background image

37

CAPACITY CONTROLLERS – CAPL-2

and field conditions. For example, in milder climates setting may be as low
as 110 to 115 degrees. In more severe climates up to 150 degrees.) As long
as there is a heating call (WIN energized), the following will occur.

HEAT STAGING ON:

• If the 

leaving air is 130 degrees or less

and heat one is off, heat

one will turn on within four minutes.  If heat one is on, heat two will
turn on within ten minutes.

HEAT STAGING OFF

:

• If 

the 

leaving air is between 145 and 150 degrees

and heat two

is running, heat two will turn off.  Heat one will turn off after 150
Degree setpoint is exceeded 

If the 

leaving air is 150 degrees or greater

then all heat stages

will turn off and the indoor blower fan is energized until heat one
turns back on or until the heat call is satisfied.

NO STAGING:

If the 

leaving air is greater than 130 and less than

or equal to 145 degrees, 

then no heat staging will occur.

HEATING CALL (Heat Pump)

(heat setpoint 118). As long as there

is a heating call (WIN energized), the following will occur:

HEAT STAGING ON:

• If the 

leaving air is 98 degrees or less

and heat one is off, heat

one will turn on within four minutes.  If heat one is on, heat two will
turn on within eight minutes.

HEAT STAGING OFF

:

• If 

the 

leaving air is between 113 and 118 degrees

and heat two

is on, heat two will shut off after running a minimum of four min-
utes.  Heat one will turn off after it has been on a minimum of four min-
utes and heat two has been off a minimum of six minutes. 

• If 

the 

leaving air is 118 degrees or greater

then all heat stages will

turn off after the last heat stage running has run for at least four min-
utes.

NO STAGING:

• If the 

leaving air is greater than 98 and less than or equal to

113

degrees, then no heat staging will occur.

The CAPL-2 consists of the following:

A. Digital Display

– Three digit LED.  Normally displays the leaving air

temperature of the HVAC unit. When the UP/DN buttons are pressed, the
cut-out setpoints are displayed. Refer to the Setpoint Calibration
section for reading and adjusting the setpoints.  

B. Microcontroller

– Activates and controls outputs based upon leaving

air temperature comparison with programmed setpoint. Occasionally soft-
ware upgrades may become available. If so, the CAPL-2 software can be
field upgraded by changing this microcontroller.

C. Thermometer Calibrator

– Calibrates the leaving air temperature

thermometer. Turn clockwise to lower temperature. Turn counterclock-
wise to raise. Refer to CALIBRATION section for complete calibration infor-
mation.

D. Economizer Selection Jumper:

ECON – Place here if you have an economizer.  
ECOFF – Place here if no economizer.

E. Leaving Air Sensor (LAS) Terminals

– Leaving air temperature

sensor is connected to the CAPL-2 here.  Red to + and white to –.  The
sensor monitors the leaving air of the HVAC system.  If preferred, the
CAPL-2 can be mounted up to 500 feet from the sensor.  See Installation
section for further information. 

F. HVAC/System Controller Interface Terminals

– Y IN – Cool call

input, Economizer output; Y1 – Compressor 1; Y2 – Compressor 2;
G – Indoor blower fan; W IN – Heat call input; W1 – Heat 1; W2 – Heat
2.  See Wiring section for detailed wiring instructions.

G. HVAC Power Terminals

– Connect to HVAC system 24V AC power

source.  R is 24 V hot.  C is 24 V rtn.  Cannot be connected to any other
power source.  CAPL-2 uses less than 2 VA of power.  See Wiring section
for detailed wiring instructions.

H. Status Lights

– 

ECONO

– On during cool call.  Indicates economiz-

er enabled; Y1 – On when first stage compressor energized; Y2 – On
when second stage compressor energized; Y3 – On when third
stage compressor energized; Y4 – On when fourth stage compressor
energized; FAN – On when indoor blower fan energized by System Con-
troller or CAPL-2 (G energized); W1 – On when first stage furnace
energized; W2 – On when second stage furnace energized; W3 – On
when third stage furnace energized; W4 – On when fourth stage furnace
energized.

