*MINIMUM DISTANCE 50 mm (2") BETWEEN PUMPS

EXTRA PROTECTION SYSTEMS

  TWO-PUMP SYSTEM

  The extra protection two-pump system is an economical solution to the costly duplex 

alternating pump system and it's easy to install.

  The extra protection two-pump systems consists of:

  a. 
  b.  one alarm system
  c.  two unicheck valves as required

  ADVANTAGES

  1)  The two pump system offers high pump performance without the high price.  It is 

economical and easy to install.

  2)  Delivers more dependability than a single pump system and greatly reduces the risk of 

costly and time-consuming problems.

  3)  Affords greater satisfaction and peace of mind to all concerned by providing state of the 

art protection for costly and expensive surroundings.

  4)  Ability to change lead and lag positions by changing pump plug connection.

PUMP 1 ON

PUMP 1 OFF

PUMP 2 ON

PUMP 2 OFF

ALARM ON

 VARIABLE LEVEL FLOAT SWITCH

(ALARM)

PUMP 1

PUMP 2

ALARM

P/N 10-1494 ILLUSTRATED

PEA GRAVEL

SK878

 FOR YOUR PROTECTION, ALWAYS DISCONNECT PUMP FROM ITS POWER SOURCE BEFORE HANDLING

.  For single 

phase pumps supplied with a grounded plug, 

DO NOT, UNDER ANY CIRCUMSTANCES, REMOVE THE GROUND PIN.

  The plug 

must 

 be inserted 

into a mating grounded receptacle. 

If

 the installation does not have such a receptacle, it must be changed to the proper type, wired and grounded 

in accordance with all applicable local codes and ordinances.  
All three phase pumps require motor starting devices with motor overload protection.  Three phase pumps

 must

 be installed in accordance with all applicable 

local codes and ordinances. Pumps are not to be installed in lo

  Risk of electrical shock.  

Do not remove power supply cord and strain relief or connect conduit directly to the pump.

PUMP WIRING INSTRUCTIONS

Single Phase Installation

To operate a non-automatic pump automatically, a control panel or 20 amp 

control switch (P/N 10-0748) must be added to the power circuit. Follow 

Three Phase Installation

Three phase pumps are nonautomatic. To operate automatically, a control panel 

is required. Follow the instructions provided with the panel to wire the system.

Before installing a pump, check the pump rotation to insure that wiring has been 

connected properly to power source, and that the green lead of power cord, is 

connected to a valid ground, momentarily energize the pump, observing the 

directions of kick back due to starting torque. Rotation is correct if kick back 

is in the opposite direction of rotation arrow on the pump casing. If rotation 

is not correct, switching of any two power leads other than ground, should 

provide the proper rotation.

For automatic three phase pumps see automatic 3 phase wiring diagram 

located to the far right. 

NONAUTOMATIC

3 PHASE

AUTOMATIC

3 PHASE

MOTOR

(3)

BLUE

RED

BLACK

GREEN

L1

L2

(1)

(2)

YELLOW

L3

WHITE

RED

013071

006848

- 18 - 

© Copyright 2019 Zoeller Co. All rights reserved.

Содержание 910

Страница 1: ...maged it must be replaced by an authorized Zoeller Representative 9 Pump may contain oil which becomes pressurized and hot when operating Allow 2 1 2 hours after disconnecting before attempting servic...

Страница 2: ...onsult the factory Do not attempt to service or otherwise disassemble pump Service must be performed by an authorized Zoeller Company representative SERVICE CHECKLIST EASY DO S DON T S FOR INSTALLING...

Страница 3: ...ions with warranty after installation This product must be installed in accordance with National Electric Code ANSI NFPA 70 so as to prevent moisture from entering or accumulating within boxes conduit...

Страница 4: ...N COVER AND CLEANED PERIODICALLY High Head unit see 3 under Caution on front page Water stream will be visible from this hole during pump run periods mechanism s Use full size discharge pipe Basin mus...

Страница 5: ...nnection Check valve Ball valve Inlet hub 2 Pipe 2 Pipe Union 600 mm 23 19 32 Length 90 mm 3 1 2 Coupling Length 200 mm 7 7 8 For reference only 2 BSPT slip 2 NPT slip or 2 Pipe 2 BSPT slip 2 NPT slip...

Страница 6: ...pe seal Vent adaptor Discharge pipe seal Cord seal For alarm 2 Union Check valve 2 turn DN50 Length 90 mm 3 1 2 Length 762 mm 30 DN100 2 NPT slip x 2 or 1 1 4 NPT slip x 1 Inlet hub Discharge pipe sea...

Страница 7: ...ailure to follow these precautions could result in serious injury or death Replace product immediately if switch cable becomes damaged or severed Keep these instructions with warranty after installati...

Страница 8: ...ge as shown in Figure A Pumping range can be adjusted by moving the float stop up or down the rod 2 Insert hose clamp through slots in mounting bracket as shown in Figure B 3 Position hose clamp aroun...

Страница 9: ...OTE THE HOLE MUST ALSO BE BELOW THE BASIN COVER AND CLEANED PERIODICALLY High Head unit see 3 under Caution on front page Water stream will be visible from this hole during pump run periods mechanism...

Страница 10: ...ights reserved Union Pipe DN50pipe DN50 550 mm 21 21 32 STEP 3 Check valve Ball valve 1 1 2 BSPT x 1 1 2 slip 1 1 2 Pipe 1 1 2 Pipe Union Pipe DN40 1 1 2 Pipe 13 8 2 11 9 EA0054 Vent adaptor TYPICAL D...

Страница 11: ...seal Discharge pipe seal With thread Cord seal 2 orDN50 Union Check valve Grinder only Grinder only Grinder only 2 turn DN50 Length 90 mm 3 1 2 Length 762 mm 30 DN100 Inlet hub 2 BSPT x 2 slip or 2 N...

Страница 12: ...drill the 5 mm hole Location to fix the float 4 Basin 460x760 mm 1 2 3 4 5 Electrical wiring and protection must be in accordance with governing electrical code and any other applicable local electri...

Страница 13: ...EA0055 Basin 460x760 mm 1 2 3 4 5 Electrical wiring and protection must be in accordance with governing electrical code and any other applicable local electrical requirements Install proper Zoeller un...

Страница 14: ...valve Ball valve Coupling 2 Pipe Union 13 8 2 11 9 Pump diagram for reference only EA0055 TYPICAL DEWATERING INSTALLATION Turn Top logo upward DN100Pipe RECOMMENDED INSTALLATION FOR ALL APPLICATIONS...

Страница 15: ...into track if caught on outer edge B To insert your 4 ABS or PVC pipe Step 1 Cut pipe square Step 2 Chamfer end Failure to do so can cut built in O rings off The O rings in the Snap in hub make the s...

Страница 16: ...0 mm DIMENSIONAL DATA A D SK2903 C B SK2694 A D C B 673 mm A B C Size Dimensions 24 x 24 26 1 2 651 mm 25 5 8 203 mm 8 711 mm 28 520 mm 20 1 2 560 mm 22 1 16 241 mm 9 1 2 406 mm 16 552 mm 21 3 4 762 m...

Страница 17: ...E BELOW THE BASIN COVER AND CLEANED PERIODICALLY High Head unit see 4 under Caution on front page Water stream will be visible from this hole when pump is operating 5 mechanism s 6 Use full size disch...

Страница 18: ...in accordance with all applicable local codes and ordinances All three phase pumps require motor starting devices with motor overload protection Three phase pumps must be installed in accordance with...

Страница 19: ...RATION OF CONFORMITY We Zoeller declare under our sole responsibility that the models 49 53 55 57 59 72 76 86 88 98 137 139 140 4140 145 4145 152 153 161 162 163 165 185 189 222 264 266 267 268 270 42...

Страница 20: ...3 161 162 163 165 185 189 371 372 373 222 264 266 267 268 270 4270 271 4271 282 292 293 294 4290 4291 422 807 2702 2722 1 2 3 20 2019 Zoeller 1 8 5 7 130 54 104 2 3 4 6 5 2 11 8 7 10 5 mm 6 9 1 2 3 4...

Страница 21: ...1 4 2 3 5 6 8 9 7 10 11 4 12 13 3 14 21 1 5 5 1 2 3 4 A D Zoeller F G E B C 2019 Zoeller...

Страница 22: ...610x610mm 2 1 1 4 2 1 1 4 1 1 4 2 2 or DN50 2 x16 2 or DN50 BSPT NPT BSPT 2 DN50 90 mm 170 mm 200 mm 375 mm x2 22 2019 Zoeller 1 1 3 1 90 mm 90 mm 2 1 EA0053...

Страница 23: ...5 6 14 4 7 9 260 mm 3 13 12 23 2019 Zoeller 5 mm 45 180 2 375 mm 1 2 3 4 6 7 8 9 10 11 12 13 14 5 1 2 EA0053 EA0053 5mm 4 610x610mm...

Страница 24: ...24 2019 Zoeller 3 EA0053 610x610 mm 2 2 2 1 1 4 1 1 4 2 1 1 4 BSPT NPT BSPT NPT BSPT NPT 2 600 mm 90 mm 200 mm or DN50 DN50 DN100...

Страница 25: ...m 1 1 2 2 orDN50 2 NPT or BSPT x4 2 orDN50 2 90 mm 762 mm x3 DN100 EA0054 1 1 2 BSPT x4 1 1 2 1 1 2 1 1 2 90mm 762 mm x3 DN100 2 DN50 2 DN50 2 DN50 2 2 1 1 4 NPT x4 2 2 90 mm 762 mm x3 DN100 2 DN50 1...

Страница 26: ...26 EA0095 U S Patent No 5 155 311 Canadian Patent No 2 060 748 20 170 mm 52 C 125 F 2019 Zoeller...

Страница 27: ...27 A C B 1 2 3 4 1 5 A 1 2 3 1 5 230 230 90 mm 260 mm 320 mm 2019 Zoeller A 1 2 3 4 5 B A...

Страница 28: ...460x560 mm 5 6 14 4 7 9 90 mm 260 mm 320 mm 13 3 12 12 12 28 2019 Zoeller 1 2 EA0054 EA0054 5 mm 4 5 mm 45 1 2 3 4 5 180 6 7 8 9 10 11 12 13 14...

Страница 29: ...13 460x560 mm 29 2019 Zoeller 3 EA0054 DN100 DN50 2 2 DN50 DN50 DN50 1 1 2 1 1 2 1 1 2 550 mm Top 2 8 2 11 9 or 2 1 1 4 1 1 4 2 1 1 4...

Страница 30: ...30 2019 Zoeller 460x760 mm 2 2 or DN50 2 x8 x6 2 or DN50 x3 NPT NPTorBSPT 90 mm 762 mm DN100 EA0055 1 1 4 2 1 1 4 170 mm 2 1 1 4 NPT 2 DN50...

Страница 31: ...31 2019 Zoeller 460x760 mm 2 5 6 4 7 9 1 2 EA0055 EA0055 5 mm 4 5 mm 45 1 2 3 4 5 180 6 7 8 9 10 11 12 13 14...

Страница 32: ...32 2019 Zoeller 3 13 3 12 12 12 EA0055 460x760 mm 5 mm 45 1 2 3 4 5 180 6 7 8 9 10 11 12 13 14...

Страница 33: ...460x760 mm 33 2019 Zoeller 4 2 2 13 8 2 11 9 550 mm EA0055 Top DN100 DN50 2 2 1 1 4 1 1 4 2 1 1 4 DN50 DN50...

Страница 34: ...4 DWV ABS Sch40 4 PVC Sch40 4 1 2 20 120 TOP A B 4 ABS PVC O Ring O Ring 4 1 2019 Zoeller 34...

Страница 35: ...35 2019 Zoeller SK2694 A D C B 673 203 711 520 560 241 651 A B C D 460 x 560 552 762 267 406 419 460 x 760 610 x 610 460x560 mm 460x760 mm A D SK2903 C B 610x610 mm mm...

Страница 36: ...2019 Zoeller 10 30 0164 50 mm 1 1 2 30 0152 63 mm 2 30 0160 90 mm 3 5 mm 4 180 10 2421 FM1597 FM0531 FM0732 FM1420 457mmX610 mm 100 mm 100 mm AC U F 3 3 3 3 1 2 3 13 8 7 11 5 4 12 12 9 10 6 1 2 3 7 9...

Страница 37: ...SK1217 SK1218 37 2019 Zoeller FM0526 PVC 10 1457 3 3 L1 L2 1 2 L3 013071 006848 20 P N 10 0748...

Страница 38: ...V WU 220 V 1 Ph 50 Hz 5 10 15 20 22 9 13 5 18 22 24 1 2 L1 L2 3 011835 20 WU SK305 38 2019 Zoeller V WU 1 25 5 22 WU a b c 1 2 3 4 EA0047 2 2 2 1 1 1 P N 10 1494 50 mm...

Отзывы: