6.3 CONNECTING THE AIr PIPING
6.3.-1 Flexible connection
Connect the pipes to the exhaust and the suction necks
using flexible connections to stop the transfer of vibrations
and it allows easier removal of the unit from the installation
place when servicing.
Type
DN
HRV14EC
160
HRV15AC
160
HRV15EC
160
HRV30AC
160
HRV30EC
160
HRV50AC
250
HRV50EC
250
HRV70AC
250
HRV70EC
250
YOU WILL NEED
•
Side nut wrenches
• 4 flexible connection sleeves
• Cross head screwdriver
• Sealing tape, sealant
DN
6. INSTALLATION
DO NOT MISS!
•
The connected pipes must be of the same diameter as the ex-
haust and suction necks. If pipes of a smaller diameter will be
used, the unit performance could drop and in some cases the
lifespan of the ventilators could also decrease.
•
Any joints between the air distribution pipes and the unit
must be sealed using a sealant or a sealing tape.
•
The minimum distance of the bent air pipes or adapting pie-
ces from the unit neck should be 500 mm.
6.3-2 Protective grid
In the event that some of the necks of the unit will not be used
for connecting pipes, it is necessary to fix the opening with a
grid for protection from touching the rotating parts of ventilator,
heater bars etc..