Commissioning & Decomissioning LVRSys™
6.1
Lights & Switches
Figure 6-1 Lights and switches
1
System switch (0: position off; 1: position on)
2
Signal lamp (green: operation; red: error)
Table 6-1 Explanation of numbering
6.2
Commissioning and decomissioning LVRSys™
For operating the LVRSys IN, LVRSys OUT and BYPASS, observe chapter 6.5.
The starting position is:
0
Closed BYPASS (F3).
0
Opened input (F1 / LVRSys IN).
0
Opened output (F5 / LVRSys OUT ).
0
The controller is in the Off state.
DANGER!
Risk of fatal injury from electric shock!
Ensure that the LVRSysTM is only operated and put into operation by
qualified electricians or persons trained in electrical engineering who
are either certified in accordance with VDE 0105-100 or certified with
respect to the local wiring and safety regulations applicable in your
country.
Never partially open LV fuse switch disconnectors.
Only ever actuate LV fuse switch disconnectors by using the handle.
CAUTION!
Destruction of components due to overload!
Only Switch the LVRSys™ On and Off as described above.
Never activate BYPASS during CONTROL operation.