AZT-9
28
ZPrAE Sp. z o.o.
6.1. Read from disturbance recorder
To check the list of recorded disturbances select RECORDER option in the main
program window. A window as shown in fig. 6.2 will be displayed. A table with the records
saved in the device is displayed in the main part of the window. Records are saved
following the circular buffer principle. Depending on the time set for a single recording the
buffer can store from 1 to 210 records in non-volatile memory. In the upper part of the
window there is a REFRESH button which queries the recorder and refreshes the record
table. In addition, it is possible to trigger the recording manually by RECORDER
TRIGGER. To download a record from the device, choose the record line in the table and
select the DOWNLOAD RECORD option by clicking the right mouse button.
Fig. 6.2. Record list window.
After the transmission, program asks where the record should be saved, by default
it is the default folder for a given device. The files are saved in COMTRADE format.
Record files *.cfg *.dat can be opened in iREC viewer supplied with ZPrAE-EDIT software.
After default installation the iREC software should run automatically once the record is
saved. It is possible to view the records saved on the PC drive, select the OPEN RECORD
FOLDER and run a given file.