9
Type of air
curtain
Postflow *
Air
output
Noise
[dB(A)]**
Heater output ***
Heater
power supply
Fans power
supply
Weight
[m]
[m³/h]
3m
5m
[kW]
[V/A]
[V/A]
[kg]
VCIN...150-S0AC
7,5
11550
67,5
63,0
-
-
230/3,9
51
VCIN...150-V2AC
10300
67,5
63,1
91,3***
-
230/3,9
60
VCIN...150-P2AC
VCIN...150-E1AC
11550
67,5
63,0
24,3
400/35,2
230/3,9
55
VCIN...200-S0AC
8,0
15100
69,3
64,9
-
-
230/5,1
69
VCIN...200-V2AC
13700
68,4
64,0
123***
-
230/5,4
78
VCIN...200-P2AC
VCIN...200-E1AC
15100
69,3
64,9
32,4
400/47,0
230/5,1
74
VCIN...250-S0AC
7,5
18500
71,1
66,7
-
-
230/6,5
83
VCIN...250-V2AC
17000
70,0
65,5
154***
-
230/6,7
98
VCIN...250-P2AC
VCIN...250-E1AC
18500
71,1
66,7
40,5
400/58,6
230/6,5
89
Type of air
curtain
Postflow *
Air
output
Noise
[dB(A)]**
Heater output ***
Heater
power supply
Fans power
supply
Weight
[m]
[m³/h]
3m
5m
[kW]
[V/A]
[V/A]
[kg]
VCIN...150-S0EC
7,5
11400
#
#
-
-
230/3,87
51
VCIN...150-V2EC
10500
#
#
#
-
230/3,95
60
VCIN...150-P2EC
VCIN...150-E1EC
11400
#
#
#
400/35,2
230/3,87
55
VCIN...200-S0EC
8,0
15200
#
#
-
-
230/5,16
69
VCIN...200-V2EC
13700
#
#
#
-
230/5,27
78
VCIN...200-P2EC
VCIN...200-E1EC
15200
#
#
#
400/47,0
230/5,16
74
VCIN...250-S0EC
7,5
19000
#
#
-
-
230/6,45
83
VCIN...250-V2EC
17500
#
#
#
-
230/6,85
98
VCIN...250-P2EC
VCIN...250-E1EC
19000
#
#
#
400/58,6
230/6,45
89
*
The distance at which the medium speed of air flow drops to 3 m / s.
(under optimal conditions and max. output of device, measured according to ISO 27327-1))
**
Acoustic pressure at a distance of 3 m or 5 m from the air curtain and parameter Q = 2.
*** With the temperature water gradient 110/80 ° C and the intake air tempe 15 ° C.
6. TECHNICAL SPECIFICATIONS
# Other specifications can be found in the technical sheet of the product
EC
AC