Page 18
We take care of it.
5.2
Fuse protection (internal side)
System
F8 (3x)
F9 (3x)
Resistors Trafo
big-X2
Resistors
Trafo small-X2
32 A 6 % to
32 A 10 %
D01GG40V16
582.1203
X
MI5HT25V0,63
582.1020.00.63
MI5HT25V0,63
582.1020.00.63
63 A 6 % to
160 A 6 %
D02GG40V25
582.1205
X
MI5HT25V2
582.1020.02
MI5HT25V0,63
582.1020.00.63
160 A 8 % to
160 A 10 %
D02GG40V25
582.1205
X
MI5HT25V5
582.1020.05
MI5HT25V1
582.1020.01
200 A 6 % to
355 A 8 %
D02GG40V40
582.1207
X
MI5HT25V5
582.1020.05
MI5HT25V2
582.1020.02
355 A 10 % to
580 A 8 %
NH00GR50V80
582.1246
D02GG40V25
582.1205
MI5HT25V8
582.1020.08
MI5HT25V5
582.1020.05
580 A 10 % to
910 A 6 %
NH00GR50V100
582.1247
D02GG40V35
582.1206
MI5HT25V8
582.1020.08
MI5HT25V5
582.1020.05
910 A 8 % to
910 A 10 %
NH00GR50V125
D02GG40V50
582.1208
MI6SA12,5V25
MI5HT25V6,3
582.1020.06.30
Table 5-7 Protection of the systems internal side
Measuring voltage taps Output voltage (XF) are protected with G-fuse links super-fast FA
5x20 3.15 A (MI5FA25V3.15 / 582.1018). Measuring Voltages Input voltage (XF) are
protected by G-fuse links super-fast FA 6.3x32 3.15 A (MI6FA25V3.15).