I. Power Switch

– When off, the display is off, the CAPL-2 is disabled and

the relay contacts are closed. The HVAC unit can run at this time but will
not have staging control or capacity control protection. When the switch
is on, the display is on, and the CAPL-2 is operational.  

J. Board Number

– This number indicates the circuit board number and

revision. May need to know this number if conferring with technical
support.

K. Heat Pump/Gas Electric selection jumper

– Place at GE position

for gas/electric units.
Place at HP position for
heat pump units that use
gas/electric thermostats.

L. Setpoint Adjust-
ment

– Use the UP/DN

buttons to view and
change the cutout set-
points. Refer to the Set-
points, Calibration sec-
tion (Page 41) for read-
ing and adjusting the set-
point

s.  

F

G

Y IN Y1 Y2 GIN

R C

WIN W1 W2

W1 W2

Y1 Y2

F

A
N

E
C
O
N
O

UP

DN

ON

OFF

GOUT

HP

GE

ECON

ECOFF

B

D

I

J

K

L

H

A

C

E

+ -

990616B

R4

COMPONENTS

Содержание System 2000

Страница 1: ...Zonex Systems System 2000 2 20 Zone Auto Changeover System 1000 2 7 Zone Manual Changeover Design Installation for Part 101ASIM Rev September 2003...

Страница 2: ...Round Zone Dampers 18 19 Rectangular Zone Dampers 20 21 Sizing Zone Dampers 22 Wiring Zone Dampers 22 Damper Installation Notes 22 Paralleling Zone Dampers 23 Bypass Dampers 23 Barometric 23 24 Electr...

Страница 3: ...sed for the zones not calling for the operating mode When the HVAC Heat Pump unit is not running all Zone Dampers are open to provide ventilation if the indoor blower fan is running continuously While...

Страница 4: ...ONS AND UNDER OVER 5 TONS Low Pressure Dampers Medium Pressure Dampers Round 101ARZD size up to 5 SP Round 101AMPD size up to 1 75 SP Rectangular 101EC W x H up to 5 SP Rectangular 101MRTD W x H up to...

Страница 5: ...urn on the compressor and fan The air conditioner will continue to operate until all cooling calls are satisfied or the majority changes to heating HEAT CALLS If the majority of calls are for heat the...

Страница 6: ...s running in cool mode ON Indoor blower fan runs continuously H COOL and HEAT mode switches AUTO Accepts calls from thermostats OFF Ignores calls I Power switch When on applies 24V AC power to G of TB...

Страница 7: ...e information Operation The Controller operates the Heat Pump using signals from each zone thermostat in the system When heating or cooling calls are sent to the controller it treats these calls as vo...

Страница 8: ...tes After 8 minutes from Y1 if the supply air temperature is 60 or higher Y2 second stage of cooling will energize The Rev Valve LED will change from flashing to steady ON Cool B mode for Rev Valve LE...

Страница 9: ...zing 24V damper transformer Requires in line fuse See table on page 42 for sizing transformer and fuse C terminal for hardwired electronic thermostats only J1 Reversing Valve Selection Jumper Leave ju...

Страница 10: ...g with the Controller and able to start and stop the air conditioner NOTE Heat and Cool Led indicators will toggle every two min utes to check opposite mode callers regardless of heat and cool switch...

Страница 11: ...Bypass damper will independently bypass any supply air not needed back to the return duct System 1000 Zonex Systems Supplied Components Switching Centers Pages 11 14 Zone Thermostats Pages 16 17 Zone...

Страница 12: ...RLAT or Digital Version 101CAPGE CAPACITY CONTROLLERS DIGITAL CAPACITY CONTROLLER SYCAP Switching Center SYHPA 2 Stage Heat 1 Stage Cool GAS ELECTRIC ZONE THERMOSTATS ZONE THERMOSTATS HEAT PUMP 5 TONS...

Страница 13: ...G made to R and the indoor blower fan will run This allows ventilation in all zones 1 5 Wire Link Terminals Daisy chain wires to zone dampers YD Cool call input signal Current flows in this terminal w...

Страница 14: ...link wire sizing C terminal for hard wired electronic thermostats only Open motor not utilized on low pressure spring open dampers If using more than one damper per thermostat refer to Paralleling Zon...

Страница 15: ...h tells the dampers of all zones not calling to close and energizes E E made to R What E is wired to depends on the make of your heat pump Refer to the SYHPA wiring diagram for further information Not...

Страница 16: ...P TERMINALS E G R Y O B W2 L C SYCAP CAPACITY CONTROL PG 33 Y1 Y1 W2 W2 C R 3 4 5 7 B 2 6 1 CLOSE MOTOR OPEN MOTOR ZONE DAMPER If the heat pump does not energize the indoor blower fan when emergency h...

Страница 17: ...it has check for shorts on the WD and or YD wires on the five wire link and replace the 1 10 amp fuse Turn the POWER switch on the SYHPA and SYCAP OFF Check all thermostats to be sure that they are of...

Страница 18: ...tage heat When the the red light labeled HT2 is on the stat is calling for second stage heat This zone thermostat is designed for zones that require supplemental heat This thermostat can be ordered wi...

Страница 19: ...through an optional telephone controller Dimensions are 3 75 W x 5 H x 1 D Color White ZONE THERMOSTATS COMPATIBILITY The 101ASSB gas electric and 101AACBHP heat pump controllers are compatible with...

Страница 20: ...The motor is designed for contin uous full stall operation Special winding and heavy duty gearing provide for long motor life and easy spring open operation A cross pin on the motor shaft provides pos...

Страница 21: ...13 15 17 19 21 PART 101AMPD06 101AMPD08 101AMPD10 101AMPD12 101AMPD14 101AMPD16 101AMPD18 6 8 10 12 14 16 18 Nominal CFM Duct Diameter Duct Velocity FPM Damper P WC 10 12 14 16 6 8 7 9 410 660 1450 10...

Страница 22: ...ZONE DAMPERS 101MRTD W x H Zonex Systems rectangular medium pressure dampers are recommended for systems under 7 5 tons with a maximum differential static pressure of 1 These are power open power clos...

Страница 23: ...WIDTH A Rectangular dampers should operate at 1500 FPM E G A 24 x 12 damper 2 square feet 2 square feet X 1500FPM 3000 CFM 4 200 280 390 490 700 1090 1500 2000 2500 3000 3600 4000 630 960 1400 1850 22...

Страница 24: ...d along with the ductwork The hat sec tion on the damper is delivered with insulation between the hat sec tion and pipe Therefore insulation should be applied to the round pipe and be butted against t...

Страница 25: ...ers are used to provide constant air delivery through the air handling unit This is done by bypassing excess air from the supply duct back to the return duct As a zone is satisfied its zone damper clo...

Страница 26: ...inutes to equalize pressure Then make sure all dampers are open by checking for air flow out of each damper c By moving counter weight up or down the lever arm adjust it so that the damper just wants...

Страница 27: ...w the smallest zone air volume is 400 CFM and we have a four ton system Thus the air volume we need to bypass is 400 4 400 which equals 1200 CFM Using the ROUND BYPASS SELECTION TABLE we would select...

Страница 28: ...4667 16500 18333 20167 22000 48 12000 14000 16000 18000 20000 22000 24000 8 10 12 14 16 18 20 22 8 667 833 1000 1167 1333 1500 1667 1833 10 833 1042 1250 1458 1667 1875 2083 2292 12 1000 1250 1500 175...

Страница 29: ...ypass damper is Closed Bypass dampers using a square motor have a grey release lever on the bottom side of the damper near motor to manually open or close the damper c At 101ASPC Static Pressure Contr...

Страница 30: ...during capacity cut out This ensures the heat exchanger properly cools down and the AC coil warms up during capacity cut out It also provides better zone tem perature control by providing conditioned...

Страница 31: ...isplay during this time Enable Mode On the digital display E followed by the leaving air temperature indicates that the 101CAPGE is in the Enable Mode The purpose of this mode is to ensure the furnace...

Страница 32: ...ASSB Switching Center SYGE R G W Y 4 2 5 1 3 CAPACITY CONTROLLERS 101CAPGE G HVAC System Controller Interface Terminals Y1 controls the A C compressor and W1 controls the furnace W1 controls the first...

Страница 33: ...starts the heater and returns indoor blower fan control to the heater or Switching Center Controller Cut out disable The cool cutout is disabled in heat mode The heat cutout is disabled in cool mode T...

Страница 34: ...ir temperature drops below 47 degrees Fahrenheit and re energize when the temperature rises above 47 degrees This setpoint is non adjustable It has no control for preventing compressor short cycling I...

Страница 35: ...is disabled Every four minutes after Y1 is broken the leaving air temperature is checked If the temperature rises above the cool cut out setpoint Y1 Y1 is made red light DL1 turns off and the compress...

Страница 36: ...ts Calibration section Page 41 for reading and adjusting the setpoints K Board Number This number indicates the circuit board num ber and revision You may need to know this number if con ferring with...

Страница 37: ...nd test point Rotate the correspond ing potentiometer until the meter reads the proper voltage according to Table 2 below WIRING The 101ALAS is installed as detailed in the Capacity Controllers Instal...

Страница 38: ...s on it will run a minimum of four minutes This prevents short cycling and ensures sufficient compressor oil return When the heat call is removed all compressors are immediately turned off SEQUENCE OF...

Страница 39: ...controller C Thermometer Calibrator Calibrates the leaving air temperature thermometer Turn clockwise to lower temperature Turn counterclock wise to raise Refer to CALIBRATION section for complete cal...

Страница 40: ...mizer if available is enabled and outside air is supplied based on enthalpy COMPRESSOR STAGING ON If the leaving air is 58 or greater the next compressor will turn on within four minutes As long as th...

Страница 41: ...icates economizer enabled Y1 On when first stage compressor energized Y2 On when second stage compressor energized Y3 On when third stage compressor energized Y4 On when fourth stage compressor energi...

Страница 42: ...circuit board away from casing 3 Pull sensor out of casing 4 Reattach circuit board to casing with screws previously removed 6 Place sensor in hole made in duct and secure with tape wire tie or cable...

Страница 43: ...TPOINTS CALIBRATION FIVE WIRE LINK Zonex Systems s patented Five Wire Link is one of the most important ele ments of the System 1000 2000 zoning system Extra care should be made to ensure the wiring i...

Страница 44: ...ng Center System Controller The power rating of the transformer must be sufficient to power the number of dampers used Also a properly rated in line fuse must be used on the secondary of the transform...

Страница 45: ...Fan Mode AUTO ON is usually selected at the System Controller Switching Center If preferred the Fan Mode can be selected at one zone thermostat using this diagram The thermostat needs to have a fan s...

Страница 46: ...E ON HEATER W Y R LINE VOLTAGE 24 V STAT B W Y G R d W Y R C RO MC RC TB2 TB1 DAMPER RELAY BOARD W 2 W 2 B W Y G R d W Y R C RO MC RC TB2 TB1 DAMPER RELAY BOARD W 2 W 2 C C C Terminal used for electro...

Страница 47: ...00 turning Controller Power switch off will remove power from GD The Power switch will not remove power from GD on System 1000 2 BD B 24V return chassis ground Measure all Daisy Chain voltages in refe...

Страница 48: ...9 Factory 714 898 9963 Fax 714 898 6802 Visit our Web Site http www hvaccomfort com E mail us at calecon hvaccomfort com PATENTED PRODUCT Zonex Systems reserves the right to discontinue or change at a...

Отзывы: