BTR TANK TYPE HEATERS
SERVICE WORKBOOK
A.O. Smith Water Products
Service Handbook
Irving, Texas ©2000
Training Department
43
GENERAL SERVICE CHART
CONDITION
CAUSE
SOLUTION
DAMPER OPENS NO POWER
TO IID MODULE
. DAMPER NOT FULLY OPEN
. DEFECTIVE PROTECTOR
SWITCH
.EFFIKAL – REPLACE DAMPER CONTROL
ASSEMBLY
. REPLACE DAMPER
. REPLACE PC BOARD
PILOT LIGHTS, SPARKS
CONTINUOUSLY
PILOT FLAME NOT PROVING
SEE FLAME RECTIFICATION - STEP 16
HEATER WILL NOT IGNITE
NOT PROVING PILOT
FLAME EXISTANCE
INTERRUPT 120 VAC POWER
. CHECK GROUND WIRE
ATTACHMENT
. CLEAN OR REPLACE PILOT
ASSEMBLY
PILOT GAS NOT COMPLETELY
INTERRUPTED AT END OF
HEATING CYCLE
. CHECK SUPPLY GAS PRESSURE
. REPLACE GAS VALVE
. THERMAL EXPANSION
ADD THERMAL EXPANSION TANK
WEEPING TEMPERATURE
AND
PRESSURE RELIEF VALVE
. FAULTY VALVE
REPLACE RELIEF VALVE
. EXCESSIVE WATER
TEMPERATURE
. CHECK WIRING
. REPLACE DUAL CONTROLLER
LARGE VOLUME WATER
RELIEF FROM T&P VALVE
. FAULTY RELIEF VALVE
REPLACE RELIEF VALVE
PREMATURE TANK
LEAKAGE
CONDENSATION
. INCREASE STORED WATER
TEMPERATURE AND CONFIRM
PROPERLY SIZED APPLICATION
CONTAMINATED AIR
. REMOVE CONTAMINANTS.
. SUPPLY CLEAN COMBUSTION
AIR.
WATER HAMMER
. ADD WATER HAMMER
ARRESTOR.
. REDUCE WATER PRESSURE.
. REMOVE UNNECESSARY CHECK
VALVES.
THERMAL EXPANSION
ADD THERMAL EXPANSION TANK.
DEPLETED ANODES
SCHEDULE ANODE CHECKS -
REPLACE AS NEEDED.
DAMPER WILL NOT OPEN
BINDING SHAFT
SUPPORT VENTING
SHAFT SPRING WEAK/BROKEN
REPLACE DAMPER NON-EFFIKALS
DAMPER MOTOR
REPLACE MOTOR EFFIKAL-REPLACE DAMPER
CONTROL ASSEMBLY
NO SPARK AT PILOT -
DAMPER FULLY OPEN
DAMPER ASSEMBLY
REPLACE PC BOARD - SEE STEP 10
Services Switch may bypass problem until
replacement part is received. (EFFIKAL –
REPLACE DAMPER CONTROL ASSEMBLY
IID MODULE
REPLACE IID STEP 12
SPARK CABLE
REPLACE CABLE STEP 13