background image

8

Make sure the correct size fuse is installed in-line with the transformer
powering the Controller.

For both Gas/Electric and Heat Pump Controllers

1. These system tests are to be done with all wiring to the air condi-

tioning unit disconnected.

A. Be sure that the power switch to the Controller is in the “OFF”

position. For 

Gas/Electric

remove “R,” “W1,” “Y1” and “G” wires

from Terminal Strip 2 labeled (TB2).  

B. Be sure that the power switch to the Controller is in the “OFF”

position. For 

Heat Pumps

remove “R,” “W,” “Y2,” “Y1,” “O/BL”

and “G” wires from Terminal Strip 2 labeled (TB2).  

2.

Check wiring of the 5 wire link to the dampers.  All connections
must be made color to color.

3.

If you are not using Zonex Systems supplied zone thermostats,
check each one to make sure it is an auto changeover type stat.
Turn all thermostats to the OFF position.  Check the Controller
“HEAT” and “COOL” switches to be sure that both are in the “OFF”
position.  The “FAN” switch should be in the “AUTO” position. Observe
the fuse on the Controller Board and transformer.  Turn the power
switch to “ON.”  If the fuse blows, there is a wiring problem.  If the
fuse does not blow, turn the “HEAT” switch to “AUTO” and “COOL”
switch to “AUTO.”  If the fuse blows at any of these steps, find and
repair the short in the wiring.

4.

If the system is operating normally, the Heat light should be on for
the 101ASSB, and 101AACB-HP.  Set the “HEAT” switch to “OFF”.
Check the first zone by turning it on and setting it to call for cool-
ing. If the call is received by the Controller, the “Damper” and
“Cool” lights will turn on.  If the lights come on, turn off the first
stat and the “Damper” light should turn off.  Test each stat this way
to be sure that each one is capable of communicating with the
Controller, and able to start and stop the air conditioner.

NOTE:

“Heat” and “Cool” Led indicators will toggle every two min-

utes to check opposite mode callers, regardless of heat and cool
switch positions.

5.

After cooling calls are tested, turn the cooling switch to “OFF” and
set the heating switch to “AUTO”.  Set the first zone to call for heat.
If the call is received by the Controller, “Damper” and “Heat” lights
will turn on.  Test each thermostat to be sure that each properly
communicates with the Controller for the heating sequence.

6.

After all zones have been checked, turn the ON/OFF switch at the
System Controller to OFF.

7.

Before wiring the System Controller to your A/C unit or furnace,
check the relays with a volt meter (set on 200 Ohms).  Be cer-
tain no continuity exists on the A/C unit terminal connections at the
System Controller.  Check between each terminal to the “R” termi-
nal. There should be no continuity between the terminals.  (If you
do show continuity, your System Control board should be replaced.)

8.

If no continuity exists from the test detailed above, connect the
terminal to the A/C unit and the System Controller.  Be certain all
thermostats are now in the “OFF” position.

9.

Turn the power switch to “ON” and the “HEAT” and “COOL”  switch-
es should be set to “AUTO”.  Initiate a call for cooling from only one
stat.  After a time delay, both compressor and fan should be running.
Turn off the cooling and initiate a heating call, (you may experience
up to a 4 minute time delay).  The heat should come on and after a
short time delay the fan will be operated by the internal controls of
the unit.  On the Heat Pump controller, eight minutes on the ini-
tial start of CAPL-2 after stage one starts, the LAS or capacity con-
trol will control second stage operation.

10. After completing the system check and startup procedure, set the

system up for normal operation.

SYSTEM 2000 SYSTEM STARTUP

Содержание System 2000

Страница 1: ...Zonex Systems System 2000 2 20 Zone Auto Changeover System 1000 2 7 Zone Manual Changeover Design Installation for Part 101ASIM Rev September 2003...

Страница 2: ...Round Zone Dampers 18 19 Rectangular Zone Dampers 20 21 Sizing Zone Dampers 22 Wiring Zone Dampers 22 Damper Installation Notes 22 Paralleling Zone Dampers 23 Bypass Dampers 23 Barometric 23 24 Electr...

Страница 3: ...sed for the zones not calling for the operating mode When the HVAC Heat Pump unit is not running all Zone Dampers are open to provide ventilation if the indoor blower fan is running continuously While...

Страница 4: ...ONS AND UNDER OVER 5 TONS Low Pressure Dampers Medium Pressure Dampers Round 101ARZD size up to 5 SP Round 101AMPD size up to 1 75 SP Rectangular 101EC W x H up to 5 SP Rectangular 101MRTD W x H up to...

Страница 5: ...urn on the compressor and fan The air conditioner will continue to operate until all cooling calls are satisfied or the majority changes to heating HEAT CALLS If the majority of calls are for heat the...

