ZSI-320 User Manual
Issue 03
Page 12 of 20
ZVM Port
MAC address
The address to which this unit will respond to polls from another control unit.
Default = 8
Terminated
The state of the 120R line terminator
Ticked
= Un-terminated
Un-ticked
= terminated.
Default = Un-terminated
Polled
To indicate that the unit should expect to be polled. If
On
the unit will wait for a poll before transmitting any
information on this port.
Default =
On
Controller
Z
S
I
-
3
2
0
To indicate that the unit is to make the decision on telemetry control from operators. If set to
Off
the unit will
forward control request messages to the device on the ZVM port.
Default =
Off
Telephone
The telephone numbers for up to 50 sites (20 on earlier versions of ZSI-320) can be configured.
MEYERTECH LIMITED