4
5
2VV.
Creating innovative solutions for you and your business since 1995.
ver.8 07-12-19
5. TECHNICAL PARAMETERS
Type
Maxi-
mum
airflow
[m3/h]
Supply
filter
class
Exhaust
filter
class
Phase
[pcs]
Voltage
[V]
Fre-
quen-
cy
[Hz]
Fan
power
[W]
Pre-he-
ater
Input
[kW]
Weight
[kg]
L
p
A at
3m
[dB]
Noise
surroun-
dings
L
w
A [dB]
Noise
suction
supply
L
w
A
[dB]
Noise
suction
exhaust
L
w
A [dB]
Duct
diame-
ter
[mm]
Unit
hei-
ght
[mm]
Unit
width
[mm]
Unit
length
[mm]
HRV14EC
185
F7
G4
1
230
50/60
53
0,6
19,5
37,7
59,0
57,9
66,2
160
270
555
1000
HRV15AC
185
M5+G2
G4
1
230
50
105
1,0
17,4
37,3
58,6
55,1
64,8
160
270
555
1000
HRV15EC
175
F7
G4
1
230
50/60
65
1,0
17,2
37,7
59
57,9
66,2
160
270
555
1000
HRV30AC
265
M5+G2
G4
1
230
50
145
1,3
19,5
38,9
60,2
58,9
66,4
160
270
555
1000
HRV30EC
315
F7
G4
1
230
50/60
170
1,3
19,3
43,5
64,8
64,7
72,3
160
270
555
1000
HRV50AC
515
M5+G2
G4
1
230
50
230
2,5
35
47,1
68,8
59
69,6
250
360
846
1391
HRV50EC
535
F7
G4
1
230
50/60
220
2,5
35,5
45,8
67,2
56,3
68,7
250
360
846
1391
HRV70AC
650
M5+G2
G4
1
230
50
270
2,5
40
42,9
64,5
59,1
67,3
250
360
846
1391
HRV70EC
785
F7
G4
1
230
50/60
430
2,5
40,7
53,6
75,2
63,7
74,7
250
360
846
1391
Airflow output characteristic
6. INSTALLATION
6.1 CHOOSE THE PLACE OF INSTALLATION
TECHNICAL INFORMATION
It must be operated inside covered and dry areas with a room
temperature ranging from
+5°C up to +40°C.
+5°C
+40°C
The filtered air should have a temperature ranging from -20°C
up to +40°C and relative humidity up to 90%.
-20 °C
+40 °C
max. 90%
T
HE
vENTILATION
UNIT
PrOjECT
SHALL
ALwAyS
bE
DEvELOPEr
by
THE
HvAC