Страница 6: ...s running in cool mode ON Indoor blower fan runs continuously H COOL and HEAT mode switches AUTO Accepts calls from thermostats OFF Ignores calls I Power switch When on applies 24V AC power to G of TB...

Страница 7: ...e information Operation The Controller operates the Heat Pump using signals from each zone thermostat in the system When heating or cooling calls are sent to the controller it treats these calls as vo...

Страница 8: ...tes After 8 minutes from Y1 if the supply air temperature is 60 or higher Y2 second stage of cooling will energize The Rev Valve LED will change from flashing to steady ON Cool B mode for Rev Valve LE...

Страница 9: ...zing 24V damper transformer Requires in line fuse See table on page 42 for sizing transformer and fuse C terminal for hardwired electronic thermostats only J1 Reversing Valve Selection Jumper Leave ju...

Страница 10: ...g with the Controller and able to start and stop the air conditioner NOTE Heat and Cool Led indicators will toggle every two min utes to check opposite mode callers regardless of heat and cool switch...

Страница 11: ...Bypass damper will independently bypass any supply air not needed back to the return duct System 1000 Zonex Systems Supplied Components Switching Centers Pages 11 14 Zone Thermostats Pages 16 17 Zone...

Страница 12: ...RLAT or Digital Version 101CAPGE CAPACITY CONTROLLERS DIGITAL CAPACITY CONTROLLER SYCAP Switching Center SYHPA 2 Stage Heat 1 Stage Cool GAS ELECTRIC ZONE THERMOSTATS ZONE THERMOSTATS HEAT PUMP 5 TONS...

Страница 13: ...G made to R and the indoor blower fan will run This allows ventilation in all zones 1 5 Wire Link Terminals Daisy chain wires to zone dampers YD Cool call input signal Current flows in this terminal w...

Страница 14: ...link wire sizing C terminal for hard wired electronic thermostats only Open motor not utilized on low pressure spring open dampers If using more than one damper per thermostat refer to Paralleling Zon...

Страница 15: ...h tells the dampers of all zones not calling to close and energizes E E made to R What E is wired to depends on the make of your heat pump Refer to the SYHPA wiring diagram for further information Not...

Страница 16: ...P TERMINALS E G R Y O B W2 L C SYCAP CAPACITY CONTROL PG 33 Y1 Y1 W2 W2 C R 3 4 5 7 B 2 6 1 CLOSE MOTOR OPEN MOTOR ZONE DAMPER If the heat pump does not energize the indoor blower fan when emergency h...

Страница 17: ...it has check for shorts on the WD and or YD wires on the five wire link and replace the 1 10 amp fuse Turn the POWER switch on the SYHPA and SYCAP OFF Check all thermostats to be sure that they are of...

Страница 18: ...tage heat When the the red light labeled HT2 is on the stat is calling for second stage heat This zone thermostat is designed for zones that require supplemental heat This thermostat can be ordered wi...

Страница 19: ...through an optional telephone controller Dimensions are 3 75 W x 5 H x 1 D Color White ZONE THERMOSTATS COMPATIBILITY The 101ASSB gas electric and 101AACBHP heat pump controllers are compatible with...

Страница 20: ...The motor is designed for contin uous full stall operation Special winding and heavy duty gearing provide for long motor life and easy spring open operation A cross pin on the motor shaft provides pos...

Страница 21: ...13 15 17 19 21 PART 101AMPD06 101AMPD08 101AMPD10 101AMPD12 101AMPD14 101AMPD16 101AMPD18 6 8 10 12 14 16 18 Nominal CFM Duct Diameter Duct Velocity FPM Damper P WC 10 12 14 16 6 8 7 9 410 660 1450 10...

Страница 22: ...ZONE DAMPERS 101MRTD W x H Zonex Systems rectangular medium pressure dampers are recommended for systems under 7 5 tons with a maximum differential static pressure of 1 These are power open power clos...

Страница 23: ...WIDTH A Rectangular dampers should operate at 1500 FPM E G A 24 x 12 damper 2 square feet 2 square feet X 1500FPM 3000 CFM 4 200 280 390 490 700 1090 1500 2000 2500 3000 3600 4000 630 960 1400 1850 22...

Страница 24: ...d along with the ductwork The hat sec tion on the damper is delivered with insulation between the hat sec tion and pipe Therefore insulation should be applied to the round pipe and be butted against t...

Страница 25: ...ers are used to provide constant air delivery through the air handling unit This is done by bypassing excess air from the supply duct back to the return duct As a zone is satisfied its zone damper clo...

Страница 26: ...inutes to equalize pressure Then make sure all dampers are open by checking for air flow out of each damper c By moving counter weight up or down the lever arm adjust it so that the damper just wants...

Страница 27: ...w the smallest zone air volume is 400 CFM and we have a four ton system Thus the air volume we need to bypass is 400 4 400 which equals 1200 CFM Using the ROUND BYPASS SELECTION TABLE we would select...

Страница 28: ...4667 16500 18333 20167 22000 48 12000 14000 16000 18000 20000 22000 24000 8 10 12 14 16 18 20 22 8 667 833 1000 1167 1333 1500 1667 1833 10 833 1042 1250 1458 1667 1875 2083 2292 12 1000 1250 1500 175...

Страница 29: ...ypass damper is Closed Bypass dampers using a square motor have a grey release lever on the bottom side of the damper near motor to manually open or close the damper c At 101ASPC Static Pressure Contr...

Страница 30: ...during capacity cut out This ensures the heat exchanger properly cools down and the AC coil warms up during capacity cut out It also provides better zone tem perature control by providing conditioned...

Страница 31: ...isplay during this time Enable Mode On the digital display E followed by the leaving air temperature indicates that the 101CAPGE is in the Enable Mode The purpose of this mode is to ensure the furnace...

Страница 32: ...ASSB Switching Center SYGE R G W Y 4 2 5 1 3 CAPACITY CONTROLLERS 101CAPGE G HVAC System Controller Interface Terminals Y1 controls the A C compressor and W1 controls the furnace W1 controls the first...

Страница 33: ...starts the heater and returns indoor blower fan control to the heater or Switching Center Controller Cut out disable The cool cutout is disabled in heat mode The heat cutout is disabled in cool mode T...

Страница 34: ...ir temperature drops below 47 degrees Fahrenheit and re energize when the temperature rises above 47 degrees This setpoint is non adjustable It has no control for preventing compressor short cycling I...

Страница 35: ...is disabled Every four minutes after Y1 is broken the leaving air temperature is checked If the temperature rises above the cool cut out setpoint Y1 Y1 is made red light DL1 turns off and the compress...

Страница 36: ...ts Calibration section Page 41 for reading and adjusting the setpoints K Board Number This number indicates the circuit board num ber and revision You may need to know this number if con ferring with...

Страница 37: ...nd test point Rotate the correspond ing potentiometer until the meter reads the proper voltage according to Table 2 below WIRING The 101ALAS is installed as detailed in the Capacity Controllers Instal...

Страница 38: ...s on it will run a minimum of four minutes This prevents short cycling and ensures sufficient compressor oil return When the heat call is removed all compressors are immediately turned off SEQUENCE OF...

Страница 39: ...controller C Thermometer Calibrator Calibrates the leaving air temperature thermometer Turn clockwise to lower temperature Turn counterclock wise to raise Refer to CALIBRATION section for complete cal...

Страница 40: ...mizer if available is enabled and outside air is supplied based on enthalpy COMPRESSOR STAGING ON If the leaving air is 58 or greater the next compressor will turn on within four minutes As long as th...

Страница 41: ...icates economizer enabled Y1 On when first stage compressor energized Y2 On when second stage compressor energized Y3 On when third stage compressor energized Y4 On when fourth stage compressor energi...

Страница 42: ...circuit board away from casing 3 Pull sensor out of casing 4 Reattach circuit board to casing with screws previously removed 6 Place sensor in hole made in duct and secure with tape wire tie or cable...

Страница 43: ...TPOINTS CALIBRATION FIVE WIRE LINK Zonex Systems s patented Five Wire Link is one of the most important ele ments of the System 1000 2000 zoning system Extra care should be made to ensure the wiring i...

Страница 44: ...ng Center System Controller The power rating of the transformer must be sufficient to power the number of dampers used Also a properly rated in line fuse must be used on the secondary of the transform...

Страница 45: ...Fan Mode AUTO ON is usually selected at the System Controller Switching Center If preferred the Fan Mode can be selected at one zone thermostat using this diagram The thermostat needs to have a fan s...

Страница 46: ...E ON HEATER W Y R LINE VOLTAGE 24 V STAT B W Y G R d W Y R C RO MC RC TB2 TB1 DAMPER RELAY BOARD W 2 W 2 B W Y G R d W Y R C RO MC RC TB2 TB1 DAMPER RELAY BOARD W 2 W 2 C C C Terminal used for electro...

Страница 47: ...00 turning Controller Power switch off will remove power from GD The Power switch will not remove power from GD on System 1000 2 BD B 24V return chassis ground Measure all Daisy Chain voltages in refe...

Страница 48: ...9 Factory 714 898 9963 Fax 714 898 6802 Visit our Web Site http www hvaccomfort com E mail us at calecon hvaccomfort com PATENTED PRODUCT Zonex Systems reserves the right to discontinue or change at a...

Отзывы: