6. INSTALLATION
ATTENTION
•
Threaded rods must be able to take the weight of the unit!
•
Considering the weight of the unit, it is necessary to use
suitable lifting equipment (a fork lift truck etc.) or use
two or more persons who will hold it up until it is safely
mounted
•
Measure up the place of installation
•
Drill the holes into the wall and hang the unit on threaded
bars on all corners of the unit.
YOU WILL NEED
•
4 wall plugs according to type and size of the screw (also
depending on the ceiling material and the weight of the unit)
•
Electric drill and drills of the relevant size
6.2 CONNECTING THE CONDENSATION
wATEr OUTLET
YOU WILL NEED
•
drain hose 1/2“
h1=150mm
The remaining holes blind
by plugs.
Connect the siphon on to the neck and the drain pipe which will
lead to the sewerage system.
DO NOT MISS!
•
Check whether the unit is tilted so the condensate may run off
freely (we suggest 5° tilt, see the figure below).
•
The siphon must be connected and sealed properly in the
heat exchange unit.
DO NOT MISS!
Check the following prior to the first activation of the ventilation
unit:
•
That unit is correctly attached to the framework.
•
That unit is closed properly, all of the necks are connec-
ted to the pipelines or protected with a grid and therefore
there is no risk of injury from rotating or hot parts.
•
Electrical connections must correspond with wiring dia-
gram.
•
That all electrical components are correctly connected.
•
That condensation water outlet is connected to the drai-
nage
•
That installation corresponds with all instructions from
this manual
•
That there are no tools or other objects left inside the unit
which could damage it.
•
Whether unit includes a clean filters.
ATTENTION!
•
Interventions and changes to the internal connection of the
unit are prohibited, they may lead to warranty loss.
•
We suggest using the accessories supplied by our company.
In case of any doubts in use of the original accessories please
contact the supplier.
5 °
ATTENTION
I
mPrOPEr
CONNECTION
OF
THE
SIPHON
mAy
CAUSE
FLOODING
AND
DAmAGE
TO
THE
HEAT
ExCHANGE
UNIT
.
T
HE
SIPHON
(SK-HL138)
mAy
bE
INSTALLED
ON
THE
wALL
Or
CONCEALED
.