8

 -

use  dry  nitrogen  or  the  mixture  of  nitrogen  and  refrigerant  indicated  on  the 

information plate, 

 -

the test pressure for both the high and low pressure circuits must not exceed 42 

bar in cases where the appliance is equipped with the optional pressure gauge.

• 

The high pressure circuit pipes are made of copper and have a diameter equal to or 

greater than 1’’5/8. A certificate as indicated in §2.1 in compliance with standard 

NF EN 10204 must be requested from the supplier and filed in the installation’s 

technical file.

• 

Technical data relative to the safety requirements of the various applicable directives 

are indicated on the information plate. All this information must be recorded in 

the appliance’s installation manual, which must be kept in its technical file: model, 

code,  serial  number,  maximum  and  minimum  OT,  OP,  year  of  manufacture,  CE 

marking,  manufacturer’s  address,  refrigerant  and  weight,  electrical  parameters, 

thermo-dynamic and acoustic performance.

LABELLING

• 

The equipment must be labelled so as to specify that it is out of order and that the 

refrigerant has been drained.

• The label must be dated and signed.

• 

For appliances containing a flammable refrigerant, check that labels are placed on 

the equipment stating that it contains a flammable refrigerant.

RECOVERY

• 

When draining the refrigerant for maintenance or decommissioning, best practices 

should be followed in order to safely drain all of the refrigerant.

• 

When  transferring  refrigerant  to  a  cylinder,  make  sure  that  you  use  a  recovery 

cylinder that is compatible with the refrigerant. Make sure that the correct number 

of cylinders are provided for recovering all of the refrigerant. All cylinders used must 

be intended for the recovery of refrigerant and must be labelled for this specific 

refrigerant. The cylinders must be equipped with a vacuum valve and a stop gate 

in good working order. Empty collection cylinders are drained and, where possible, 

cooled before recovery.

• 

The recovery equipment must be in good working order, the instructions for using 

the equipment must be within reach and the equipment must be compatible for 

use  with  the  refrigerant  concerned,  including,  where  appropriate,  a  flammable 

refrigerant.  Moreover,  a  set  of  calibrated  scales  must  be  available  and  in  good 

working order. The pipework must be complete, have no leaks or disconnected 

connectors, and must be in good condition. Before using the recovery unit, check 

that  it  is  in  good  working  order,  that  it  has  been  well  maintained  and  that  the 

associated electric components are sealed so as to prevent any risk of fire in the event 

of refrigerant being released. If you have any doubts, contact the manufacturer.

• 

The recovered refrigerant must be sent to the refrigerant supplier in its recovery 

cylinder with a waste transfer note. Do not mix different refrigerants in the recovery 

units, and in particular in the cylinders.

• 

If the compressor has been removed or if oil from the compressor has been drained, 

check that the refrigerant has been completely removed to prevent it from mixing 

with the lubricant. The draining process must be carried out before returning the 

compressor to the supplier. Only the electric heater of the compressor body can 

Содержание PX50 MD12

Страница 1: ...H0686900_REVB 2020 03 More documents on www zodiac com PX50 Instructions for installation and use English Heat pump Translation of the original instructions in French EN...

Страница 2: ......

Страница 3: ...sory or mental capabilities unless they receive supervision and are instructed on how to use the appliance by a person responsible for their safety and if they understand the hazards involved Children...

Страница 4: ...national regulations on category III overvoltage and which disconnects all poles of the power supply circuit must be installed on the power supply circuit to the appliance This disconnection method i...

Страница 5: ...egulations in terms of the environment and installation in particular French decree No 2015 1790 and or European regulation EU 517 2014 a leak test must be performed on the cooling circuit at least on...

Страница 6: ...inguisher near the work area No source of ignition No person carrying out work on a cooling system involving exposing the piping may use any ignition source which could create a fire or explosion risk...

Страница 7: ...er sources must be disconnected from the equipment on which the work is being carried out before removing the insulating cover etc If the equipment must be powered during maintenance work a leak detec...

Страница 8: ...efrigerant and cause corrosion to the copper piping If a leak is suspected all naked flames must be removed extinguished If a refrigerant leak is detected and requires soldering the entire quantity of...

Страница 9: ...k check the following points mechanical handling equipment is available if needed to handle the refrigerant cylinders all personal protective equipment is available and used correctly the recovery pro...

Страница 10: ...ecovery cylinder that is compatible with the refrigerant Make sure that the correct number of cylinders are provided for recovering all of the refrigerant All cylinders used must be intended for the r...

