H0548600.B - EN - 2016-05
5
1.3 I Electricity supply connecti ons
• Incorrectly ti ghtened terminals may cause the terminal unit to heat up and invalidate the
warranty.
• Before any work inside the device, you must cut the electricity supply as there is a risk of
electric shock which may cause material damage, serious injury or even death.
• Only a qualifi ed and experienced technician is authorised to carry out cabling in the equipment
or to replace the supply cable.
• The installer must consult the electricity provided if necessary and ensure that the equipment
is connected correctly to an electricity network with impedance under 0.095 ohm.
•
The heat pump's electrical supply must be provided through a protecti on and circuit breaking device (not supplied)
complying with the standards and regulati ons in force in the country where it is installed,
•
The device is provided for connecti on to a general power supply with a TT and TN.S neutral regime.
•
Electrical protecti on: by circuit breaker (D curve) (for calibre, see § “5.2 I Technical specifi cati ons”), with a 30 mA
dedicated diff erenti al circuit breaker (circuit breaker or switch).
•
Additi onal protecti on may be required during installati on to guarantee the II overvoltage category.
•
The electricity supply must correspond to the voltage indicated on the device's informati on plate.
•
The electricity supply cable must be insulated against any cutti ng or hot elements that may damage or crush it.
•
The equipment must be connected to an earth socket.
•
The electrical connecti on lines must be fi xed.
•
Use the gland to pass the supply cable into the device.
•
Used the supply cable (RO2V type) adapted for outdoor or buried use (or run the cable into a protecti on duct) with
an external diameter of between 9 and 18mm.
•
We recommend burying the cable at a depth of 50 cl (85 cm under a road or path) in an electrical duct (red ribbed).
•
If this buried cable meets another cable or pipe (gas, water, etc.), there must be more than 20 cm between them.
•
Connect the supply cable to the connecti on terminal unit inside the device.
L: live
N: neutral
: earth
L1-L2-L3: live
N: neutral
: earth
Single phase terminal unit
Three-phase terminal unit