2VV.
Creating innovative solutions for you and your business since 1995.
ver.8 07-12-19
6. INSTALLATION
The unit is not designed for the filtration of air containing
flammable or combustible compounds, chemical fumes,
rough dust, black carbon, grease, poisons, germs etc.
IP protection of the unit mounted into the pipelines is
the IP 20 type (protection against objects larger than
12.5 mm, not protected from water!)
6.1-1 Built up dimensions
The unit must be installed in such a way that the direction of
the air flow throughout the unit corresponds with the air flow
in the distribution system.
The unit must be installed in such a way that the direction of
the air flow throughout the unit corresponds with the air flow
in the distribution system.
6.1.-2 Required distances
ATTENTION
Non-flammable materials must not obstruct the suction and
exhaust openings.
•
The safe distance of flammable materials from the entry neck
of the unit is 500 mm.
•
The safe distance of flammable materials in the remaining
directions is 100 mm.
6.1.-3 Mounting of the unit
500 mm
380 mm
•
These dimensions are recommended for servicing access.
TECHNICAL INFORMATION
• All types of ventilation units can be installed in following
positions:
•
Any other position is prohibited.
•
The unit must be installed in such a way that the direction of
the air flow throughout the unit corresponds with the air flow
in the distribution system.
•
The unit installation must allow for sufficient access for main-
tenance, service purposes or its dismantling. The access main-
ly concerns the revision lids allowing their opening.
MATERIAL OK
MATERIAL OK
100 mm
100 mm
500 mm
500 mm
806
515
1 351
960
M8
M8
•
4xM8 - Threaded rods
•
16xM8 Nut
(not supplied in delivery)
•
8xM8 Large washers
(supplied in delivery)