H0548600.B - EN - 2016-05
11
❸ Maintenance
3.1 I Wintering
• Wintering is vital to prevent the condenser breaking due to freezing. This is not covered by
the warranty.
• To avoid damaging the equipment with condensati on, do not fully cover it; a wintering cover
is provided.
•
Set the regulator to "standby" mode by pressing and holding for 3 seconds and disconnect the power supply,
•
Open valve B,
•
Close valves A and C and open valves D and E (if present),
•
Make sure that there is no water circulati ng in the heat pump,
•
Drain the water from the condenser (risk of freezing) by unscrewing the two water input and output connectors on
the back of the heat pump,
•
In the case of full wintering for the pool (complete shutdown of the fi ltrati on system, bleed the fi ltrati on circuit or
even pool drainage): ti ghten the two connectors by one turn to prevent any foreign bodies from getti ng into the
condenser,
•
In the case of wintering for the heat pump only (shutdown of the heati ng only, the fi ltrati on keeps running): to not
ti ghten the connectors but add 2 caps (provided) on the condenser's water inputs and outputs.
•
We recommend that you put the aired wintering micro cover (provided) on the heat pump.
3.2 I Maintenance
• It is recommended that the device be general serviced at least on a yearly basis to ensure
proper operati on, maintain performance levels and prevent some potenti al failures. These
operati ons are carried out at the user's expense, by a technician.
3.2.1 User maintenance
•
Make sure that the fi lter is not blocked by any foreign bodies.
•
Clean the evaporator (for locati on see § “5.3 I Dimensions and marking”) using a soft brush and a fresh water spray
(disconnect the power cable); do not fold over the metal wings, then clean the condensati on drainage pipe to remove
any impuriti es that may be blocking it.
• Do not use a high pressure jet. Do not spray with rain water, salt water or water which is full of minerals.
•
Clean the outside of the device; do not use any solvent-based products. We can provide you with a specifi c cleaning
kit as an opti on: the PAC NET, see § “5.1 I Descripti on”.
3.2.2 Maintenance to be carried out by a qualifi ed technician
•
Check that the regulati on is operati ng correctly connected.
•
Check that the condensati on fl ows correctly when the device is operati ng.
•
Check the safety mechanisms.
•
Check the connecti on of the metal masses to the earth.
•
Check that the electrical cables are correctly ti ghtened and connected and that the electrical unit is clean.