Страница 11: ...pose of reuse recycling or transformation If it contains any substances that may be harmful to the environment these will be eliminated or neutralised Contact your retailer for recycling information b...

Страница 12: ...act your retailer Write down your retailer s contact details to help you find them more easily and fill in the product information on the back of the manual your retailer will ask you for this informa...

Страница 13: ...installation on a roof a balcony or any other support Front Rear Anti vibration pads View of the appliance base from below for installing the anti vibration pads The appliance must not be installed W...

Страница 14: ...ass valve Water outlet valve Water inlet adjustment valve optional Water outlet adjustment valve optional Water treatment system To evacuate the condensates fit an internal 18 pipe under the appliance...

Страница 15: ...ed for connection to a general power supply with a TT or TN S neutral regime Electrical protection by circuit breaker D curve rating to be defined according to the table in 5 2 I Technical specificati...

Страница 16: ...g system Filtration is kept in operation or activated if the pool temperature falls below the desired temperature For the connection connect the filtration timer to terminals 1 and 2 dry contact no po...

Страница 17: ...s operation 24 7 To maintain the temperature throughout the season run automatic circulation for the equivalent of the water temperature divided by two the longer this time the more sufficient the ope...

Страница 18: ...ical part see 5 3 I Dimensions and marking Set the valves as follows valve B wide open valves A C D and E closed Water inlet valve By pass valve Water outlet valve Water inlet adjustment valve optiona...

Страница 19: ...utomatically once the temperature setpoint is reached Information HEATING COOLING mode automatic regulation When the HEATING COOLING operating mode is selected the PX50 heat pump automatically switche...

Страница 20: ...ating requirements and silent operation desired Cooling hot zones heat waves sheltered pools etc The compressor speed directly affects the appliance s power output Press BOOST SMART or SILENCE the ind...

Страница 21: ...k on the appliance you must cut the electricity supply as there is a risk of electric shock which may cause material damage serious injury or even death It is recommended that the appliance undergo ge...

Страница 22: ...n the minimum operating temperature The appliance is smoking The machine has come to the end of the defrost cycle water has changed to gaseous state and passes through the grid If your heat pump is no...

Страница 23: ...Check D3 Sensor disconnected or out of order Reconnect or replace the sensor PP10 Condenser cooling temperature too high protection Ambient temperature too high Check the temperature Refrigerant probl...

Страница 24: ...e phases Abnormal water flow rate Check the water flow rate Fluctuating power supply Check the electrical grid EE08 Communication error between the controller and the power board The connection is fau...

Страница 25: ...rinted circuit board The propellers are faulty Check the propellers EE18 Abnormal PFC module operating temperature The printed circuit board is faulty Replace the printed circuit board Check the fan s...

Страница 26: ...ockage inversion of the 4 way valve Switch to heating cooling mode to check inversion of the valve Replace the 4 way valve Low refrigerant no d5 TH2 or d3 TH1 detection Check refrigerant levels EE27 E...

Страница 27: ...25 4 3 I Wiring diagrams 25 4 3 1 PX50 MD3 MD4 MD5 MD6 MD7 EN...

Страница 28: ...26 4 3 2 PX50 MD9...

Страница 29: ...27 4 3 3 PX50 MD11 MD12 EN...

Страница 30: ...28 4 3 4 PX50 TD11 TD12...

Страница 31: ...iption A PX50 B 50 PVC connectors x2 C Anti vibration pads x4 D Winterising cover Heating priority E Remote control kit F Condensate drainage connector x2 G Hose x2 H PAC NET cleaning product Included...

Страница 32: ...45 Max High pressure Low pressure side bar 25 Average water flow rate m h 2 9 3 4 4 4 8 6 7 4 9 8 8 10 3 10 Sound pressure at 10 m db A 31 32 33 35 39 50 68 Refrigerant type R32 R410A R32 R410A Refri...

Страница 33: ...inlet Pool water outlet Evaporator Front E D Side F G H Top Model A B C D E F G H I J MD3 858 25 626 97 348 90 334 371 270 293 MD4 MD5 MD6 985 25 736 107 440 110 350 390 321 349 MD7 MD9 1073 25 927 1...

Страница 34: ......

Страница 35: ......

Страница 36: ...e owners Zodiac Pool Care Europe Bd de la Romanerie BP 90023 49180 St Barth l my d Anjou cedex S A S U au capital de 1 267 140 SIREN 395 068 679 RCS PARIS Votre revendeur Your retailer Mod le appareil...

Отзывы: