7. Cabinet Reinforcement

9. Communication Connection Requirement 

8. Electrical Connection Requirement

As shown in the figure

As shown in the figure

As shown in the figure

· After the cabinet is located onto the anchor bolts, it shall be locked tight by using M12 nuts, spring washers and flat 
washers 

· The power cable, preferably YJV-3×50+2×25, shall enter the cabinet from the bottom

· 50mm

2

 cable is used for A/B/C; 25mm

2

 cable is used for N/PE; 

  the crimped terminal width shall be ≤22mm

· It is connected to the input terminal A/B/C/N of the PCS; 

  the wiring screw tightening torque is 18-22N.M 

· PE connects to the grounding copper strip; the wiring screw tightening torque is 8-10 N.M 

· For external communication of EMU, it is recommended to use Ultra Cat6 cable; the cable enters the cabinet from the 
bottom 
· After the cable runs through the transfer connector, the RJ45 is crimped. The overall installation is shown below

AC220V UPS power cable,  preferably 22AWG cables × 2, connected to the L/N of the outlet terminal 

8

9

10. Other Requirements

· Put back the forklift cover

· Turn tight the waterproof joint of the power cable, and fill packing material to an extent as necessary 

· Turn tight the waterproof joint of the communication cable, and fill packing material to an extent as necessary