Installation
16
Instruction manual ADMR
3
is
3.3.1
Air humidity and ambient temperature
The boiler room must be frost-free, or be protected against frost. The table
shows the environmental conditions that must be adhered to for correct
functioning of the electronics present in the appliance to be guaranteed.
Air humidity and ambient temperature specifications
3.3.2
Maximum floor load
In connection with the appliance's weight, take account of the maximum floor
loading, refer to the table.
3.3.3
Water composition
The appliance is intended for heating drinking water. The drinking water must
comply with the regulations governing drinking water for human consumption.
The table gives an overview of the specifications.
Water specifications
Note
If the water specifications deviate from those stated in the table, then the
tank protection cannot be guaranteed (16 "Warranty (certificate)").
Air humidity and ambient temperature
Air humidity
max. 93% RV at +25 °C
Ambient temperature
Functional: 0 < T < 60 °C
Weight of the appliance filled with water
ADMR 40
ADMR 50
ADMR 60
ADMR 80
ADMR 90
ADMR 115
ADMR 135
504 kg
578 kg
507 kg
573 kg
522 kg
523 kg
581 kg
Water composition
Hardness
(alkaline earth ions)
> 1.00 mmol/l:
•
German hardness> 5.6° dH
•
French hardness > 10.0° fH
•
English hardness > 7.0° eH
Conductivity
> 125 µS/cm
Acidity (pH value)
7.0 < pH value < 9.5
Summary of Contents for ADMR - 40
Page 4: ...4 Instruction manual ADMR gis ...
Page 10: ...Introduction 10 Instruction manual ADMR 1 gis ...
Page 54: ...Shutting down 54 Instruction manual ADMR 10 gis ...
Page 62: ...Main menu 62 Instruction manual ADMR 11 gis ...
Page 76: ...is Instruction manual ADMR 76 ...
Page 78: ...Maintenance frequency 78 Instruction manual ADMR 14 is ...
Page 84: ...Performing maintenance 84 Instruction manual ADMR 15 s ...
Page 92: ...Appendices 92 Instruction manual ADMR 17 is ...
Page 94: ...Instruction manual ADMR 94 ...