Spacing distances
Only non-flammable materials
(do not burn, do not glow, do not carbonize) or not easily flammable material (do
not burn, mostly glow - e.g. drywall)
may be at a distance of 100 mm from the air curtain in all directions.
These
materials must
not cover the intake or exhaust vents.
For a safe distance of surfaces of building construction and objects made of flammable materials from the air cur-
tains with electric heating, it applies:
•
The safe distance of flammable materials in the direction of the main airflow (i.e. in front of the intake grille and
behind the exhaust slot) is
500 mm.
•
The safe distance of flammable materials above the air curtain is
500 mm.
•
The safe distance of flammable materials in all other directions is
100 mm.