Installation
34
Instruction manual ADMR
3
is
Gas control for ADMR 135
3.11.1
Preparation
1. Isolate the appliance from the power supply (10.3 "Electrically isolating the
appliance").
2. There are two test nipples on the gas control. Test nipple (6) is used to check
the supply pressure. The other test nipple on the gas control is not used. The
manifold test nipple (8) is used to measure the burner pressure.
Sealing screws are located inside the test nipples. Loosen both sealing
screws by a few turns. Do not completely loosen them; they can be difficult
to re-tighten.
3. Connect a pressure gauge to the manifold test nipple (8).
4. Open the gas supply and bleed the air from the mains gas supply via test
nipple (6).
5. Connect a pressure gauge to the manifold test nipple (6) when gas starts to
flow from this nipple.
6. Switch on the power to the appliance using the isolator on the appliance.
7. Switch the electronic controller
ON
by setting the 0/I switch to
position I
.
Legend
Only applicable numbers are
mentioned.
1. burner pressure regulator
2. burner pressure regulator cap
3. burner pressure regulator
adjustment screw
6. supply pressure test nipple
7. gas control
8. manifold test nipple
9. high-low control
1
9
6
7
8
2
3
IMD-0129 R1
Summary of Contents for ADMR - 40
Page 4: ...4 Instruction manual ADMR gis ...
Page 10: ...Introduction 10 Instruction manual ADMR 1 gis ...
Page 54: ...Shutting down 54 Instruction manual ADMR 10 gis ...
Page 62: ...Main menu 62 Instruction manual ADMR 11 gis ...
Page 76: ...is Instruction manual ADMR 76 ...
Page 78: ...Maintenance frequency 78 Instruction manual ADMR 14 is ...
Page 84: ...Performing maintenance 84 Instruction manual ADMR 15 s ...
Page 92: ...Appendices 92 Instruction manual ADMR 17 is ...
Page 94: ...Instruction manual ADMR 94 ...