...